HomeMy WebLinkAboutProject Informationwrightsoft Project SummaryJab' Date: Apr 01, 2020 Entire House • By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE. FL 34946 Phone: 772-465-6799 Fax 772-48"795 Egad: OUICKCALCS@AOL.COM Project• • For. PHILLIPPE RESIDENCE PALM DRIVE, FORT PIERCE, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gdlb Heating Summary Sensible Cooling Equipment Load Sizing Structure 27560 Btuh Structure 23079 Btuh Ducts 8478 Btuh Ducts 12095 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh e) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 36038 Btuh Use manufacturers data n Ratelswing multiplier Equipment load 0.95 33415 Btuh Infiltration sensible Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4217 Btuh Ducts 3355 Btuh Central vent (0 cfm) 0 Btuh Heatingg Cooling (none) Area (ft�) 2357 2357 Equipment latent load 7571 Btuh Volume (ft3) 24389 24389 Airchangeslhour 0.32 0.16 Equipment Total Load (Sen+Lat) 40987 Btuh Equiv. AVF (cfm) 130 65 Req, total capacity at 0.70 SHR 4.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIER Model Cond CA16NA04800GOBO AHRI ref Coil FX4DNF061L AHRI ref 202025347 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 9.5 kW Sensible cooling 32650 Btuh Heating output 32440 Btuh Latent cooling 13950 Btuh Temperature rise 19 OF Total cooling 46500 Btuh Actual airflow 1550 cfm Actual airflow 1550 cfm Air flow factor 0.043 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ' wri`gt%esoft' 2o20-Apr-0115:01:44 '�- ••••+•-•+— •—• RlghtSuBe® Uniwma1201919.0.08 RSU08101 Page 1 ZCK ... ocumnetslWrigMsoft WACIPHILIPPE RESIDENCEmp Calc - MJ8 Front Door faces: W wrightsofC Right-M Worksheet Job. Entire House Date: Apr 01, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466.6796 Emil: QUICKCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 207.6 ft 34.0 ft 3 Room height 10.3 ft 11.0 ft heat/coal 4 Room dimensions 17.0 x 17.0 it 5 Room area 2357.0 ft- 289.0 fN Ty Construction number U-valuo (BluNO'-°F) Or HTM (Btuh/W) Area (fi or perimeter (ft) Load (Btuh) Area (ft.) or perimeter (ft) Load (Btuh) Heat Caul Grass N/P/S Heal Cool Grass NIP/S Heat Cool 6 UN I��G4oc 13As 2 glazing clr Iowa 2 glazing clr low 0.143 0.650 0.650 n n n 4.00 18.20 18.20 2.19 14.99 14:99 611 20 99 495 0 0 1982 354 1747 1083 300 1439 187 0 48 139 0 0 557 0 974 304 0 720 V�! �C T�C 11 13A4ecs 2 glazing clr low-e 0.143 0.650 a a 4.00 18.20 2.19 33.77 510 9 441 0 1766 164 965 304 0 0 0 0 0 0 0 0 W �G 2 alazina clr la -e 13A41xs 2 glazing, air Icw-e 0.650 0.143 0.650 a as as 18.20 4.00 18.20 33.77 2.19 23.80 60 28 8 0 20 _ 4 1092 at 146 2026 44 190 0 0 0 0 0 0 0 0 0 0 0 0 ty 13A4ocs 2 glazing, clr law-e 0.143 0.650 s s 4.20 18.00 4.19 12.19 3%12 12 24 224 022 1218 558 180 0 0 0 0 0 0 0 0 2 glazing Or low-e 2 glazing clr low-e 2 glazing clr low-e 0.650 0.650 0.650 s s s 18.20 18.20 18.20 14.99 14.99 14.99 20 20 48 41 41 96 372 372 974 306 306 720 0 0 0 0 0 0 0 0 0 0 0 0 W I--G 13A4ocs 2 glazing, cir bwe 0.143 0.650 sw sw 4.00 18.20 2.19 23.80 29 8 20 4 81 146 44 190 0 0 0 0 0 0 0 0 W (LI�--GGG 13A4ocs 2 glazing ch Iowa 2 glazing clr low -a 0.143 0.650 0.650 w w w 4.00 18.20 18.20 2.19 33.77 33.77 607 9 20 558 0 0 2234 164 364 1221 304 675 187 0 20 167 0 0 669 0 364 365 0 675 C 29lazina co- aw-e 161330ad 0.650 0.032, w - 18.20 0.90 33.77 1.60 20 2357 0 2357 366 2112 679 3771 0 _ 289 0 289 0 259 a 462 F 22Atph 1.358 - 38.02 0.00 2357 208 78M 0 289 34 12M 0 6 c)PED emursion 0 76 Envelope loss/gain 235M 15307 4015 2603 12 a) Infiltration 40M 1072 699 197 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 6700 300 Subtotal (lines 6 to 13) 27560 23079 4714 3090 Less a denial load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 5 6 14 Subtotal 27560 23079 4719 3099 15 Duct loads 31% 52% 8478 12095 31% 52% 1452 1624 Total room load 38038 35174 6170 4723 Air required (cfm) 1550 1550 265 208 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -Of&- wrl-gnisoTt- 2020-Apr-o1 15:01:44 