HomeMy WebLinkAboutProject Informationect Summary Job: 2265 MODEL -GAR LEFT Pro - wrightsoft° Entire House Byte: MAY 22, zozo QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772466-6796 Email: QUICKCALCS@AOL.COM Project For: ADAMS HOMES 8108AMALFI CIRCLE, PORT ST LUCIE, FL 34951 Notes: Design Information Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TO 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 24426 Btuh Structure 21287 Btuh Ducts 7150 Btuh Ducts 9631 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 31575 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 29372 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3967 Btuh Ducts 2801 Btuh Central vent (0 cfm) 0 Btuh Heatingg Cooling (none) Area (ft2) 2277 2277 Equipment latent load 6768 Btuh Volume (fta) 20348 20348 Air changesthour 0.32 0.16 Equipment Total Load (Sen+Lat) 36140 Btuh Equiv. AVF (cfm) 109 54 Req. total capacity at 0.70 SHR 3.5 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC542AO0300 Cond 25HBC542AO0300 AHRI ref 9155360 Coil FX4DNF043L AHRI ref 9155360 Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 29050 Btuh Heating output 42000 Btuh @ 47'F Latent cooling 12450 Btuh Temperature rise 28 OF Total cooling 41500 Btuh Actual airflow 1383 cfm Actual airflow 1383 cfm Air flow factor 0.044 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.82 Capacity balance point = 35 OF Backup: Input = 8 kW, Output = 28539 Btuh, 100 AFUE Calculations approved byACCA to meet all requirenWpfn04%lp>f q -PI:- wrigftts fi- AMA • Right-SuileO Universal 201919.0.08 RSUD8101 ...fl HVACWDAMS HMS- 8108 AMALFI 2265 MODEL A.rup CaIc=MJ8 Front Doorfaces: N 2020-May-22 13:45:38 Page 1 wrightsoft RighW@ Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fac 772466-6796 Email: OUICKCALCS@AOL.COM 1 2 3 4 5 Room name 6posed wall Room height Room dimensions Room area Entire House 2022 It 8.9 ft 2276.5 fl2 O W IC 1 7.0 It 8.0 It heatfccol 5.0 z 7.0 ft 35.0 ft2 Ty I Construction number U-value (BtutVftk*F) Or HTM (BtuNft2) Area (fl2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 ' 19-flocs 2glazing clr low-e 2g1azing cir low,-e 2 glazing, clr low-e 2 glazing, clr lowe _111)0 _ 0143 0.650 0.650 0.650 0.650 -0.390 n n n n n -n_ a a a s ' s s s sw sw w w w W-_1820 - 460 1820 1820 16.20 ' 11120 10.92 4.00 18.20 18.20 `4 00 18 20 1820 18.20 4,00 18.20 4 00 1820 1820 0.90 =36.02 2.19 10.68 10.68r 10.68 10.68 -10.34 2.19 32.42 32.76 2.19 14 99 1499 11.27 2.19 14.20 2.19 23.79 20.23 ,,,,_,.20:42 1.60 - -0.00 7--320�210 10 30 36 •13 -20 468 30 18 482 60 18 12 42 8 0 °,., 0"- " 0 0 20 842 182 546 `-655 244 -223 460 107 321 "- 385 143 �211 '-'0 0 0 ' • 0 0 --0-0 0 0 0 g 0 0 0 0 0 -- 66 0 0 ..0 35 =35 "0 '0 0 0 - 0 0 0 0 0 0 - 0 ` ' 0 . 