Loading...
HomeMy WebLinkAboutCompaction testHeadquarters 11345 U.S. Highway 1 Sebastian, FL. 32958 Orlando 723 Progress Way Sanford, FL. 32771 Mailing PO Box 78-1377 Sebastian, FL. 32978 Phone: 772-589-0712 C.A.# 5693 KSMengineering.net DATE TESTED:KSM JOB #:203349-1d/MH/ct PERMIT #:NUC #630 CONTRACTOR:Adams Homes Nuc Model:MC-1DR-P JOB LOCATION:8305 Cristelle Court Nuc Serial #:30630 Lot 2, Block 2, Water Stone Ft. Pierce, Florida ITEM TESTED:Compacted Foundation Fill TEST LOCATION OF SAMPLE DEPTH PEN READ DRY DENSITY MAX. DRY PROCTOR VALUE (P.C.F) PERCENT COMPACTION 1. S.E.0" - 12"50 111.4 114.9 97.0% 2. S.W."50 112.6 "98.0% 3. Center "50 113.4 "98.7% 4. N.E."50 111.9 "97.4% 5. N.W."50 112.2 "97.7% Soil Description: Brown Sand with Shell & Clay Fragments In Place Moisture: 8.1% Proctor Optimum Moisture: 11.0% Proctor Max. Dry Density: P.C.F. 114.9 @ Test Locations the Density & Penetrometer readings indicate the Degree of Compaction Meets Minimum Requirement for Staked Foundation Respectfully Submitted: Bryan E. Dahlke, P.E. V.P. of Engineering PE # 81439 7/22/2020 Email to: rjohnson@adamshomes.com SOIL COMPACTION REPORT ASTM D 1557 and ASTM D 6938 July 21, 2020 2006-0467 Disclaimer:Contractor is responsible to maintain the tested area in the condition that KSM completed the indicated passed compaction test. KSM is not responsible if the tested area has been altered from the approved inspected condition. Proudly Serving Florida since 1990 111.0 112.0 113.0 114.0 115.0 116.0 8 9 10 11 12 13 14 W E I G H T P . C . F . D R Y Moisture -% of Dry Weight