RightSuite(DUniversal 20l9lg.0.OB RSU09101 Page 1 ...ocumnets4Wrightsoft WACIPHILIPPE RESIDENCE rup Calc=MJB Front Door faces: W wrightsoft Right-l®Worksheet Job: Entire House Bate: Apr 01, 2020 BY: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-46&6799 Far 772-466-6796 Email: gU1CKCALCS@AOL.COM 1 Room name M W IC 1 M W IC 2 2 Exposed wall 7.0 It 0 It 3 Room height 10.0 it heat/mal 10.0 it heat/cocl 4 5 Room dimensions Room area 5.0 x 7.0 it 35.0 fN 4.0 x 6.0 it 24.0 It' Ty Construction U- Iue Or HTM Area (ft') Load Area (w) Load number (etuhlfl'= F) (Stuhlft) or perimeter (H) latuh) or perimeter (fl) (Btuh) Heat Cool Gross NIP/S Heat Cool Grass N/P/5 Heat Cool 6 V71 13A4ccs 2 glazing, airlow-e 2 glazing, air lava 0.143 (LM 0.650 n n n 4:00 18.20 18.20 2.19 14.99 14:99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I�-GG U�! E--f 11 13A4ocs 2 glazing, cU Iowa 0.143 0.650 a a 4.00 18.20 2.19 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �-C W L--(' 2 alazina, cU low-e 13A4ocs 2 glazing, air law-e 0.650 0.143 0.650 a se se 18.20 4.00 18.20 33.77 2.19 23.80 0 0 0 0 0 0 0 0 0 0 0 _ 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 YYYVVY������111111 13A4acs 2 glazing, clr low -a 0.143 O.650 s s 4.00 18.20 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, air Iowa 2 glazing, air Iowa 2 glazing, an Iowa 0.650 0.650 0.650 s s s 18.20 16.20 18.20 14.99 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V71 L-C 13A-0acs 2 glazing, c4lava 0.143 _ 0.650 sw sw 4.00 18.20 2.19 23.80 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V)I ILA--GGG 13A-0acs 2 glazing, ch lava 2 glazing ct Iowa 0.650 0.&90 0.650 w w w 4.20 1&20 1&20 33.77 3.77 33.77 70 0 0 70 0 0 280 0 0 153 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C 2 glazina, co- lama 16B-30ad 0.650 0.032 w - 10.20 (X90 33.77 1:60 0 35 0 35 0 31 0 55 0 24 0 24 0 _ 22 0 38 F 22Atph _ 1.358 3&02 0.00 35 7 266 0 24 0 0 0 61 c)AED excursion .17 Al Emelops loss/gain 578 192 22 28 12 a) Infiltration 131 35 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 300 300 Subtotal Pines 6 to 13) 709 527 22 328 Less eMen d lead 0 0 0 0 Less transfer 0 0 0 0 Redistdbution 0 0 7 11 14 Subtotal 709 527 28 339 15 Duct loads 31% 52% 218 276 31% 52% 9 176 Total room load 927 803 37 517 Air required (cfm) 40 35 2 23 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -rl d- wrlghtr f!- 2020-Apr-01 15:01:44 .EGA '• RlghtSuite® Universal 201919.0.08 RSU08101 Page 2 ...ocunnets\Wrightsoft HVACIPHILIPPE RESIDENCErup Calc = MJB Front Door faces: W wrightsof ' Right-l@ Worksheet Job. Entire House Date: Apr 01, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Roam name M HALL LPIFSI 2 FVosed wall a ft O ft 3 Room height 10.0 It heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 4.0 x 4.0 It 16.0 ft. 4.0 x 2.0 ft 8.0 fN Ty Construction U i Iue Or HTM Area (ft') Load Area (ft-) Load number (Btuh/WF) (Btuh/fN) or perimeter (ft) (Bluh) or perimeter (it) (Btuh) Heat Cool Gross NIP/S Heat Cool Gross NIP/S Heat Cool 5 1q/ 13A4ccs 2 glazing, clr low-e 2 glazing, clr Iowa 0.143 0.650 0.650 n n a 4.00 18.20 18.20 2.19 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 II---�!'' �7 �C T�mmm-CCGG 1 t 13AAocs 2 glazing, clr lave 0.143 0.650 a a 4.00 18.20 2.19 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 t-G 2 alazina clr lave 13A4ocs 2 glazing, clr Im-e 0.650 0.143 0.650 a as as 16.20 4.00 18.20 33.77 2.19 23.80 0 0 0 0 0 0 0 a 0 0 0 0 0 0 0 0 0 0 0 a 0 0 a 0 2 glaflocs 2 glazing, cU bwa 0.650 0.650 s s 18.20 8.20 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, or Iowa 2 glazing, clr Iowa 2 glazing, ci Iowa 0.650 0.650 0.550 s s s 18.20 18.20 18.20 14.99 14.99 14.99 0 0 0 a 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 VN I--G 13A4ocs 2 glazing, ca.Iawa 0.143 0.650 sw sw 4.00 18.20 2.19 23.80 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N1aA-4ccs 2 glazing, ch lava 2 glazing, ch Iowa 0.143 0.650 0.650 w w w 4.00 18.20 18.20 2.19 33.77 33.77 0 0 0 