0 0 0 0 _ 0 '" '�0 0 0. 0 0 __ 0 �224 0 0.0 31 = 266 -"'-0 0 0 0 0 _„_-_.0 0 0 0 --'0 0 0 10 0 0 --123 .0 _-._.._..:.0. 56 =-=O - . W . W� �CG (-C �G W HT--G --G C F= 13A-0gcs 2 glazing, clr low-e 2 glazlnq clr„, low-e 1A&s 3 2 glazing clr lgwE ,2glazing clr lcwe 2 glazing, clr Im s 2glazing,clrlow-e>........-0.650._s..u._18.20--...11.27 13A4ocs 2 glazmq caves 13A-0acs"lr l- 2glazing, clr lowe 2glazing, clr low-e .291azm9, clrlow,e_... 16B-30ad 22A-tph�,e,..� 0.143 0.650 0.650 0.143 0 650 0.650 0.650 0.143 0 650 0.143 0.650 0.650 „,_--,0.650 0.032 _ 1:358 420 2 1 ,_,_-,,,,, 377 60 18 12 34 5 422 1 1 ,,;,,..�......1 2277 = 202 1682 546 325 -- 1510 1092 325 218 .-,.__-273-169,.....,.___0,,,_._._.-.-0 138 146 �... 1691 164 273 ,a-,:, -285.v„„„319 2040 =7687 919 973 585 ='M 899 268 135 75 114 -9P4 214 303 3642 =-_A '0 0 0 0 0 _ 0 -' 56 0 0 0.w;1._._.0 �35 =--7 4 62 9 15 ._,,,.,e,�:.,w16 2277 =2277 61 c)AED excursion 0 -5 Envelope loss/gain 21086 11992 522 174 12 a) Infiltration b) Room ventilation 3339 .0 895 0 105 0 28 0 13 Internal gains: Occupants Q 230 Appliances/other 0 0 8400 0 0 0 Subtotal(lines 6to 13) 24426 21287 627 202 14 15 Less etdemal load Less transfer Redistribution Subtotal Duct loads 29% 45% 0 0 0 24426 7150 0 0 0 21287 9631 29% 47% 0 0 0 627 184 0 0 0 202 96 Total room load Air required (din) 31575 1383 30918 1383 8" 36 298 13 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -rw wrigt�tso6f!- 2020-May-2213:45:38 A Right -Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...It WAC1NDAMS HMS- 8108 AMALFI 2265 MODEL Arup Calc = MJ8 Front Doorfaces: N -�' Wrightsof- Right-M Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466.6799 FaC 772-466-6796 Email: OUICKCALCS@AOL.COM 1 2 3 4 5 Roan name Exposed wall Room height Room dimensions Room area O WIC 2 0 it 8.0 It heat/cool 5.0 x 7.0 ft 35.0 ft2 O BATH 6.0 0 8.0 ft heaticool 1.0 x 124.0 ft 124.0 ft2 Ty Construction number U-value (Btuh/ftMF) Or HTM (Btuh/ff2) Area or perimeter (ft) (BLtuh) (02) oorpedmeter (ft) Load (Btuh) Heat Cool Gross WP/S Heat Cool Gross I NIP/S Heat Cool 6 11 13A-0ocs 2 glazing, clr lowe 2 glazing, clr lcwe 2 glazing, clr lo✓✓- 2 glazing, clr low a 11D0__, 13A4ocs 2 glazing, clr low -a 2 gtazinq qlr laws 13A-4ocs 2glazing clr lave 'glazing cir:lowe 2glazing clr low-e .'glazing„clr Icw e„_, 13A-4ocs 'glazing clr low-e 13A4 cs 2 glazing, ch lowe 'gluing, clr low- 291azin9.clr lgw-e.....,, 16830ad 0343 0.650 0.650 0.650 0.650 - n' n n n n 40o 18.20 1820 1820 18.20 219 10.68 10.68 T10.68 10.68 -10.34 219 32.42 32.76 2.19 14.99 14.99 11.27 .,_,..11.27 2.19 14.20 2.19 -23.79 20.23 _,.e;2042 1.60 -0 A "'0' '.0, 0 0 -0 0 '0. e 0 10 -`0 0 0 " 0 0 0 0 _ 0 0 0 -0 0 ,.'0 0 0 0 0 D 0 0 ---0 0 "" 0 0 0 0 -0 0 . 