Project SummaryJob: wrightsoft° Enure House By: Mar27, 2020 QUICK CALCS, INC. 317 ST LUCIE LANE. FORT PIERCE, FL 34946 Phone: 772-066,6799 FaX 772-466-6796 Email: OUCKCALCS@AOLCOM Pro*ect Information For. VINCENT CIMINO 6702 DONLON ROAD, FORT PIERCE, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 grllb Heating Summary Sensible Cooling Equipment Load Sizing Structure 17080 Btuh Structure 16388 Btuh Ducts 3824 Btuh Ducts 5493 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 20904 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 20787 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2597 Btuh Ducts 1458 Btuh Central vent (0 cfm) 0 Btuh Heat'" Coolingg (none) Area (fta) 1439 1439 Equipment latent load 4055 Btuh Volume (ft3) 11844 11844 Airchanges/hour 0.45 0.23 Equipment Total Load (Sen+Lat) 24842 Btuh Equiv. AVF (cfm) 89 45 Req. total capacity at 0.70 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS030-230A" AHRI ref Coil CBX27UH-030-230'++TDR AHRI ref 7625605 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 10.0 kW Sensible cooling 19600 Btuh Heating output 34121 Btuh Latent cooling 8400 Btuh Temperature rise 33 OF Total cooling 28000 Btuh Actual airflow 933 cfm Actual airflow 933 cfm Air flow factor 0.045 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.84 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2020-Mar-27 13:09:62 Rlght-Suite® Unlwmal 2019 10.0.08 RSU08101 Page 1 .91.�.H E:1DocumnetslWaghtsaR HVACICIMINO RESIOENCE.mp Cal, = MJ8 Front Door hoes: S wrightsof - Right-JO Worksheet Job: Entire House Date: Mar27, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUCKCALCS@AOL.COM 1 Room name Entire House BEDROOM 3 2 Exposed wall 154.0 R 23.0 R 3 Room height 8.2 ft 8.0 It heat/cool 4 Room dimensions 1.0 x 131.0 ft 5 Room area 1439.0 ft- 131.0 fF Ty Construction U-value Or HTM Area (R� Load Area (fly Lead number (Btuh/ftMF) (Btuh/ftl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Ccol Gross WP/S Heat Cool Gross WP/S Heat Cool 6 11 13A4= 0.143 n 4.00 2.19 43r 365 1460 798 96 96 384 210 I� 2 glazing, cir burs 0.650 n 18.20 14.99 30 0 546 450 0 0 0 0 2 giving, clr lore 0.650 n 18.20 14.99 40 0 732 603 0 0 0 0 �qJ 134-4acs 0.143 a _ 4.00 2.19 299 291 1166 637 0 0 0 0 11 L-C 2 glazing, clr lox¢ 0.650 a 18,20 33,77 8 0 146 210 0 0 0 0 14J 13A-4= 0.143 s 4.00 2.19 240 185 740 405 0 0' 0 0 �-G IL 2 glazing, clr loxes 0.650 s 18.20 14.99 15 15 273 225 0 0 0 0 2 glazing, clr Ici 0.650 s 18.20 14.99 20 20 364 300 0 0 0 0 -GC 2 glazing, clr Iox-e 0.650 - s 18.20 14.99 20 : 20 365 301 0 0 0 0 W 13A4ccs 0.143 w 4.00 2.19 288 270 1081 591 88 73 292 160 2 glazing, clr lowe 0.650 w 18.20 33.77 3 0 55 101 0 0 0 0 2 plazinp, cIr lore 0.650 w 18.20 33.77 15 0 273 507 15 0 273 507 C 16B30ad 