0 0 0 0 0 0 0 0 0 a a 0 0 0 0 0 0 0 0 0 0 C 2 glazina. clr lava 1683aad 0.650 0.032 w - 1820 0.90 33.77 1.60- 0 16 0 16 0 14 0 26 0 8 0 8 0 7 0 13 F 22ASph 1.358 - 38.02 0.00 16 0 0 0 e 0 0 0 6 c)AED excursion -1 0 Envelops loss/gain 14 25 7 12 12 a) infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal Vines 6to 13) 14 25 7 12 Less exemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -14 -25 -7 -12 14 Subtotal 0 0 0 0 15 Duct loads 1 31% 52% 0 0 31% 52% 0 0 Total room load 0 0 0 0 Air required(ofm) 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. t\ -PW wrlghtooft- 2020-Apr-01 15:01:44 w RlghtSulte®Unlvemel 201g 19.0,08 RSU08101 Page 3 ...ocumnetslWrightsoft HVACIPHILIPPE RESIDENCE rup Colo =MIA Front Door faces: W vvrightsoft Right-J@ Worksheet Job: Entire House Date: Apr 01, 2020 eY: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-456-6799 Fez 772-466-8796 Emil: OUICKCALCS@AOL.COM 1 Room name M TOILET M BATH 2 3 E)q)osed wall Room height 6.0 ft 10.0 ft heat/cool 31.6 ft 10.0 ft heat/cool 4 5 Room dimensions Room area 5.0 x 6.0 ft 30.0 ft2 1.0 x 237.0 ft 237.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft'-OF) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P1S Heat Cool Gross N/P1S Heat Cool 6 4)1.. _ 13A ncs 2 glazing, clr low-e 2 glazing, clr Iowa 0.143 0.650 0.650 n n In 4.00 18.20 18.20 2.19 14.99 14.99 0 . 0 0 0 0 0 0 0 0 0 0 0 0- 0 0 0 0 0 0 0 0 0 0 0 11 13AAocs 2 glazing, clr low -a 0.143 0.650 a a 4.00 18.20 2.19 33.77 0 0 0 0 0 0 0 0 60 0 60 0 _ 240 0 131 0 1---G ttt---GGG U+/ L-C 2 alazinq, clr Iowa 13A-4ocs 2 glazing, Or Iowa,. 13A-4ocs 2 glazing, clr Iowa 2 glazing, clr Iowa 2 glazing, clr Iowa 2 glazing, clr lows 13A-0ws 2glazing, clr li 13A-4ms 2 glazing, ctr Iowa 2 glazing, clr low¢ 2 glazing clr Iowa 16B30ad 0.650 0.143 0.650 0.143 0.650 0.650 0.650 0.650 0:143 0.650 0.143 0.650 0.650 0.650 0.032 a se se s s s s s sw sw, w w w w - 18.20 4.00 18.20 4.00 19.20 18.20 18.20 18.20 4M 18.20 4.D0 18.20 18.20 18.20 0.90 33.77 -2.19 23.80 2.19 14.99 14.99 14.99 14.99 2.19 23.80 2.19 33.77 33.77 33.77 1.60 0 0 0 0 0 0 0 0 0 '0 60 0 0 0 30 0 0 .0 0 0 0 0 0 0 0 60 0 0 0 30 0 0 ' 0 0 0 0 0 0 0 0 240 0 0 0 27 0 0 0 0 0 0 0 0 0 0 131 0 0 0 48 0 28 8 80 12 0 0 0 28 8 120 0 0 0 237 0 20. 2 68 12 0 0 0 20 2' 120 0 0 0 237 0 81 146 272 218 0 0 0 81 146 480 0 0 0 212 0 44 190 149 180 0 0 0 44 190 263 0 0 0 379 UUU��tJJJ t-G W I--C �C F _ 22Atph 1.358 - 38.02 0.00 30 6 _ 228 0 237 32 1201 0 6 c)AED excursion -16 -54 Envelope loss/gain 495 153 3078 1517 12 a) Infiltration 112 30 592 159 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 300 0 Subtotal (lines 6 to 13) 607 493 3670 1676 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 607 493 3670 1676 15 Duct cad 1 31% 52% 187 259 31% 52% 1129 878 Total room load I 1 794 1 752 4799 2554 Air required (cfm) 34 33 206 113 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ,c wrLgn - t- 2020-Apr-0115:01:44 "- tt^ RlghtSulte® Universal 201919,0,0a RSU08101 Page 4 ... ocumnets\Wdghtsoft HVAC1PHILIPPERESIDENCE.mp Cale=MJB Front Doorfaces: W wrightsofr Right-M Worksheet Job: Entire House Bete: Apr 01, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772.466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIANG ROOM OFFICE 2 Eposed wall 16.0 It 10.0 It 3 Room height 11.0 ft heaVccol 10.0 ft heat/cool 4 5 Room dimensions Room area 16.0 x 13.0 It 208.0 fl' 10.0 x 13.0 it 130.0 fN Ty Construction U-value Or HTM Area (fN) Lead Area (ft.) Load number (BtuhlftW) (BtuWfl') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIPIS Heat Cool Grass N/PIS Heat Cool 6 Vpl 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, air Iowa 0.550 n 18.20 14.99 0 0 0 0 0 0 0 0 II----GG 2 glazing, air Iowa 0.650 n 18.20 14.99 0 a 0 0 0 0 0 0 13AAacs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 11 2 glazing, air Iowa 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 clazina. clr Iowa 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AAccs 0.143 se 4.00 2.19 0 0 0 0 0 0 0 0 �C 2 glazing clr Iowa 0.650 se 18.20 23.80 0 0 0 0 0 0 0 0 2 glazing, clr Iowa 2 glazing, 0.650 O.fi50 s s 4.20 18.20 4.19 14.99 17a 0 100 0 431 0 230 0 100 0 B0 0 310 0 174 0 2 glazing, air Iowa 2 glazing, clr Iowa 0.650 0.650 s s 18.20 18.20 14.99 14.99 0 20 0 20 0 372 0 306 20 0 20 0 372 0 306 0 2 glazing, air Iowa 0.650 s 18.20 14.99 48 48 974 720 0 0 0 0 W 13A-0ocs 0.143 sw 4.00 2.19 0 0 0 0 0 0 0 0 T-C 2 glazing, clr Iowa 0.650 sw 18.20 23.80 0 0 0 0 0 0 0 0 Vi! 2 gamin s 2 glazing, ctr Iowa 0.650 O.