HomeMy WebLinkAboutEnergy CodeComponent Performance Method for Commercial Buildings Form 400B-94
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLA/COM-94 Version 2.1A
PROJECT NAME_OFFICE WAREHOUSE___________ PERMITTING OFFICE:
ADDRESS: GLADES RD. Fort Pierce
------------------ - -----------------
-------------- -
FT. PIERCE, FL CLIMATE ZONE: 6
-----------
OWNER: --------------- CAT RECYCLING PERMIT NO: X
------------
AGENT: JURISDICTION NO:661100
---------------------------- - ------
BUILDING TYPE: _Factory - Industrial_______
CONSTRUCTION CONDITION: New construction
DESIGN COMPLETION: _Finished Building__________
CONDITIONED FLOOR AREA: 500 NUMBER OF ZONES: 1
- ---------
MAX. TONNAGE OF EQUIPMENT PER SYSTEM :----------- ----
2_________________
COMPLIANCE CALCULATION:
METHOD B
DESIGN
CRITERIA
RESULT
-----------------
ENVELOPE PERFORMANCE
------
39.82
--------
67.92
------
PASSES
OTHER ENVELOPE REQUIREMENTS
PASSES
LIGHTING
INTERIOR LIGHTING
880.00
1049.33
PASSES
EXTERIOR LIGHTING
120.00
270.00
PASSES
LIGHTING CONTROL REQUIREMENTS
PASSES
HVAC EQUIPMENT
COOLING EQUIPMENT
1. SEER
10.00
9.70
PASSES
HEATING EQUIPMENT
AIR DISTRIBUTION SYSTEM INSULATION
LEVEL
1. With Insulated Roof
6.00
4.20
PASSES
WATER HEATING EQUIPMENT
PIPING INSULATION REQUIREMENTS
----------------------------------------------------------------------------
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and
specifications covered by this calcu-
lation are in compliance with the
Florida Energy Efficiency Code.
PREPARED BY:_________________________
DATE:
I hereby certify that this building is
in compliance with the Florida Energy
Efficiency Code.
OWNER/AGENT:
--------------------------
DATE:
Review of the plans and specifica-
tions covered by this calculation
indicates compliance with the
Florida Energy Efficiency Code.
Before construction is completed,
this building will be inspected
for compliance in accordance with
Section 553.908, Florida Statutes.
BUILDING OFFICIAL:
DATE:
I I hereby certify(*) that the system design is in compliance with the Florida
Energy Efficiency Code.
SYSTEM DESIGNER REGISTRATION/STATE
ARCHITECT
MECHANICAL : _ h7 - - u ---------- ---------------
,PLUMBING
-----------------------------------------------------------------
ELECTRICAL:
LIGHTING :______________________
-------------------------------------------
-----------------------------------------------------------------
(*) Signature is required where Florida law requires design to be performed
by registered design professionals. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
Y
401.---- ZI GLA•NG�-`-'LONE
Elevation Type
East Commercial
South Commercial
BUILDING
INFORMATION
COMPLIANCE
CHECK
_------------------------- v_
I---------------
U SC VLT Shading___-___
Area(Sgft)I
'----------I
1 31
----
.67 .73
------
None
121
1.31
.67 .73
None
121
Total Glass Area
in Zone 1 =
241
Total
Glass Area =
241.
402.------WALLS--ZONE 1---------------------- --U Added R
Elevation Type
_ ______
------ ---------------------
West Frame Wall + 3" InS. 0.081 11
South Frame Wall + 3" InS. 0.081 11
0.081 11
East Frame Wall + 3" InS.
North Frame Wall + 3" InS•008111
Total Wall Area Zone 1
Total Gross Wall Area =
Gross(Sgft)
135
342
135
342
954
954
403.------DOORS--ZONE 1----- - U Area(Sgft)I
Elevation Type
-----I
--------- ------------------------------------------
South 1-3/4 Steel Door -Polyurethane core (18 0.29
401
201
North 1-3/4 Steel Door -Polyurethane core (18 0.29
=
601
Total Door Area in Zone 1
Total Door Area =-601
404 ----ROOFS--ZONE 1------- ----------------------------------
U Added R
------I_
Area(Sgft)I
Color
Type -------
Type
----------1
____________
ROOF TRUSSES R-30 INSLULATION Light .03 30
1 =
5701
5701
Total Roof Area in Zone
5701
Total Roof Area =
405.______FLOORS-ZONE 1_
R
1
Area(Sg)I
Type -------
----------I
_______ ___ -----------------------------
0
570I
Slab on Grade/Uninsulated
Total Floor Area in Zone 1 -
5701
Total Floor Area =
5701
406.------INFILTRATION---------------------- ____________________________I___
ICHECKI
Infiltration Criteria in 406.1.ABC.1 have been met.I__--_i---
407.------COOLING SYSTEMS--------------'--'-------
IPLV
Tons
Type No Efficiency
--------------
1. Single Package
408.------HEATING
Type
1. No Heating System
409,------VENTILATION
1 10 10 1.50
No Efficiency
--o ----------
Ventilation Criteria in 409.1.ABC.1 have been met.