0 "" .0 -0 4y .`.0.390 0.143 0.650 0.650 0:143 0.650 0.650 0'Wo -.0.650 0.143 0.650 0.143 0.650 '0:650 .._0.65o 0.032 _n_ a a a s.: s s s .ems.- sw sw w w w „wW - v10.92 4.00 18.20 18.20 400 1620 1820 1820 _-.»18.20 4.00 1820 400 18 20 1820 .,.„,a1820 0.90 =3802 "_,_ 0 0 0 0' 0. �O 0 _.v-.z„..m0 0 0 _0 0 0 m..._, ...>,o 35 -0-0-0-0 0 0 0 0 0 0 0 ._<®____,0 0 0 -�` 0 0 0 0 35 0 0 _m 0 0 0 0 0 n.._- 0 0 0 --"0 0 0 .:_.„-._, 0 31 0 0 _AO ,0 0 - 0 0 ,_. ,._.,0 0 0 0 0 0 . 10 0 '0 0 1,0 0 0 �0 0 0 0 0-0=,_.70 0 0 0 „_-..�0 0 _ 0 -39 1 .0 ;:_....,_.,..�0 124 ��fi 0 0 0 0 0 0. --g 0 0 --'156 164 0 __0 111 , �228� -0 0 0 0 0 0 '0 �D 0 0 "�85 214 0 198 0 ,,,,,,- t-C -0 0 0 e;._,.:.__0 56 48 9 0 --_0 124 _i C '.F _._ 22A-tph��__� ---_-_-_ �1.358 w35 �0 �.0 �0 =-724 6 c)AF_D excursion -1 110 Envelope loss/gain 31 55 659 608 12 a) Infiltration b) Roornventilation 0 0 0 0 90 0 24 0 13 Internal gains: Occupants @ 230 Applianceslother 0 0 0 0 0 0 Subtotal(lines 6to 13) 31 55 750 633 14 15 Less e)demal load Less transfer Redistribution Subtotal Duct loads 29% 471/6 0 0 0 31 9 0 0 0 55 26 29% 47% 0 0 0 750 219 0 0 0 633 3DO Total room load Alr required(cfm) 1 1 41 2 81 4 969 42 932 42 Calculations approved bYACCA to meet all requirements of Manual J Sth Ed. c -r'{:- wrl9tioYC- 2020-May-2213:45:38 'A RightSuite® Universal 2019 19.0.08 RSUOB101 Page 2 ...A WWADAMS HMS- 8108 AMALFI 2265 MODEL A.mp Calc=MJ8 Front Doorlaces: N P�Fwrightsoft Right-MWorksheet Job: 2265 MODEL- GAR LEFT Entire House Date: MAY 22, 2828 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS AOL.COM 1 2 3 4 5 Room name E)Vwed wall Room height Room dimensions Room area O TOILET 0 It 8.0 It heat/cool 4.0 x 6.0 ft 24.0 fN O LINEN 4.0 ft 8.0 It heat/cool 5.0 x 4.0 ft 20.0 ft2 Ty Construction number U-value (BtuMR°F) Or HTM (Btuh/ft2) Area (ft.) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PIS Heat Cool Gross NIP/S Heat Ccol 6 11 13AA5-=-m -� 2 glazing, cir laws 2 glazing, clr low- 2 glazing, clr lcw-e '2 glazing clr love a 11D0 -13A4ws 0.143 0.650 0.650 0.650 0:650 __- n n- n n n _n. a a a_ s s s, s ..,s_ sw sw - 4 00 11120 18.20 1820 18.20 -10.92 219 10.68 10.68 10.68 10.68 -10.34 -0, 0 -0 , 0 0 - 0 0 0 -0 . 0 , 0 0 0. 0 , ; 0 --'0 0 0 6 0 --0 0 0 0 0 0 0 -C 0 0 0 _0 . 0 0 0 0 0 0 -"0 0 0 0 0 2 glazing, clr Im-e 2 glazinq cly)ow-e 13AAws" 2 glazing clrlow-c 2glazing cirlaw-e 2 glazing clr low-e 2 glazing, clr.lpw-e __ 13A-4ocs 2 glwinq clr lower -13A46cs" . 2glazing clr lowe 2gluig clr,lwv 2glazmg rctr Icw_e_, 16830ad 0.143 0.650 0.650 0143 0.6w 0.650 0.650 -_._0.650 0.143 Q650 "'0.143 0.650 0.650 -0.650 0.032 4.00 18.20 18.20 '400 1820 1820 .1820 --18.20 4.00 18 20 - 4 00 '1820 1820 2.19 32.42 32.76 2"19 14.99 14.99 1127 _-11.27 219 14.20 "Zll) 23.79 2023 20_42 -0 --0.0.390 0 0 0 0 0- 0 0 _.