&90 w w 4.20 18.20 3.77 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing cU Iowa 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 LIB--GGG 2 glazing, air Iowa 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 "C 1613-30ad 0.032 - 0.90 1.60 208 208 185 333 - 130 130 116 208 F 22A-tph 1.356 - 38.02 0.00 208 16 SOB 0 130 10 380 0 6 c)AED excursion -28 -05 Envelope loss/gain 2471 1566 11871 643 12 a) Infiltration 329 88 187 50 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 700 Subtotal (lines 6lc 13) 2800 1654 1374 1393 Less e)demal lead 0 0 0 0 Less transfer 0 0 0 0 Redistribution 4 6 0 0 14 Subtotal 2803 1660 1374 1393 15 Duct loads 31 % 52 % 862 670 31 % 52 % 423 730 Total room load 3666 2530 i 1797 1 2123 Air required (cfm) 158 Ill 77 94 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. c -PW wrlghtsoTe- 2020-Apr-0115:01:44 �� '- RlghtSuita® Universal 201919.0.08 RSU08101 Page 5 ...ocumnetslWdghtsog HVAC1PHILIPPE RESIDENCE Calc=MA Front Door faces: W +�! wrightsofr RighW@ Worksheet Job' Entire House Date: Apr 01, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: gUCKCALCS@AOL.COM 1 Room name DINING ROOM KITCHENIFAMILY 2 E)pcsed wall 14.0 ft 8.0 ft 3 Room height 11.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 14.0 x 23.0 ft 14.0 x 23.0 ft 5 Room area 322.0 W 322.0 W Ty Construction U-value Or HTM Area (w) Load Area (it') Load number (BtutdfP--°F) StuhlfP) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIP/S Heat Cool Gross NIPIS Heat Cool 6 y! 13AAocs .0.143 n 4,00 2.19 154 106 424 232 80 60 2,40 131 2 glazing, ctr low-e 2 glazing, clr love 0.650 0.650 n n 18.20 18.20 14.99 14.99 0 48 0 0 0 974 D 720 20 0 0 0 364 0 300 0 V�! 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 11 ♦---G 2 glazing, clr low-e 0.650 a 18.20 33.77 0 o a 0 0 0 0 0 �--G I r 2 olazina clr low-e 13A-4ocs 2glazing. cIr kw� 0.650 0.143 0.650 a se se 18.20 4.00 18.20 33.77 2.19 23.80 0 0 0 0 0 0 0 0 a 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, Or hw�e 2 gl&ns 0.650 0.650 s s 4.20 18.20 4.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing clr low-e 2 glazing, clr'low-e 2 glazing, clr low-e 0.650 0.650 0.650 s s s 18.20 18.20 18.20 14.99 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Utl 13A-4acs 0.143 sw 4.00 -2.19 0. 0 D 0 0 0 0 0 L--C 2 glazing, ck low-e 0.650 . sw 18.20 23.90 D 0 0 0 0 ,. 0 0 0 1�y 13Adocs 0.650 w 4.20 0 0 0 0 0 0 0 0 2 glazing ch Iowa 0.650 w 18.20 3.77 33.77 0 0 0 0 0 0 2 glazing ch bw� 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 0 0 I���-GG C 2 glazing cir Igwe 16B30ad 0.650 0.032 w - 18.20 0.90 33.77 1.60 0 322 0 322 0 289 0 - 515 0 322 0 , 322 0 289 0 515 F 22Atph 1.358 - 39.02 0.00 322 14 532 0 322 8 304 0 6 c)AED excursion -95 -87 Enelope loss/gain 2119 1371 1197 859 12 a) Infiltration 28B 77 150 40 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 1500 1800 Subtotal (lines 6 to 13) 2407 2948 1347 2699 Less ademal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 7 11 325 375 14 Subtotal 2413 2960 1871 3074 15 Duct loads 31% 52% 742 1551 31% 52% 514 1611 Total room load 3156 4511 2185 4685 Air required (cfm) 136 199 94 205 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. Right-wrYghtsofC` 2020-Apr-0115:01:44 .Zc-N HILIPP uiREte@ Universal Y919 19.0.08 J8 Front Page 6 ...acumne[sVWrigMsoft HVAC1PHILIPPE RESIDENCE Calc=MJB Front Door faces: W wrightsoft RighW@ Worksheet Job: Entire House Date: Apr 01, 2020 