Duct-
410.-----AIR DISTRIBUTION SYSTEM---------D-
Location
AHU Type Duct-
1. Packaged Constant Volume
411.-----PUMPS AND PIPING -ZONE
Type
-------I---
BTU/hr01
----- -I---
ICHECKI
I I
R-value)
With Insulated Roof 6
R-value/in Diameter Thicknessl
----------
-- ---------I
0 0 01
1. Non -Circulating _________-�
412.-----WATER HEATING SYSTEMS -ZONE 1-----------------------
Type Efficiency StandbyLoss_InputRate ___Gallons
413.-----ELECTRICAL POWER DISTRIBUTION-------- ---------- ICHECK
Metering criteria in 413.1.ABC.1 have been met. I
Transformer criteria in 413.1.ABC.2 have been met. I
__ --__
____________________________________I_
414._____MOTORS ___________ __
Motor efficiencies in 414.1.ABC.1 have been met.-_-
415.-----LIGHTING SYSTEMS -ZONE 1-----------------
Space Type No Control Type 1 No Control Type 2 No Watts Area-Sgft)
-
--- --
Reading, T 1 On/Off 2 None 2 880 4901
Total Watts for Zone 1 - 8801
Total Area for Zone 1 = 4901
Total Watts = 8801
Total Area = 4901
ICHECKI
Lighting criteria in 415.I.ABC have been met.--_- -I 1
-------------------------------------------------
16. HVAC load sizing has been performed. (407.1.ABC.1) I I
--------------------------------
----------------------------------I-----I---
17. Duct sizing and design have been performed. (410.1.ABC.1.2)
---- ---- ------------------------------- ---
18. Testing and balancing will be performed. (410-i.ABC.4) I 1
--------------------------
----------------------------------------I-----I---
19. Operation/maintena-ace manual will be provided to owner.(102_1)I-____I-__
--------------------------
I{. '.::..i is � ,, • •
******** PASSES ********
EXTERIOR LIGHTING CRITERIA:
AREA AREA AREA OR ALLOWANCE
YICODE DESCRIPTION LENGTH WATTS
2 Entrance (without canopy) 6.00 180.00
2 Entrance (without canopy) 3.00 90.00
Exterior Lighting Power Allowance 270.00 W
******** PASSES ********
THE LIGHTING SYSTEM CONTROL REQUIREMENTS:
TOTAL EQUIVALENT
SPACE NO. CONTROLS CONTROL POINTS
NO. DESCRIPTION AREA TASKS TYPE 1 NO. TYPE 2 NO. INSTLD. REQD.
26 Reading, T 490.0 1 On/Off 2 None 2 2= 2
******** PASSES ********
PROJECT TITLE OFFICE WAREHOUSE
BUILDING TYPE Factory - Industrial
BUILDING LOCATION : Fort Pierce
BUILDING AREA(ft2): 570
HVAC SYSTEMS PERFORMANCE:
Cooling System
Type
Measure
#1 #2
Minim.
#1
Minim.
#2
System
Eff.#1
System
Eff.#2
Result
for #1
Result
for #2
Single Pack.
SEER
9.70
0.00
10.00
10.00
PASSES
Heating System
Measure
Minimum Req.
Efficiency
Result
******** PASSES ********
AIR DISTRIBUTION SYSTEM INSULATION LEVELS:
Zone
# Duct
Location
Minimum R-Value
Design R-Value
Result
1.
With
Insulated Roof
4.20
6.00
PASSES
PROJECT TITLE
v BUILDING TYPE
BUILDING LOCATION
BUILDING AREA(ft2):
******** PASSES ********
OFFICE WAREHOUSE
Factory - Industrial
Fort Pierce
570
HEATING SYSTEMS PRESCRIPTIVE CRITERIA
I
t
PROJECT TITLE OFFICE WAREHOUSE
BUILDING TYPE Factory - Industrial
'B,UILDING LOCATION Fort Pierce
BUILDING AREA(ft2): 570
`i%JILDING ENVELOPE
N NE
COMPONENT
WALL
E
PERFORMANCE
ORIENTATION
SE S SW
W NW
WEIGHTED
AVER. CRITERIA
WALL
342
135
342
135
0.03
0.290
GL
0
12
12
0
WWR
WWR
SC
0.000
0.670
0.670
0.000
0.34
0.500
PF
0.00
0.00
0.00
0.100
0.00
0.00
VLT
0.00
0.73
0.73
0.00
0.37
N/A
Uof
0.000
1.310
1.310
0.000
0.66
1.150
W UO
0.04
0.04
0.04
0.04
0.04
0.371
HCJ
1.52
1.52
1.52
1.52
1.52
1
IP
3
3
3
3
3
N/A
0.176
0.117
L 0 A D S
0.271
0.078
TOTAL
HEAT
0.642< 3.691
COOL
12.500
6.847
15.311
4.520
39.178< 64.228
SUM
12.676
6.964
15.582
4.598
39.820< 67.918
******** PASSES *******
OTHER ENVELOPE REQUIREMENTS
MAXIMUM PERCENTAGE OF ROOF AREA IN SKYLIGHTS: DESIGN LIMIT
Percentage of Roof Area in Skylights 0.000 = 0.0000
MAXIMUM ALLOWABLE Uo:
Roof 0.016 < 0.0868
n
******** PASSES *******
PROJECT TITLE OFFICE WAREHOUSE
BUILDING TYPE Factory - Industrial
BUILDING LOCATION : Fort Pierce
BUILDING AREA(ft2): 570
SYSTEM PERFORMANCE CRITERIA
BUILDING DESIGN :
Interior Lighting Power
Exterior Lighting Power
INTERIOR LIGHTING CRITERIA:
Space . No.
Type Area Clg Ht Spaces
A 26 490.0 9.0 1
880 W
120 W
AF UPI) PB LPB
1.19 1.80 2.14 1047
Unit Power Density
Interior Lighting Power Allowance
1.76 W/Gross ft2
2.14 W/Gross ft2
1049 W
Total LPB
1047
System Measure Minimum Maximum Design Design Result
Type EF / Et SL EF / Et SL
r **** Not Applicable ****
1
`PIPING INSULATION REQUIREMENTS:
Pipe Insulation Thickness(in)
System Type O.D.(in) Minimum Req. Design Result
**** Not Applicable ****