HomeMy WebLinkAboutS Platt Engineering Seal0 0 r�) M M ROLL —UP -----DOOff--------- 1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING. BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS. 2. THIS STRUCTURE IS DESIGNED AS A NON —HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE APPLICATION OF ADDITIONAL LOADS. 3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2. 4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15. 5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE RESPONSIBILITY OF THE OWNER. 6. ROOF AND WALL SHEATHING SECURED WITH #12-14x1" SELF —DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX. 7. FIELD FRAMING CONNECTIONS SECURED WITH #12-140/4" SELF —DRILLING SCREWS. 8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP. 9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,50OLB TENSILE STRENGTH. 10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL. SUB —GRADE SOILS: —TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION —MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS —ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE DESIGNED TO SLOPE AWAY FROM THE STRUCTURE —MINIMUM GRADE 40 STEEL —REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED: —THE REBAR IS BENT COLD —THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED 6—BAR DIAMETERS: AND —REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1" HORIZONTALLY TO 6" VERTICALLY. —COVER: —2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY IN CONTACT WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF J" FOR FINE GROUT, AND 4" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL. REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR WEATHER. GALVANIZATION: —METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153, CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED. MIN. 2,500 PSI 4" CONCRETE SLAB WITH W.W.F. (OR FIBER MESH) AND 12"x12" REINFORCED FOOTER PERIMETER -------BOLL— UP------------------------------------------------------------RQLL---UP- DOOR DOOR M M 4%54" EXPANSION ANCHOR WITHIN 6" OF EACH POST/TRUSS ALONG SIDES AND EVERY OTHER END —WALL POST 2" MIN.- GRAD _ MINIMUM SOIL BEARING CAPACITY 2,000 PSF(TYP.) E RAIL N Z2I ,500 PSI 4" CONCRETE SLAB W.W.F. OR FIBER (2) #5 REBAR ® 6" O.C. CONTINUOUS WITH MINIMUM 12" OVERLAP SPLICE CONCRETE FOUNDATION/BASE RAIL ANCHOR DETAIL 2 5" PLAN VIEW DOOR FRAMING J" RECESS 4" OOR WIDTH ELEVATION VIEW DOOR FRAMING " RECESS .751 4" OOR WIDTH OPTIONAL ROLL -UP DOOR CONCRETE SPLASH -GUARD RECESS 12"x12" REINFORCED FOOTER ------------------------------- � -------------------SM G+NI&------------ DOOR 3'-0" 4'-1 12" 1 I I I I CODE VERSION FBC 2017 6th Editiol ASCE-7-10 MANUFACTURER CARPORTS ANYWHERE BUILDING TYPE UTILITY STRUCTURE CONSTRUCTION TYPE II—B RISK CATEGORY I FIRE PROTECTION NONE FIRE SUPPRESSION SYSTEM NONE OCCUPANCY UTILITY, U WIND SPEED VUIt-165mah ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/— 0.18 IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 1OPSF ROOF LIVE LOAD 20PSF OR 3001b P.L. FLOOR DEAD LOAD 1OPSF FLOOR LIVE LOAD 50PSF "R"RATING OF WALLS, FLOOR, ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO SQUARE FOOTAGE 1,200 SQ. FT. STUB —UP DATE MTB 3/6/20 220 Emerald Ave., Ft. Pierce ISIZE 401 X 30'W X 12'H II t _ t.:7- W } z Matthew T. Baldwin P.E. Q Florida License #64608 6j I F Sheet: CA-1 OF 4 12 o ,o'Aga RPUR ANYII IERE CODE INFORMATION CODE VERSION FBC 2017 6th Edition ASCE-7-10 MANUFACTURER CARPORTS ANYWHERE BUILDING TYPE UTILITY STRUCTURE O CONSTRUCTION TYPE II-B b RISK CATEGORY I r FIRE PROTECTION NONE FIRE SUPPRESSION SYSTEM NONE OCCUPANCY UTILITY, U WIND SPEED Vult-165mph EXPOSURE B ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/- 0.18 IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 10PSF 30'-0ROOF LIVE LOAD 20PSF OR 3001b P.L. FRONT/REAR END WALL FLOOR DEAD LOAD 