0.032 - 0.90 1.60 1439 1439 1289 2302 131 131 117 210 F 22A4ph 1.358 - 38.02 0.00 1439 154 5856 0 131 23 875 0 6 c)AED excursion 0 185 Envelope loss/gain 14346 74119 1942 1270 12 a) Infiltration 2733 748 399 109 b) Rmmverdiation 0 0 0 0 13 Internal gains: Occupants (d1 230 0 0 0 0 Appliaraestother 8150 300 Subtotal (fines 6 to 13) 17080 16388 2340 1680 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 99 42 14 Subtotal 17080 imm 2439 1722 15 Duct leads 22% 34% 3824 5493 229% 34% w577 Total room lead 20904 21881 2985 2299 Air required(cfm) 933 933 133 98 Calculations approved by AC CA to meet all requirements of Manual J 8th Ed. _ wrlghTeof!- 2020-Mar-2713:08:52 Right-Sulle® Universal 2019 19.0.08 RSL08101 Page 1 AUME1Documnets\Wrightsoft WAMCIMINO RESIDENCE.rup Cale =MJ8 Front Door faces: S wrightsoft RighW@ Worksheet Job: Entire House Date: Mar27,2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34945 Phone. 772466-6799 Fax 772466-6796 Email: ONCKCALCS@AOL.COM 1 Room norne CLST 3 BATH 2 2 3 Fx:csed wall Room height 2.0 ft 8.0 ft heat/cod 6.0 It 8.0 fl heat/cod 4 5 Room dimensions Room area 9.0 x 2.0 ft 18.0 fF 9.0 x 6.0 0 54.0 ft- TV Construction number U-value (Btuh1ft;°F) Or HTM (Bmhft2) Area UP) or perimeter at) Load (Btuh) Area (fly or perimeter Qt) Load (Rtuh) Heat Cool Gnus WP/S Heat C001 Gross WPIS Heat Cool 6% 11 �1' I--C' 13 A 4acs 2 glazing, cir lot 2 glazing, clr love 1314-0 2glazirg, dr lwre 13A4a 2 glazing, clr lave 2 glazing, clr lov o 2 glazing, cir love -. 13M-0 2 glazing, cIr Iowa 2 plazim, dr leas 16BOQad- 0.143 0.650 0.690 0.143 0.650 0.143 0.650 0.650 0.650 0.143 0.650 0.650 0.032 6 n n a a s s s s w w w - 4.00 18.20 18.20 4.00 18.20 4.00 18.20 18.20 18.20 4.00 18.20 18.20 0.90 2.19 14.99 14.99 2.19 33.77 2.19 14.99 14.99 14.99 2.19 33.77 33.77 1.60 0 0 0 0 0 0 0 0 0 16 0 0 18 0 0 0 0 0 0 0 0 0 16 0 0 18 0 0 0 0 0 0 0 0 0 64 0 0 - 16 0 0 0 0 0 0 0 0 _ 0 35 0 0 29 0 0 0 0 0 0 0 0 0 48 3 0 54 0 0 0 0 0 0 0 0 0 45 0 0 54 0 0 0 0 0 0 0 0 0 180 55 0 48 0 0 0 0 0 0 0 0 0 98 101 0 86 l4V L--G �--G C F 22Ptph 1.358 - 38.02 0.00 18 2 76 0 54 6 228 0 6 c)AED excursion -1 37 Envelope bssJgain 156 63 611 323 12 a) Infiltration b) Roomventilation 35 0 9 0 104 0 28 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6to 13) 191 72 615 351 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 -191 0 0 -72 0 0 198 813 0 85 436 15 Dud loads 22% 349% 0 0 22% 347. iffi 146 Total room load Air requined(dm) 0 0 0 0 1196 44 5ffi 25 Calculations approved by ACCA to meet all requirements of Manual J ath Ed. ,�:- wrigF+tsof_i- 2020•Mar-2713:08:62 Right -Suite® Universal 2019 19.0.08 RSLID8101 Page 2 E:\Documnets%Wdghtsot HVAC%CIMINORESIDENCE.rup Calc=10J8 Front Doorfaces: S wrightsoft Right-M Worksheet Job: Entire House Date: Mar27, 2020 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-46"796 Email: OUICKCALCS@AOL.COM 1 Room name CLST2 BEDROOM 2 2 Eximed wag 2.0 ft 28.0 ft 3 Room height 8.0 it heaVcod 8.0 It heaUcool 4 Room dimensions 9.0 x 2.0 it 12.0 x 11.0 ft 5 Room area 18.0 fF 132.0 ft' Ty Constructio U-value Or HTM Area 01� Load Area Load number (Btuh/ft;*F) (&uh/W) or perimeter (ft) (Btuh) or perimeter (ft) (Bluh) Heat Cool Gross WP/S Heat cool Gross WP/S Heat Cool 6 1tV 13PAws 0.143 n 4.00 . 2.19 0 0 �0 0 0 0 � 0, 0 2 glazing, Or low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 II----GG 2 glazing, dr for 0.650 In 18.20 14.99 0 0 0 0 0 0 0 0 V� 13A-0ocs 0.143 a 4.00 2.19 0 0 0 0 40 40 160 88 11 L-C 2 glazing, clr lose 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 l4/ 13PAws 0.143 s 4.00 2.19 0 0 - 0 0 96 81 324 177 IfL----ffG' 2 glazing, dr lave 0.650 s 18.20 14.99 0 0 0 0 15 15 273 225 2 glazing, dr lo,e 0.650 s 18.20 14.99 0 0 0 '0 0 0 0 0 2 glazing, clr Iowa 0.650 s 18.20 14.99 0 0 0 .0 0 0 0 0 W, 13AAws 0.143 w 4.00 2.19 - 16 16 64 35 88 88 352 193 I�tC, 2glazing, dr to" 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 clazino. dr Ip 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16630ad 0.032 - 0.90 1.60 ' 18 18 16 29 132 132 118 211 F 22A-tph 1.358 - 38.02 0.00 18 2 76 0 132 28 1065 0 6 c)AEDexcursion -1 -29 Envelope loss/gain 156 63 2293 865 12 a) Infiltration 35 9 485 133 b) Roomventitatio 0 0 0 0 13 Internal gems: Occupants 0 230 0 0 0 0 Applianceslother 0 650 Subtotal (roes 6 to 13) 191 72 2778 1647 Less eldenal load 0 0 0 0 Less trarafer 0 0 0 0 Redistribution -191 -72 99 42 14 Subtotal 0 0 2877 1690 15 Dud loads 22% 34% 0 0 22% 34% 644 5W Trial morn load 0 0 3W1 2258 Air required (rim) 0 0 157 96 Calculations approved byACCA to meet all requirements of Manual J Bth Ed. 2020-Mar-2713:08:52 "'-'-' RightSulte® Universal 2019 19.0.08 RSU08101 Page 3 E:%Documnets%W6ghtsox WAC\CIMINORESIDENCE.rop Cale=MJB Front Doorfaces: 8 wrightsoftRight-l®Worksheet Job: Entire House Date: Mar27, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: OUICKCALCS@ AOLCOM 1 Room name HALL DINING 2 Exposed wall 0 It 16.0 it 3 Room height 8.0 It heaticod 8.0 ft heallcod 4 Room dimensions 3.0 x 10.0 It 12.0 x 8.0 ft 5 Room area 30.0 fP 96.0 ft2 Ty Construction U-value Or HTM Area (ft!) Load Area (fl2) Load number (Btuh/f MIF) (Sluh/ft) or perimeter (ft) (&uh) or perimeter (ft) (81uh) Heal Cool Grass WP/S Heat Cool Gross WP/S Heat Cool 6 XEj134-0acs 0.143 �n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, dr Iowa 0.650 It 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing; cir lowe 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 32 32 128 70 t i I-C 2 glazing, cir lox a 0.650 a 18,20 33.77 0 0 0 0 0 0 0 0 tyV 13A-4ws 0.143 s 4.00 ! 