HomeMy WebLinkAboutGenerator Specificationse
General Information
Specifications
Generator
Model
9 kW
11 kW
16 kW
20 kW
22 kW
Rated Voltage
240
Rated Maximum Load
Current (Amps) at Rated
37.5
45.8
66.6
83.3
91.7
Voltage with LP'
Main Line Circuit Breaker
40Amp
50Amp
70Amp
100Amp
100Amp
(Generator Disconnect)
Phase
1
Rated AC Frequency
60 Hz
Battery Requirement
12 volts, Group 26R-540CCA Minimum or Group 35AGM-650CCA Minimum
(Field supplied)
(see Replacement Parts)
Enclosure
Aluminum
Weight (lbs/kilos)
340/164
3481158
409/186
448/203
466/211
(without battery)
This unit is tested In accordance to UL 2200 standards with an operating temperature of -20 °F (-29 °C) to 122 °F
Normal Operating Range
(50 °C). For areas where temperatures fall below 32 °F (0 °C) a cold weather kit is recommended. When operated
above 77 °F (25 °C) there may be a decrease in engine power. See Engine.
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine GeneratorAssemblies, and CSA-C22.2 No. 100-04
Standard for Motors and Generators.
Natural Gas ratings will depend on specific fuel joules/BTU content. Typical derates are between 10-20% off the LP gas rating.
Engine
Model
9 kW
11 kW
16/20122 kW
Type of Engine
GH-426
GTH-530
GT-999
Number of Cylinders
1
2
2
Displacement
426 cc
530 cc
999 cc
Cylinder Block
Aluminum w/ cast iron sleeve
Recommended Spark Plug
See Replacement Parts
Spark Plug Gap
0.020 in (0.508 mm)
0.030 in (0.76 mm)
0.040 in (1.02 mm)
Valve Clearance
0.002-0.004 in
(0.05-0.1 mm)
0.002-0.004 in
(0.05-0.1 mm)
0.002-0.004 in
(0.05-0.1 mm)
Starter
12 VDC
Oil Capacity Including Filter
Approx. 1.1 qt (1.03 L)
Approx. 1.7 qt (1.6 L)
Approx. 1.9 qt (1.8 L)
Recommended Oil Filter
See Replacement Parts
Recommended Air Filter
See Replacement Parts
Engine power is subject to and limited by such factors as fuel BTUrloules, ambient temperature and altitude. Engine power decreases about 3.5% for
each 1000 ft (304.8 m) above sea level, and also will decrease about 1 % for each 10 °F (6 °C) above 60 °F (15 °C) ambient temperature.
The specification sheet for your generator was included in the documentation provided with the unit at the time of
purchase. For additional copies, consult your local Independent Authorized Service Dealer (IASD) for your specific
generator model.
Owner's Manual for 60 Hz Air -Cooled Generators
General Information
001786
Figure 2-2. llkW--22kW—Components and Control Locations
A.
Lock with Cover
E.
Battery Compartment
J.
Oil Fill Cap
N.
Sediment Trap
(Battery not supplied)
B.
Main Line Circuit
F.
Exhaust Enclosure
K.
Oil Filter
O.
Fuel Regulator
Breaker (Generator
Disconnect)
C.
Airbox with Air Cleaner
G.
Status LED Indicators
L.
Composite Base
P.
Fuel Inlet
D.
Control Panel
H.
Oil Drain
M.
Oil Dipstick
Q.
Data Plate Location
6
Owner's Manual for 60 Hz Air -Cooled Generators