1OPSF FLOOR LIVE LOAD 50PSF 1 •-o' "R"RATING OF WALLS,FLOOR,ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO D.C. MAX. 22 2 -o" 10'-0` 0 I 0 ROLL -UP DOOR 2 10'-0' 0 � 0 ROLL -UP DOOR m .I SWINGING DOOR 3 -0' p� 2 a._0. SQUARE FOOTAGE 1,200 SQ. FT. REVISIONS REV DESCRIPTON DATE BY 1 NO STUB -UP 3/9/20 MTB 0 I N DRAWN er: MTB DATE' 3/6/20 LOCATION: 220 Emerald Ave., Ft. Pierce SIZE' 40'L X 30'W X 12'H LEFT SIDE WALL 10'-0' O.C. MAX_ O O ROLL -UP DOOR t3 n LLI LLI Matthew T. BaldWin P.E. Florida License #64608 RIGHT SIDE WALL _ Sheet: CA-2 OF 4 MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH SC) 12 14xi" SELF —DRILLING 147/ NIPPLE TO V � BASE RAIL NIPPLE T BASE RAI MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH (4)#12-14xj" SELF —DRILLING SCREWS 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xi" SELF —DRILLING SCREWS POST TO BASE RAIL END POST TO BASE RAIL CONNECTION CONNECTION 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xi" SELF —DRILLING SCREWS NON-STRUCTURAL HEADER OR WINDOW RAIL TO POST DETAIL INTERIOR #12-14xj" SELF —DRILLING SCREWS 0 10" O.C. MAX., 3" MAX. FROM CORNERS HORIZONTALLY/ 4" MAX. FROM CORNERS VERTICALLI EXTERIOR DOOR FRAME TO POST CONNECTION 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xj" SELF —DRILLING SCREWS 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xj" SELF —DRILLING SCREWS SINGLE OR DOUBLETS HEADER INTERMEDIATE POST TO HEADER/BASE RAIL/OR HEADER CONNECTIO WINDOW RAIL DETAIL DETAIL OPTION 1 2"xZx2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xj" SELF —DRILLING MAX. SPAW r--3" MIN. MAX. SPACING VARIES SIDE WALL ROLL -UP DOOR/FRAME OUT HEADER DETAIL INSTALL PER MANUFACTURERS INSTRUCTIONS #14x1" SELF —DRILLING SCREWS ® 6" O.C. MAX. & 6" MAX. FROM CORNERS ROLL -UP DOOR TO POST CONNECTION DESIGN PRESSURES - 165 Mph ROOF +24.6/-54.3 WALLS +28.9/-31.8 DOORS +28.9/-31.8 WINDOWS +28.9/-31.8 1 2 3 4 5 ZONE + 12.4 -27.7 + 15.5 -42.3 +24.6 -54.3 +27.8 -29.8 +28.9 -31.8 26 GAUGE ROOF SHEATHING SECURED WITH (1)#12-14xj" SELF —DRILLING SCREWS '2-1-2-1' (6" O.C. (9" D.C. MAX.)) ,a" OW — 1" 16 GAUGE FURRING CHANNEL 48" O.C. MAX. SECURED WITH (2)#12-14x1" SELF —DRILLING SCREWS TO EACH RAFTER. ROOF PANEL CONNECTION VERTICAL SHEATHING OPTION TO 7 16 GA. U—CHANNEL BRACE, MIN. 24" UP TO 7' POST, MIN. 48" OVEF 7' POST. MIN. 45' TO MAX. 60' FROM HORIZ. (EXCLUDE END —WALLS) MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH (4)#12-144" SELF —DRILLING SCREWS BOX EAVE RAFTER TO POST CONNECTION DETAIL IPPLE MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH 12-14xj" SELF —DRILLING EWS SINGLE OR DOUBLETS HEADER HEADER CONNECTION DETAIL OPTION 2 NIPP TO TRU NIPPLE TRUSSED RAFTER CONNECTION DETAIL MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH (4)#12-14x4" SELF —DRILLING SCREWS POST TO TRUSS CONNECTION APPROVED PRODUCTS APPROVAL NO. ROOF SHEATHING Carports Anywhere FL27402.1—R1 Hampton Rib Roof Panel WALL SHEATHING Carports Anywhere FL27403.1 Hampton Rib Wall Panel SWINGING DOOR ELIXER DOOR AND METAL COMPANY FL17996.5 407 STEEL DOOR ROLL —UP DOOR JANUS INTERNATIONAL CORPORATION FL12765.3—R5 SERIES 3100 O 0 11111 i 1 ► (CODE VERSION IFBC 2017 6th Edition,ll Ieccr-7—tn BUILDING TYPE UTILITY STRUCTURE CONSTRUCTION TYPE II—B RISK CATEGORY 1 FIRE PROTECTION NONE FIRE SUPPRESSION SYSTEM NONE OCCUPANCY UTILITY, U WIND SPEED Vult-165mph ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/— 0.18 IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 1OPSF ROOF LIVE LOAD 20PSF OR 3001b P.L. FLOOR DEAD LOAD 1OPSF FLOOR LIVE LOAD 50PSF VRATING OF WALLS, FLOOR, ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO SQUARE FOOTAGE 1,200 SQ. FT. REVISIONS NO STUB —UP MTB 3/6/20 220 Emerald Ave., Ft. Pierce IS¢E: 40'L X 30'W X 12'H II �tttT� It t (iKt`Tf.._ c'' - ` a � 9. ' (n Q Matthew T. Baldwin P.E. Florida License #64608 Q Sheet: CA-4 OF 4