EVALUATION REPORT FLORIDA BUILDING CODE, fiT" EDITION (2017)
Manufacturer: TAMKO BUILDING PRODUCTS, INC.
P.O. Box 1404
,poplin, MO 64802
(417) 4-44
htti),//www-tamkc).com
Quality Assurance: LPL LL(QUA9625)
SCOPE
Category: Foofi ng
Subcategory: Underlant
Code Sections: 1 0 .1.1
Properties: Physical properties
PRODUCT DESCRIPTION
TAMKOV ASTM Slate
Surfaced Roll Roofing
TAMIKOV ASTMTile
Unaler lar ranant
T IVI KO Master
Smooth
Tl Ko Moisture
Guard@
T1 Ko No. 15 ASTM
Asphalt Saturated
Organic Felt
T KO o. 15 U L
Asphalt Saturated
Organic Felt
TAMIK00 No. 30 ASTM
Asphalt Saturated
Organic Felt
T MK No. 30 UL
Asphalt Saturated
Organic Felt
TAMKO@ TW Metal and
Tile Und rlameat
TAMIK00 TIC
U nd rla ment
Issued October 19, 2017
TM D 6380. Class M,
Type 11
undorla rnont constructed from
o r a n is felt saturated
with asphalt and coated
on both
sides with asphalt and surfaced
with granules.
TM U 6380, Class M, Typo 11 and rla meat constructed from an organic felt saturated
with asphalt then coated on both sides with asphalt and surfaced with granules.
T I D 6380, Class S, Typo IV and rla m nt constructed frorn are organic felt saturated
with asphalt then coated on both sides with asphalt alt and surfaced with a fine mineral. For
use in non-HVHZ only,
Self -adhered, ASTIVI D 1970, fiberglass reinforced, modified bitumen shoot membrane
with a mineral surfacing and a removable release film on the adhesive side and
removable selvedge release tape.
ASTM D 226, Type I u nderla ment constructed from a non -perforated organic felt that Is
saturated with asphalt.
ASTM D 226, Type I underlayment constructed from a nor -perforated organIG felt that i
saturated with asphalt.
49 J"F r2c �1-erd-
T I D 226, Type 11 and rla ment constructed from a non -perforated organic felt that i
saturated with asphalt.
TI I D 226, Typo II and rla ment constructed from a nor -perforated organic felt that i
saturated with asphalt.
Self
-adhered, flexible,
ASTM U 1970 and TAS 103,
rubberized
asphalt sleet m mhran
with
a polymer film on
the surface and a removable
release film
on the adhesive side.
Self -adhered, flexible, ASTM D 1970, rubberized asphalt shoot membrane with a
polymer film on the surface and a r rnovable release film on the adhesive side.
TB P 14001.4 FL 1 -FHB Page I of 4
This evaluation report is provided for State of Florida product approval under Rule I o- . The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance hang throughout the duration for wNch this report is vAd.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
TECHNICAL SERVICES, LLC
CR K
TAMTAMKO BUILDING PRODCUT , INC.
TAMKO Underla ments
T MKO TAM -FELT Alternate to ASTM
D 226,
Type I and Type
11 and rla ra nt constructed from a non -
perforated organic
felt that
is saturated with
asphalt,
APPLICATION METHOD
Installation shall be in accordancewith the published manufacturerys installation instructions, the FBC, and the
requirements below.
Deck substrates shall
be clean, dry,
and
free from any irregularities and debris. All fasteners in the deck shall b
checked for
protrusion
and corrected
prior
to undorla
rn rat
application.
The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. Plywood deck
shall be installed in accordance with FB r qui r ment . Roof docks shall have n more than 1 / p
� at abutti n
joints.
The minimum application temperature ha II be 0' F except as follows:
a) The minimum application temperature of T TW Metal and Tile Underlayment and TAMK0@ T1
nderla m nt shall be 40'F.
b) The minimum ppli ation temperature of TAMTAMK08 Moisture Gcard shall be 350F.
The minimum roof slope shall be in accordance with FBC requirements except as follows;
a The minimum slope of TAMKOO ASTIR Slate Surfaced Doll Roofing fin shall he :1.
Underlayments shall be exposed in accordance with the manufacturer's recommendations, but in no ease shall
exposure exceed 30 days.
Exception: T MKO TW Metal and Tile Underlayment may be exposed for a maximum 90 days.
Self -adhering u nderla ments may he adhered to primed or un primed plywood substrates in the Inca-H H .
All roof coverings shall be mechanically fastened through the underlayment to the roof deal.
Allowable Roof ov rind :
Metal Roof
Mineral
Asphalt
Panels and
Surfaced Roll
Underlayment
Shing.les
Shingles
Roofing
TAMKO8 ASTM Slate
Surfaced Doll Roofing
TAM KOO ASTM Tile
Underla meat
TAMKOO Master Smooth I Y' I N I N
7AMKQQ Moisture GuarctoD I y I N IN
TAM K00 No. 15 ASTM
Asphalt saturated Organic
Y
Y
Y
Felt
TAMKOe No, 15 UL Asphalt
Saturated Organic Felt
Y
TM KOO No. 30 ATM
Asphalt Saturated Organic
Y
Y
Y
felt
TAMIK00 No. 30 UL Asphalt
Saturated Organic Felt
Y
TAMKO@ TW Metal and Tile
Underla meat
Y
TAMFCQp TW L1nderlayment I Y I Y I N
TAMKO TAM -FELT I Y I N N
Pots F 1 ) Open valley applications per 1 o7...