QUICK CALCS, INC. 317 5T LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-8799 Fes 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Rom name LAUNDRY BEDROOM 2 2 E)pmed wall 0 If 10.0 It 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 7.0 x 7.0 If 1.0 x 138.0 It 5 Room area 49.0 fN 138.0 IF Ty Construction U- lue Or HTM Area (fe) Load Area (fP) Load number (Btuh/fP-°F) (BtuhBN) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross Ni Heat Cool Gross N/P/S Heat Cool 6 4}/ 13A4ocs 0,143 n 4.00 2.19 0 0 - 0 0 0 0 0 0 2 glazing, cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 L�GG 2 glazing; clr low-e 0.650 n_ 18.20 14.99 0 0 0 0 0 0 0 0 �1 1 13A-0oos 2 glazing, clr low-e 0.143 0.650 a a 4.00 18.20 2.19 33.77 0 0 0 0 0 0 0 0 100 0 80 0 320 0 175 0 tR/ 2 elazinp, clr low-e 13A-4ocs 2 glazing„clr Iowa 0.650 0.143 0.650 a se se 18.20 4.00 18.20 33.77 2.19 23.80 0 0 0 0 0 0, 0 D _-0' 0 0 0 20 0 0 0 0 0 364 0 0 675 0 0 Uy 13A-0ocs 2 glazing, cir Iowa 0.143 0.650 s s 4. 18020 2.19 1.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, cir Iowa 2 glazing, clr Irnva 0.650 0.650 s s 18.20 18.20 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, clr Iowa 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 UN 13AAocs. 2 glazing, clr, Icua 0.143 0.650 sw sw 4.00 _ 10.20 2,19 23.80 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 1y 13Adocs 0. w 4.00 .19 0 0 0 0 0 0 0 0 2 glazing, ch' bwe 2 glazing, ch low-e 0.650650 0.650 w w 18.20 18.20 33.77 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L��---GGG 2 gI-30ad ct Iowa 0.G50 w 10.90 31.60 0 0 0 0 0 0 0 0 C 22A-tpad ._ - 0.00 49 49, _ 44 , 78 138 110 221 F 22A-tph 1.358 1.350 36.02 0.00 0.00 49 0 0 0 138 10 390 300 0 6 c)AEDexcursion -24 loss/gain 44 54 118812 .a) Infiltration 0 0 187b) Roam ventilation 0 0 013 1-14Envelope IMemal gains: Occupants @ 230 0 0 0 Appliances/other 700 Subtotal (lines 6 to 13) 44 754 1375 Less eMemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 120 53 14 Subtotal 44 754 1496 1660 15 Duct loads 31 % 52% 14 395 31% 52% 460 870 Total room load 57 1149 1956 2530 Air required(cfm) 2 51 84 111 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fk- wrlghtso(!- 2020-Apr-01 15:01:44 RlghtSuite® Universal 201919.0.08 RSU08101 Page 7 ...ocumnets\Wrightsoft 4NAWHILIPPE RESIDENCErup Cato = MJB Front Door faces: W wrightsoft' Right-J@ Worksheet Job: Entire House Date: Apr 01, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772.466-6796 Emil: QUICKCALCS@AOL.COM 1 Room name CLST 2 BATH 2 2 E:¢osed wall 2.0 ft 5.0 ft 3 Room height 10.0 ft heaticool 10.0 ft heat/cool 4 5 Room dimensions Room area 9.0 x 2.0 It 18.0 fi 9.0 x 5.0 ft 45.0 fN Ty Construction number U-value (Btuh/ft-*F) Or HTM (Btuh/ft') Area (ft') or perimeter (ft) Load (Btuh) Area (W) or perimeter (ft) Lead (Btuh) Heat Coal Gross N/P/S Heal Cool Gross N/P/S Heat Cool 6 V I--G 13A4ocs 2 glazing,. cir low-e 2glazing, clr lower 0.143 0.650 0.650 n- n - 4.00 18.20 18.20 2.19 14.99 14.99 0, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 lam; Vj1 1 13A-4ocs 2 glazing, clr low.e 0.143 0.650 _n a a 4.00 18.20 2.19 33.77 20 0 20- 0 80 0 44 0 50 9 41 0 164 164 90 304 2 alazina, cU Iowa 13A-4acs 2 glazing clr Icwm- 0.650 0.143 0.650 a se se 18.20 4.00 18.20 33.77 2.19 23.80 0 0 - 0 0 0 0 0 0 0 _ 0 0 0 0 0 0 0 0 . . 0 0 0 0 0 0 0 L--{' UUUUUUNNNNII!! 13A4ecs 2 glazing, clr Iowa 0.143 0.650 s s 4.00 18.20 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing Or Iowa 2 glazing clr Iowa 2 glazing, clr Iowa 0.650 0.650 0.550 s s s 18.20 18.20 18.20 14.99 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Y-8 13A-4ms 2 glazing clr Im-a 0.143 0.650 sw ' sw 4.00 18.20 2.19 23.80 0 . 