__0 0 0 _0--0,�- 0 0 0 0 0 0 0 --0 0 0 ----0 ,0' 0 0 0 0 ':�""0 0 0 0 _;:,._0 0 0 _"70 .0 0 :_ 0 ..,,_.0 0 0 0 "`0 0 0 0 ...-,--0 0 0 0 0 0 ��0 '0 '0 0 -_0 0 0 0 0 0 """"""01-0 0=, 0 0 .___..,0 0 0 _ _ _ 0 0 0 0 0 0 --0 0 0 -"128 0 0 .0 __0y% 0 0 0 '-'- 10 0 0 0 ..._-..-D 0 0 -70 0 0 0 W Y-C Vly--fi w w w w_ 0 0 0 '-0 0 0 0 -32 0 0 0 -32 0 0 I--G I-G C -1820 0.90 1.60 _0 24 24 22 38 20 �0 20 18 32 F -- 22A-tph-.� �.:�....-.1358 . �38 02 =0.65 :=4 -= 0 ==0 -� =0 =20 ==4 =52 � 0 6 c)AED excursion -5 -3 Envelope loss/gain 22 33 298 99 12 a) Infiltration b) Room ventilation 0 0 0 0 60 0 16 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 200 0 0 0 Subtotal (lines 6 to 13) 221233 1 358 115 14 15 Less odemal load Less transfer Redistribution Subtotal Duct loads 29% 47% 0 0 90 111 33 0 0 48 281 133 29% 47%1 0 0 0 358 105 0 0 0 115 55 Total room load Air required(cfm) 144 6 414 19 463 20 170 8 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrYghtm ft- 2020-May-2213:45:38 RIghLFI 226 Universal .rup 19.0.08 RSU08101 Page 3 ...fl HVAC1ADAMS HMS-8108 AMALFI 2265 MODEL A.rup CaIc=MJB Front Door faces: N wrightsofr Right-d®Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-066-6799 Fax 772-466-6796 Emil: QUICKCALCS@AOL.COM 1 3 4 5 Room name Room height Room dimensions Room area WING ROOM 10.0 It 0 ft heat/ccol 1.0 x 185.0 ft 185.0 ft2 FOYER 70 ft 10.0 It heal/cool 7.0 x 10.0 ft 70.0 IF Ty Construction number U-value (Btuh/ftk*F) Or HTM (BtUWft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (fN) or Perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 33AA5E 2 glazing, clr lcwe 2 glazing, co- low-e 2 glazing, clr low-e 2 glazing, cir low-e JIDD 0;143 0.650 0.650 0.650 0.650 ..`.,_0,390 n n n n n -n_ 4 00 18.20 18.20 1820 18.20 10.92 2.19 10.68 10.68 10.68 10.68 a-10.34 '-' 140 0 30 '0 0 ___0 : 110 0 0 0 0 440 0 546 0 0 _-_..,,0 -241 0 321 0 0 ___0 -70 10 0 0 13 -20 -26 0 0 0 0 �20 _ 105 182 0 0 244 _....-223 57 107 0 0 143 _a-_,__211. G . W IL-CG 13A-0ocs 2 glazing, clr lcw-e 2 glazl,[Ip clr low�e 13A-0ocs' 2 glazing clr Ic w-e 2 glazing clr lave 2 glazing clr low-e -2 glazing, clr lave_`. 13A-0ocs 2 plaznq, clr lwa 13A-0pcs - 2 glazing, clr lave - 2glazing clr law-e 2 glazrtg ,cir I=,e_ 16B30ad 0.143 0.650 0650 0�143 0 650 0.650 0.650 _-0.650 0.143 0.650 0.143 0.650 - 0.650 0.650 0.D32 a a a s- s a s _a- sw sw -`w w , w _w_ - 4.00 18.20 1820 4:oo 18.20 1820 1820 _,._18.20 4.00 18.20 4 00 18.20 1820 -18,20 0.90 2.19 32.42 32.76 2.19 14.99 14.99 11.27. __11.27 2.19 14.20 ­'E.19 23.79 20.23 20.42 1.60 60 0 0 0 0 0 0 y.___-..0 0 0 '"- 140 0 15 0 60 0 0 0 0 0 0 ....._._...