2.19 0 0 0 0 96 76 304 166 �C 2glazing, cir lbv 0.650 s A20 14.99 0 0 0 0 0 0 0 0 iL-CG 2 glazing, dr 1cwe 0.650 s 18.20 14.99 0 0 0 0 20 20 364 300 2 glazing, cir Iowa 0.650 a 18.20 14.99 0 0 0 0 0 0 0 0 13A4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 I--G 2glazing, dr lcn a 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 111---GGG 2 glazinc. cir lwre 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B3W 0.032 - 0.90 1.60 30 30 _ 27 48 96 96 86 154 F 22A4ph 1.358 - 38.02 0.00 30 0 0 0 96 16 608 0 6 c)AED excursion -1 -25 Envelope lose/gain 27 47 1491 665 12 a) Infiltration 0 0 277 76 b) Room ventilation 0 0 0 0 13 Internal gams: Occupants @ 230 0 0 0 0 Appliancesrother 0 700 Subtotal (lines 6 to 13) 27 47 1768 1441 Less aldernal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -27 47 240 129 14 Subtotal 0 0 2008 15M 15 Duct loads 22% 34% 0 0 2295 34% 450 528 Total mom load 0 0 2458 2095 Air required (cfm) 0 0 110 89 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. _ -*- w__rrghtsoTY- 2020-Mar-2713:08:52 RightSufte® Universal 2019 19.0.08 RSL08101 Page 4 E:1DocumnetslWdghtsot FMAC\CIMINORESIDENCE.mp Calc=MJ8 Front Doorfaces: S wrightsoft• Right-M Worksheet Job: Entire House Date: Mar 27, 2020 BY: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 7724666799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room rarne FOYER KITCHEN/NOOK 2 Exposed wall 6.0 R 13.0 it 3 Room height 8.0 ft heatf000l 8.0 It heatf000l 4 Room dimensions 6.0 x 4.0 ft 1.0 x 265.0 ft 5 Room area 24.0 fP 265.0 ft' Ty Construction number lYvalue (Btuhdt;°I) Or HTM PUMP) Area (W) or perimeter Ot) Load (Bluh) Area or perimeter (R) Load (Ruh) Heat Cool Gross WPfS Heat Cool Gross WP/S Heat Cool 6 V�I im4ocs 0.143 n 4.00 2.19 0 0 0 0 IN89 356 195 2 glazing, Gr Iowa 2glazirg, dr bne 0.650 0.650 n n 1&20 1&20 14.99 14.99 0 0 0 0 0 0 0 0 15 0 0 a 273 0 225 0 IL----GG �,/ L-C 1'I 13A4aos 2glazing, dr lo. 0.143 0.650 a a 4.00 113,20 2.19 33.77 0 0 0 0 0 0 0 0 0 0 a 0 0 0 0 0 ViV 13A4ocs '2 glazing, clr le wt 0. 0.650650 s s - 4.00 1&20 2.19 14.99 48 0 28 0 11 0 6 0 0 0 0 a 0 0 0 0 0 2 glazing, clr lone 0.650 s 1&20 14.99 0 0 0 0 0 a 0 0 0 L�fGi ' 2 glazing, clr lone 13A4acs 1,651 0.143 s w 18.20 4.00 14,19 2.19 20 a .. 20 0 - 366 0 - 301 0 0 a 0 0 , 0 0 a 0 2 glazing, cIr love 0.650 w 18.20 33.77 o 0 0 0 0 0 0 0 L�-(G C 2 nlazing, clr lone 16S36ad 0.650 0.032 w - 18.20 0.90 33.77 1:60 a 24 0 24 0 22 0 38 0 265 0 265 0 237 0 424 F 22A4ph 1.358 - 38.02 0.00 24 6 22B 0 265 13 494 0 6 c)AEDexcusion 6 S5 Envelope losstgain 727 407 1361 789 12 a) Infiltration 104 28 225 62 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliancestolher a 2300 Subtotal (lines 6 to 13) 