0_ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 VVyy �-G 13A4ccs 2 glazing, ch Iowa 2 glazing ctr lower 0.143 0.650 0.650 w w w 4.00 18.20 18.20 2,19 33.77 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 It--GG C 2 alazirq, clr Icwa 16BS0ad - 0.650 0.W2 w -- 18.20 0.90 33.77 1.60 0 18 0 _ 18 0 16 0 29 0 45 0 46 0 40 0 72 F 22Atph 1.358 - 38.02 0.00 18 2 76 0 45 5 Igo 0 6 c)AED excursion -3 .8 Envelope losslgain 172 70 558 457 12 a) Infiltration 37 10 93 25 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13) 210 80 652 782 Less mdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistributicn -210 -80 205 87 14 Subtotal 0 0 857 869 15 Duct loads 31% 52% 0 0 31% 52% 264 456 Total room lead 0 0 1121 1325 Air required (cm) 0 0 48 58 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrlghtsoiY- 2020-Apr-0115:01:44 "- ^ n RighlSuite® Universal 201919.0.08 RSU08101 Page 8 ...ocumnetslWrightsoft HVAMPHILIPPE RESIDENCE.mp Cale =MA Front Door faces: W wrightsoft• Right-JO Worksheet Job: Entire House Bare: Apr D,,zoz0 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34945 Phone: 772456-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 3 BEDROOM 3 2 3 E)gmed wall Room height 2.0 It 10.0 It heat/cool 12.0 ft 10.0 ft heat/cool 4 5 Room dimensions Room area 9.0 x 2.0 ft 18.0 fv 13.0 x 12.0 ft 156.0 It, Ty Construction U-value Or HTM Area (fP) Load Area Ile) Load number (Btuh/ft°F) (Btuh/ft-) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Grass N/P/S Heat Cool 6 VLj13AAccs 2 glazing, c7 Iowa 2 glazing, clr Iowa 0.143 O.BSO 0.650 n n n 4.00 18.20 18.20 2.19 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V�V F---(" 1 i 13AAccs 2 glazing, co- Iowa 0.143 0.650 a a 4.00 18.20 2.19 33.77 20 0 20 0 60 0 44 0 120 0 100 0 400 0 219 e �--C y/ L-f 2 clazin0. clr Iowa 13A-4ocs 2 glazing, clr law-e 13A-4ocs 2 glazing, or low-e 0.650 0.143 0.650, 0.143 0.650 a se se s s 18.20 4.00 .18.20 4.00 18.20 33.77 2.19 23.80 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 20 0 0 0 0 0 0. 0 0 0 364 0 0 0 0 675 0 0 0 0 2 glazing, clr Iowa 2 glazing, clr Iowa 2 glazing, cir Iowa 0.650 0.650 0.650 s s s 18.20 18.20 18.20 14.99 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W t-G 13A flocs 2 glazing, cir Iowa 0.143 0.650 sw sw 4.00 18.20 2.19 23.80 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W (-C 13A-0acs 2 glazing ch Iowa 2 glazing clr lows 0.143 0.650 0.650 w w w 4.00 18.20 1&20 2.19 33.77 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 II--fC' C 2 alazin(L a love 168J0ad 0.650 0.032 w - 18.20 0.90 33.77 1.60 0 18 0 18 0 16 0 29 0 156 0 156 0 140 0 250 F 22A-tph 1.358 - X02 0.00 18 2 76 0 156 12 456 0 6 c)AED excursion -3 -1 Emelope loss/galn 172 70 1360 1143 12 a) Infiltration 37 10 224 60 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 210 80 15&5 1203 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -210 -80 364 266 14 Subtotal 0 0 1949 1469 15 Duct loads 31 % 52% 0 0 31 % 52 % 599 770 Total room load 0 0 2548 2239 Air required (cfm) 0 0 110 99 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. '�' wrlghtsoft" 2020-Apr-01 15:01:44 -' RlghtSulte& Universal 2019 19.0.08 RSU08101 Page 9 ... ocumneta\WdghtsoitHVACIPHILIPPE RESIDENCE.mp Celc = Mde Front Door,aces: W F�h wrightsoft' Right-J@ Worksheet deb' Entire House Date: Apr 01, 202O QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-465-6799 Fax 772.45M796 Email: gUICKCALCS@AOL.COM 1 Room name HALL CLST 4 2 Elposed wall 0 ft 2.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 4.0 x 7.0 ft 28.0 ft' 10.0 x 2.0 ft 20.0 ft' Ty Construction U-value Or HTM Area (w) Load Area (ft') Lead number (Btuhlft''F) (BtuhlfP) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIP/S Heat Ccol Gross N/P/S Heat Cool 6 V8 13A-0acs 0:143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low- 0.650 in 18.20 14,99 0 0 0 0 0 0 0 0 II---GG 2 glazing, clr Iowa 0.650 n 18,20 14.99 0 0 D 0 0 0 0 0 V�f I---G 13AAms 0.143 a 4.00 2.19 0 0 0 0 20 20 w 44 11 2 glazing, clr Iowa 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 �--G y/ I-C 2 alazina clr Iowa 13A-4acs 2glazing or lcw-e 0.650 0.143 0.650 a as se IR20 4.00 18.20 33.77 2.19 23.80 0 0 0 0 0 - .