Wood shingles only
Wood
hiingles a n d
Shakes
ff
N
N
Y2
Y2
Y
1
1
N
late
h i vales
N
N
N
N
Y
Y
Y
N
N
N
Clair and
Concrete Tile
Y
I
27
10j
Y
a
10
TB P 14001A FL12328-R8 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Ruin 61 o- . The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express ror imply warranty, installation, recommended use, or other product attributes that are not
specificalJy addressed herein.
�IGK
_ TECHNICAL SERVICES, LLC
LIMITATION
TAMKO BUILDING PF D uT , INC,
TAMKO Underlayments
1 Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance in not within scope of this evaluation.
3) installation of the evaluated product shall comply with this report. the FB ' and the manufacturer's publi hed
application instructions. there discrepancies exist between these sources, the more restrictive and FB
compliant installation detail shall prevail.
4) Contact the manufacturer when installing at temperatures below the minimum application temperature.
re.
5) pp �
Unless otherwise stated T the minimum roof slope shall be in aCGordance with FBC requirements.
6) All underla ment hail be installed with the reII length parallel to the cave. starting at the ea e, and lapped
in success«e courses installed up the deck in a manner that effectively sheds water from the deck. End
laps shall be staggered between courses in accordance with the manufacturer's application instructions.
7 The underlayment may be used as described in ether current FBC product approval documents.
8) The unde-layment shall not he installed over existing roof coverings.
9) Contact the manufacturer regarding specific exposure limits for each underlayment.
10) All products listed in this report shell be manufactured under a quality assurance program In compliance with
Rule 1 0- i
REFERENCES
Entity
PRI
Construction
ate ria h
PRI
Construction
Materials
PRI
Construction
Materials
PRI
Construction
Materials
PRI
Construction
Materials
PRI I
on tru do n
Materials
PRI
Construction
Materials
ria
PRI
Construction
Materials
PRI
Construction
Materials
PRI
Construction
Materials
PRI
Construction
Materials
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
{TST6049}
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
(TST6049)
Technologies
(TST6049)
PRI Construction Materials Technologies (TST6049)
PRI Construction Materials Technologies (TST6049)
PRI Construction Materials Technologies {TS76049}
PRI Construction Materials Technologies (T5T6049)
UL LLC (TST9628)
Report No.
Standard
Year
7AP-192-02-01
ASTM
D
1970
2015a
TAP-193-02-01
ASTM
D
1970
2015a
7AP-214-02-01
ASTM
0
4869
2016
TAP-295-02-01
ASTM
D
226
2009
TAP-216-02-03
ASTM
D
E380
2003(2013)
1'AP-217-02-01 REV
ASTM
b
6380
2003(2013)
TAP-218-02-01
ASTM
D
226
2009
TAP-219-02-01
ASTM
D
226
2009
TAP-220-02-01
ASTM
D
6380
2003(2013)
TAP-222-02-01
ASTM
b
4869
2016
TAP-245-02-01
TAS 103
1995
ASTM
D
4798
2011
TAP-311-02-01
ASTM
D
1970
2015a
TAB-319-02-01.1
ACC 188
2012
TAP-387-02-01
ASTM
D
1970
2015a
TAP-388-02-01
ASTM
D
1970
2015a
13CA12289
ASTM
D
226
2009
TBP 14001,E FL12328-R8 Page 3 of 4
This evaluation report is p molded for State of Florida product approval under Rule 61 0- . The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for whhch this report is valid.
This evaluation report does not express nor imply warranty, in taliation, recommended useT or other product attribute that are not
specifically addressed herein.
C R K
TECHNICAL SERVICES, LLC
TAMKO BUILDING PRODCUTS, INC.
TAMKO Underlayments
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida E u iU n
Code, Edition 01 ) as evidenced in the referenced documents submitted by the named manufacturer,
201721 Oa 19
12:150658
-04'00'
Zachary R. Priest, P*E,
Florida Registration No. 74021
Organization No. ANE9641
GERTiFICATION OF INDEPENDENCE
R E E K Technical Services, LLC does not have, rear real it acquire. a financial interest in and company manufacturing or distributing products under this
evaluation.
R E EK Tech nica l 9 e ryi ces, LLC i s not owned, op crated, or con trolled by any com pa n y man ufaeturing a r dis trib uting p rod ucts u nde r this evaluatic n ,
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation.
Zachary R, Priest, P-E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product.
AND OF REPORT
TBP 14001.4 FL12328-R8 Page 4 of 4
This evaluation report is provided for state of Florida product approval under Rule 1 0- . The manufacturer shall notify CREEK
Technical Services, LLC of any product charges or quality assurance changes throughout the duration for which this report is valid-
Thi's evaluation report does not express nor imply warranty, Installation, recommended use, or other product attributes that are, not
specifically addressed herein.