831 435 1566 3150 Less eternal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -831 -435 &% 187 14 Subtotal 0 0 1113 =7 15 Duct loads 22% 34% 0 0 22°/ 34% 435 1119 TUa] mom lead 0 0 2377 4456 Air required (dm) 0 0 106 190 Calculations approved bYACCA to meet all requirements of Manual J 8th Ed. -01h wrrghisoft- 2020-Mar-2713:08:52 RightSuile® Universal 2019 19.0.08 RSlAet01 Page 5 E:1DocumnatslWdghtsoft WAMCIMINORESIDENCE.mp Calc=MJ8 Fmnt Doorfzces: S wrightsof , Right-J®Worksheet Job: Entire House Date: Mar 27, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Emil: ONCKCALCS@AOL.COM 1 Room name GREAT ROOM LAUNDRY 2 Exposed wall 14.0 it 4.0 0 3 Room height 8.7 R heatfcod 8.0 ft heat/Cool 4 Room dimensions 14.0 x 19.0 ft 6.0 x 6.0 it 5 Room area 266.0 fP 36.0 fP Ty Constmdion U-value Or HTM Area 02) Load Area (ft� Load number (Btuhlft;°F) (Btuh/fM or perimeter at) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP)S Heal Owl Gross WP/S Heat Cool 6 % I�-GG 13AAocs 2glazing, dr lave 2 glazing, dr lave 0.143 0.650 0.690 n n n 4.00 18.20 18.20 2.19 14.99 14.99 122 0 40 82 0 0 327 0 732 179 0 603 0 0 0 a 0 0 0 0 0 0 0 0 1'I W! LG 13AAa 2 glazing, dr to +e 0.143 0.650 a a _ 4.00 18.20 2.19 33.77 0 0 0 0 0 0 0 0 a 0 0 0 0 0 0 0 1(U 2 gImIn s 2 glazing, dr lave 2 glazing, dr love 0.650 0.650 0.650 s s s 18.20 8.20 18.20 4.99 14.99 14.99 0 0 0 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 iIL-----GGG . W, 2 glazing, cir Iovre 13AAocs 0.650 0.143 s w 18.20 4.00 14.99 2.19 0 0 ,0 0 0 0 0 0 0 32 0 32 0 12B 0 70 L�-CG C 2 glazing, cir lowe 2 plazing, clr lovu-e 16B30ad 0.650 0.650 0.032 w w - 18.20 18.20 0.90 33.77 33.77 1.60 0 0 266 0 0 266 0 0 238 0 0 - 426 0 0 36 0 0 36 0 0 32 0 0 58 F 22A4ph 1.358 - 38.02 0.00 266 14 532 0 36 4 152 0 6 c)AED excursion -42 -11 Envelope Iossrgain 1829 1164 312 117 12 a) Infiltration 264 72 69 19 b) Rcomventilation 0 0 0 0 13 Internal gems: Occupants (LD 230 0 0 0 0 Appliancesrolher 12M 500 Subtotal (lines 6 to 13) 2093 2437 382 636 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 121 79 119 62 14 Subtotal 2221 2516 501 698 15 Duct loads 22% 34% 497 843 22% 34% 112 234 Tat room load 2719 3119 613 932 Air mqu[red(ofm) 121 1'* 27 40 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. c -7# wrlgheaoTe- 2020-Mar-2713:08:52 Ak ' ^^ Right-SuitcO UnNomal2019 19.0.08 RSLA8101 Page 6 E:\Documnots\WrightsoftWAC\CIMINORESIDENCE.rup Calc=MJ8 Front Doorfaces: 8 wrightsoft Right-M) Worksheet Job: Entire House Date: Mar27,2020 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466.6799 Fax 772-466-6795 Email: OUICKCALCWOLCOM 1 Room name M BATH M TOILET 2 Exposed wall 7.0 R 4.0 It 3 Room freight 8.0 ft heaVcad 8.0 ft heatf od 4 Room dimensions 1.0 x 98.0 It 1.0 x 30.0 ft 5 Room area 