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13AAocs 2 glazing, clr Iowa 0.143 0.650 s s 4.00 18.20 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing clr Iowa 2 glazing, ctr low-o 2 glazing, clr Iowa 0.650 0.650 0.650 s s s 18.20 18.20 18.20 14.99 14.99 14.99 0 0 0 0 0 0 a 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ,VN 13A-4cm 0.143 sw 4A0 - 2.19 0 0 0 0 0 0 0- 0 L-C 2 glazing clr Iowa 0.650 sw 18.20 23.80 0 0 0 0 0 0 0 0 VI! ILA---GGG 13A4ocs 2 glazing clr Iowa 0 0.650,650 w w 1&20 &20 2.19 33.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, ctr Iowa 0.650 w 1&20 33.77 0 0 0 0 0 0 0 0 G 2 alazina co- Iowa 168BOad 0.650 0.032, w - 18.20 0.90 33.77 1.60 0 28 0 28 0 25 0 45 a 20 0 20 0 18 0 32 F 22W 1.358 - 31102 ' 0.00 28 0 0 0 20 2 76 0 6 c)AED excursion -1 -3 EnWope Ions/gain 25 43 174 73 12 a) Infiltration 0 0 37 10 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 25 43 211 83 Less odemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -25 -43 -211 -83 14 Subtotal 0 0 0 0 15 Duct loads 1 31% 52% 0 0 31% 52% 0 0 Total mom load 0 0 0 0 Air required (rim) 0 0 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -PW wri-9hGsoTt- 2020-Apr-0115:01:44 RlghtSulte& Universal 2019 19.0.0E RSU9B101 Page 10 ...ocumnetslWdghtso8 HVACIPHILIPPE RESIDENCE.mp Cale =MJB Front Door faces: W wrightsofC Rig hWO Worksheet Job' Entire House Date: Apr 01, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4 BATH 3 2 E)pcsed wall 25.0 It 16.0 it 3 Roam height 10.0 ft hezticool 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 162.0 ft 162.0 fP 6.0 x 10.0 It 60.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (fN) Load number (Btuh/fV--°F) (Btuh/W) or perimeter (ft) (Btuh) or perimeter (ft) (Bluh) Heat Cool Gross NIP/S Heat Ccol Gross N/PIS Heat Coal 6 I--C 13AAccs 2 glazing, or low-e 2 glazing, ctr Icw-s 0.143 0.650 0.650 n n n 4.00 18.20 18,20 2.19. 14.99 14.99 130 0 0 130 0 0 521 0 0 284 0 0_ 60 0 0 - 60 0 0 240 0 0 131 0 0 L--G UI! I�-GG 11 13A-0ccs 2 glazing, clr low-e 0.143 0.650 a a 4.00 18.20 2.19 33.77 120 0 100 0 400 0 219 0 0 0 0 0 0 0 0 0 vl/ L-G 2 glazina. clr Iowa 13A4ocs 2 glazing, clr low-e 0.650 0.143 0.650 a se se 16.20 4.00 18.20 33.77 2.19 23.80 _ 20 0 0 _ 0 0 0 364 0 ':0 675 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A-0acs P glazing, clr Iowa 0. 0.650650 s s 4 4.00 1.2 2.19 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, clr low-e 2 glazing, ctr Iowa 2 glazing, Or Iowa 0.650 0.650 0.650 s s s 18.20 18.20 18.20 14.99 14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 UN I--G 13A-4ocs 2 glazing, or Iowa 0.143 0.650 sw , sw 4.00 18.20 2.1g 23.80 0 0 0 '0 0 0 _ 0 0 0 0 0 0 0 0 0 0 yl 13A4acs 2 glazing, clr Iowa 2 glazing, ctr low-e 0.650 0.650 0.650 w w w 4.20 18.20 18.20 33.77 3.77 33.77 0 0 0 0 0 0 0 0 0 0 0 0 109 9 0 91 0 0 160 154 0 199 304 304 0 2 alazina, Or Iowa 0.650 w 1820 33.77 0 0 0 0 0 0 0 0 C 16830ad - 0.032 , - 0.90 1.60 162 152 145 259 60 60 54 , 96 F 22A4ph 1.358 - 38.02 0.00 152 25 951 0 60 16 608 e, 0 6 c)AED excursion -12 99 Envelope loss/galn 2381 1425 1431 B29 12 a) Infiltration 467 125 299 80 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 2848 1551 1730 909 Less eMemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 326 285 316 360 14 Subtotal 3174 1836 2646 1269 15 Duct loads 31% 52% 9761 952 31% 52% 629 665 Total room load 4150 2798 2675 1934 Air required (cfm) 179 123 115 85 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr99httsoTt- 2020-Apr-0115:01:44 /C P RlghtSuile® Universal 2019 19.0.08 RSUOB101 Page 11 ...ocumnetslWrightsoa HIVACIPHILIPPE RESIDENCE.rup Colo -MJ8 Front Door faces: W wrightsofr Right4@ Worksheet Job: Entire House Date: Apr 01, 2820 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-086-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 Roam name HALLWAY 2 E:1pooed wall 7.0 ft 3 Roam height 10.0 ft heaticcol 4 Room dimensions 6.0 x 7.0 ft 5 Room area 42.0 fP Ty Construction U-value Or HTM Area (ft') Load Area Load number (Btuhlft? °F) (Btuhlft') or perimeter (ft) (Stuh) or perimeter Heat Cool Gross NIP/S Heat Cool Gross NIPIS Heat Cool 6 Yy 13A4ccs 2 glazing, clr Im-e 2 glazing, ctr Iowa 0,143 0.650 0.650 n n n 4.00 18.20 18.20 2.19 14.99 14.99 n D 0 0 0 0 0 D 0 0 0 0 Yj� (--G 11 13A4ccs, 2 glazing, clr low-e 0.143 0.650 a a 4.00 18.20 2.19 33.77 0 0 0 0 0 0 0 0 LLL---------fGG' V�1 L--C 2 glazing clr low -a 13A4ccs 2 glazing, clr low-e 0.650 0.143 0.650 a as se _18.20 4.00 18.20 33.77 2.19 23.60 0 0 0 _ 0 0 . 