98.0 ft2 30.0 fF Ty Construction U-value Or HTM Area (ft2) Load Area (f12 Load number. (Blu1Jft-'F) (Bluwl or perimeter (ft) (Ruh) or perimeter (R) (Bluh) Heal Ceol Grass WKS Heat Cool Gross WP/S Heal Cool 6 4)/ 1344ocs 0.143 n 4.00 2.19 0 .0 0 0 0 0 0 0 2 glazing, dr lure 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 ---GG 2 glazing, or luxe 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 �/ _ 13A4ws 0.143 a 4.00 2.19 56 56 224 123 32 24 96 53 11 L-C 2 glazing, cir loxe 0.650 a 18.20 33.77 0 0 0 0 8 0 146 270 1pJ 0.650 s 0 0 0 0 0 0 0 0 2gimins luxe 2 glazing, 0.650 s 8.20 18.20 4.19 14.99 0 0 0 0 0 0 0 0 dr 2 ghazigg, dr luxe 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, dr lone 0.650 s 18.20 14.99 0 0- 0 0 0 0 0 0 13AAws 0.143 w 4.00 2.19 0 a 0 0 a 0 0 0 LsI-- Ls 2glazing, dr lur 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 z elazim. or luxe 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B3(bd 0.032 _ - 0.90 1.60 98 - 98 88 157 30 30 27 48 F 22A-tvh 1.358 - 38.02 0.00 98 7 265 0 30 4 152 0 6 c)AED excursion -12 8 Envelope loss/gain 578 267 421 379 12 a) Infiltration 121 33 69 19 b) Room ventilation 0 0 0 0 13 Internal gams: Occupants Q 230 0 0 0 0 Appliaxeslother 400 0 Subtotal (lines 6 to 13) 699 700 490 398 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 699 700 490 398 15 Duct loads 22% 34% 157 235 22% 34% 110 133 Taal room load B56 935 Sm 531 Air required(dm) 38 40 27 23 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -FW wrigtiboTi- 202&Mar-2713:08:52 A�k' RightSuite® universal 2019 19.0.08 RS1A8101 Page 7 E:1DocumnetslWdghtsoft HUAC\CIMINORESIDENCE.mp Calc=MJ8 Front Doorlaces: S wrightsoft- Right-J®Worksheet Job: Entire House Bate: Mar27, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772A66-6799 Fax 772-466-6796 Email: OUICKCALCS®AOLCOM 1 Room name M WIC MASTER BEDROOM 2 Exposed wall 0 ft 29.0 ft 3 Room height 8.0 ft heaUcod 8.7 fit heat/cool 4 Room dimensions 1.0 x 33.0 ft 13.0 x 16.0 0 5 Room area 33.0 fP 208.0 fP Ty Construction number U-value (Bluh/fWFj Or HTM (BluhHt-) Area 00 or perimeter qt) Load (Bluh) Prey (0� or perimeter Of) Load (Bluh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 13A4ocs 2 glazing, clr low-e 2 glazing, cir lame 0.143 0.650 0.650 n n n 4.00 18.20 1&20 2.19 .14.99 14.99 0 0 0 0 0 0 0 0 0 0 0 0 113 15 0 98 0 0 393 273 0 215 225 0 1pr L-G 11 13A-0ocs 2g1azirg, Gr log 0.143 0.650 a a 4.00 1&20 2.19 33.77 0 0 0 0 0 0 0 0 139 0 139 0 557 0 305 0 1344ocs 2 glazing, clr loov-e 2 glazing, dr lwae 2 glazing, clr lame 13A 4acs 2glazing, dr lc ✓e 2 alazinn. clr love 161130ad 0.143 0.650 0.650 0.650 0.143 0.650 0.650 0.032 s s a s w w w - 4.00 18.20 18.20 18,20 4.00 18.20 18.20 0.90 2.19 14.99' 14.99 14,91 2.19 33.77 33.77 1.60 0 0 0 0 0 0 0 - 33 0. 