0 0 0 0 0 0 0 13A4ocs 2 glazing, ctr Iowa 0.143 0.650 s s 4.00 18.20 2.19 14.99 0 0 0 0 0 0 0 0 2 glazing, clr Iowa 2 glazing, ctr Iowa 0.650 0.650 s s 18.20 18.20 14.99 14.99 0 0 0 0 0 0 0 0 2 glazing, clr lawa 0.650 s 18.20 14.99 0 0 0 0 t-G 13A4ocs 2 glazing, cIr Iowa 0.143 0.650 sw sw 4.00 18.20 2.19 23.80 0 0 0 0 0 0 0 0 y! 13A400s 0.143 w 4.. 70 50 200 10 ILA -EGG 2 glazing, ctr bwa 0.6 w 18.2020 333.7777 0 0 0 0 0 2 glaringctr Iowa 0.650% w 18.20 33.77 0 0 0 0 c 2 glazin(L ctr Imva 16BJOad 0.650 0.032 w - 18.20 0.90 33.77 1.60 20 42 a 42 366 38 679 67 F 22A4ph 1.358 - 3802 0.00 42 7 266 0 6 c)AED excursion 1 1 250 Envelope Imsfgain 869 1105 12 a) Infiltration 131 35 b) Room ventilation 0 0 13 internal gains: Occupants @ 230 0 0 Appliancestother 0 Subtotal (lines 6 to 13) 1000 1140 Less eMemel load 0 0 Less transfer 0 0 Redistributim -1000 -1140 14 Subtotal 0 0 15 Duct loads 31% 52% 0 0 Total mom load 0 0 Air required (cfm) 0 0 Calculations approved byACCA to meet all requirements Of Manual J 8th Ed. - - wrigr+boH- 2020-Apr-0115:01:44 A '� •'^'-• RlghtSuite® Universal 2019 19.0.08 RSU08101 Page 12 ...ocumnets\Wdghtsoft WAC\PHILIPPE RESIDENCE.rup Calc=Mae Front Door faces: W Duct System Summary Job. 1' wrlghtsofte Y Date: Apr 01, 2020 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-46E6799 Fax 772466,6796 Email: QUICKCALCS@AOL.COM For: PHILLIPPE RESIDENCE PALM DRIVE, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating , 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1650 Cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 10.500 in H2O 1.000 in/100ft 1550 cfm 175 ft Name Design (Btuh) Htg (cfm) Clg (Cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 c 1325 48 58 1.000 6.0 Ox 0 VIFx 30.4 115.0 st1 BATH h 2675 115 85 1.000 6.0 Ox0 VIFx 39.3 135.0 st4 BEDROOM 2 c 2530 84 111 1.000 7.0 Ox0 VIFx 5.8 95.0 BEDROOM h 2548 110 99 1.000 7.0 Ox0 VIFx 26.7 115.0 sti BEDROOM h 4150 179 123 1.000 7.0 Ox0 VIFx 39.3 135.0 st4 DINING ROOM c 2255 68 99 1.000 7.0 Ox0 VIFx 39.6 135.0 st5 DINING ROOM -A c 2255 68 99 1.000 7.0 Ox0 VIFx 40.4 135.0 st5 KITCHEN/FAMILY c 2343 47 103 1.000 7.0 Ox0 VIFx 28.2 115.0 st1 KITCHEN/FAMILY--A c 2343 47 103 1.000 7.0 Ox0 VIFx 16.5 115.0 st3 LAUNDRY c 1149 2 51 1.000 6.0 Ox0 VIFx 14.0 115.0 st3 LIVING ROOM h 3666 158 111 1.000 7.0 Ox0 VIFx 21.8 115.0 st3 M BATH h 4799 206 113 1.000 7.0 Ox0 VIFx 49.0 115.0 st2 M TOILET h 794 34 33 1.000 5.0 Ox0 VIFx 49.7 115.0 st2 M wlc 1 h 927 40 35 1.000 5.0 Ox0 VIFx 46.1 115.0 st2 M WIC 2 c 517 2 23 1.000 6.0 Ox 0 VIFx 47.0 115.0 st2 MASTER BEDROOM h 3085 133 104 1.000 7.0 Ox0 VIFx 48.8 115.0 st2 MASTER BEDROOM -A h 3085 133 104 1.000 7.0 Ox0 VIFx 61.6 115.0 st2 OFFICE C 2123 77 94 1.000 7.0 Ox0 VIFx 15.8 115.0 st3 wit-11 oR• 2920Apr•B1 15:01:e3 AM..W.,�.,.n..��.�,,., Rlghl-899a® Universal 2019 10.0.08 RSU08101 Page 1 AM ...ocumnets%WHghtso9 HVAC\PHILIPPE RESIDENCE.mp Colo m MJB Front Door faces: W Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (Cfm) FR (fpm) (in) (in) Material Trunk st5 Peak AVF 136 199 1.000 569 8.0 0 x 0 VinIFIx st3 st3 Peak AVF 420 558 1.000 710 12.0 0 x 0 VinIFIX st4 Peak AVF 294 209 1.000 841 8.0 0 x 0 VinlFix SO st1 Peak AVF 498 469 1.000 635 12.0 0 x 0 VInIFIX st2 Peak AVF 547 412 1.000 697 12.0 0 x 0 VinlFlx Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rbl Ox0 1550 1550 0 0 0 0 Ox 0 VIFx -Fjd- wrightsoft- 2020-Apr o1 15:01:53 .a.+.,,..e..«.ww,...f.., RlghtSuita0r Universal 201519.0.08 RSU08101 Pago 2 ...00umnatsUrghlsofl WACIPHILIPPE RESIDENCE.rup Cale a M.18 Fronk Door faoas: W