0 0 0. 0 0 0 33 0 0 0 0 0 0 0 30 0 0 0 0 0 0 0 53 0 0 0 0 0 0 0 208 0 0 0 0 0 0 0 208 0 0 0 0 0 0 0 186 0 0 0 0 0 0 0 333 ,W I�-CG C F 22A4ph 1.358 - 38.02 0.00 33 0 0 0 208 29 1103 0 6 c)AED excursion -1 -57 Envelope bss/gain 30 52 2512 1020 12 a) Infiltration b) Roomvenlilatlon 0 0 0 0 546 0 150 0 13 Internal gains: Occupants @ 230 Apphances/other 0 0 0 0 0 2100 Subtotal (lines 6 to 13) 30 52 3059 3270 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 30 52 3059 3270 15 Duct loads 22% 34% 7 17 M. 34% 685 low Trial room load 36 69 3743 4316 Air required (elm) 2 3 15/ 186 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ -pw w_rigtiCsoTt- 2020-Mar-2713:08:52 RightSude® Universal 2019 19.0.08 RS1A8101 Page 8 � EADocumnetslWrightsoR WAC\CIMINO RESIDENCE.rup Calc=MJ8 Front Door faces: S - wrightsoft° Duct System Summary Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: OUICKCALCS@AOLCOM For. VINCENT CIMINO 6702 DONLON ROAD, FORT PIERCE, FL Job: Date: Mar27,2020 By: Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply I return available pressure 0.50010.500 in H2O 0.500 / 0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 933 cfm 933 cfm Total effective length (TEL) 162 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mad Actual Ln (ft) Fig.Egv Ln (ft) Trunk BATH 2 h 996 44 25 1.000 5.0 OxO VIFx 38.8 115.0 st2 BEDROOM 2 h 3521 157 96 1.000 7.0 Ox 0 VIFx 41.0 115.0 st2 BEDROOM 3 h 2985 133 98 1.000 7.0 Ox 0 VIFx 40.3 115.0 st2 DINING h 2458 110 89 1.000 7.0 Ox0 VIFx 38.8 115.0 st2 GREAT ROOM C 3359 121 143 1.000 8.0 OxO VIFx 40.0 115.0 st2 KITCHEWNIOOK C 2228 53 95 1.000 7.0 Ox0 VIFx 27.4 135.0 st3 KITCHEWNOOK-A C 2228 53 95 1.000 7.0 OxO VIFx 26.7 135.0 st3 LAUNDRY C 932 27 40 1.000 6.0 OxO VIFx 11.4 115.0 st1 M BATH C 935 38 40 1.000 6.0 Ox 0 VIFx 15.3 115.0 st1 M TOILET h 600 27 23 1.000 5.0 Ox0 VIFx 14.6 115.0 Ed •WIC c 69 2 3 1.000 4.0 Ox0 VIFx 11.5 115.0 st1 MASTER BEDROOM C 2183 84 93 1.000 7.0 OxO VIFx 25.8 135.0 st3 MASTER BEDROOM -A C 2183 84 93 1.000 7.0 Ox 0 VIFx 26.7 135.0 st3 Trunk Htg Cig Design Veloc Diam H x W Duct Name Type (cfm) (Cfm) FIR (fpm) (in) (in) Material Trunk st2 Peak AVF 566 452 1.000 721 12.0 0 x 0 VInIFIx st3 Peak AVF 273 376 1.000 690 10.0 0 x 0 VinlFIX st1 st1 PeakAVF 367 482 1.000 730 11.0 0 x 0 VinlFlx wrlghtsof - 2020-Mar-2713:08:67 "� •+-. Rlght-Sulte® Unlsersal 2019 19.0.08 RSU38101 Page 1 �E:1DocumnetelWHghtaoft M/AC\CIMINO RESIDENCE.tup Cato =MJB Front Door faces; 8 Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1 933 933 0 0 0 0 Ox 0 VIFx .� wrightsoft- 2020-Mar•2718:08'67 ewn.vi....ui.....rro.r.... RIgM•Sulte® UnNareel 2019 19.0.08 R8U08101 Page 2 ^�^ E:1Documneta Wdghtsoft HVAMCIMINO RESIDENCE.mp Cale - MA Front Door feces: 8