-_.0 0 0 " 1 0 1 240 0 0 ` 0-"�"y'0 - 0 o 1,0 -0 0 0 -�--"25 501 0 273 0 131 0 0 0 -0 0 _.._0 0 0 ' 273 0 303 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �"�•"'-0 0 0 0 ___0 0 0 ----- 0 0 0 0 0 0 0 '"W`� 0 - 0 0 0 _. o 0 0 0 0 0 ""r"0 , 0 .0 0 ___._-0 0 0 . W _G WII-----GG� 0 0 0 0 0 0 0 0 6 h-G- C 185 __-_,_,0 185 166 296 70 70 „_,�-_0 63 _._e-,-,0 112 - �..__ Fes. .._-. _�_-..__�___ 22A-Ipl1____:_� __�_.._. _ 1.359 T,_ „-_ _.. ,..�3802 �0.09 _ r_,-_�785 _ _ �,34 = - _,,.,..1293 :_„�,.0 �7.0 ��7 _ ._.�.. ,_..,..260 =_=_0 6 c)AED emursion 89 -15 Envelope loss/gam 3459 1655 1082 615 12 a) Infiltration b) Room ventilation 640 0 171 01 132 0 35 0 13 Internal gains: Occupants Q 230 Appllanceslother 0 0 0 0 1 0 0 Subtotal (lines 6to 13) 4099 1826 1214 650 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 29% 250/6 0 0 360 4458 13M 0 0 193 2019 497 29% 47% 0 0 -1214 0 0 0 0 -650 0 0 Total room load "required (cfm) 5763 252 2515 113 0 0 0 0 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed I&y}f =Isl so_fi- 2020-May-2213:45:38 A Right -Suite® Universal 2019 19.0.08 RSU08101 Page 4 ...It WAC ADAMS HMS- 8108 AMALFI 2265 MODEL A.mp Calc = MJ8 Front Door faces: N wrightsoft' Right-J@Worksheet Job: 2265 MODEL- GAR LEFT Entire House Date: MAY 22,2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466.6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM i 2 3 4 5 Room name Egcossed wall Room height Room dimensions Room area DINING ROOM 12.0 It 10.0 If heat/cool 120 x 11.0 ft 132.0 It' FAMILYROOM 17.0 ft 10.0 ft heat/cool 1.0 x 410.0 ft 410.0 ft' Ty Construction number U-value (BtutVft?'F) Or HTM (Btuh/ft') Area (ft') or perimeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 07143 0650 0.650 0.650 0.650 .-0.390 n n n n n _n_ 4 G0 1820 18.20 18.20 1820 ^-10.92 21g 1068: 10.68 10.68 10.68 -10.34 -' 710 0 '0 ' 36 0 -0 -74 0 0 0 0' 0 -296 0 0 _ 655 0 -0 -162 0 0 385 0 0 13446F 2 glazing, clr low-e 2 glazing, clr lcwi 2 glazing, or low-e 2glazing clr low-e "-"--0 0 A ' 0 0 --0 -'--0'""0 .0 • 0 0 '0 --0 0, ^ 0 0 0 nLL.___-0 -o 0 0 ., ., 0 0 --0 ..11D0 Vy I�-CC 13A-4ocs 2 glazing, clr low-e gazing cr low-e 13A466s glazing, 2 glaze clr lower 2 lazier clr lave glazing, 2.glazing, clr low-e.„„s.._a--. 13A-4ocs 2 9;46cs clr low-e 2 glazing clr Icw a 2 g lab cir lcw-e 23Aazing, clr low-e._„a, 16B30atl 0.143 0.650 0.143 0.650 0.650 -0.650 0143 0.610 0.650 0.650 �..-_._0.650 0.032 a a e s s s .-a- sw sea w w _w.. - 4.00 18.20 4.00 18.0 18.20 _.,,18.20 4.00 11,20 18.20 18.20 18.20 0.90 38.02 2.19 32.42 2A9 1199 11:27 219 14,20 23 79 20 23 _,.,,20,42 1.60 =0.00 0 0 ' 0 0 0 0 0 _ 0 0 0 .a,„,...,._,;, O _ 132 p_..,132 0 0 _�_ 0 0 .0 0 0 _.-...._.._._0 0 _ 0 0 0 �._.,,,.,.._10 132 =12 0 0 _-�,�„0 0 0 0 0 .,�..0 0 0 0 0 0._...-__r. -'--0 0 0 0 --0 0 0 0 0 � 0 211 0 0 0 170 30 18 0 -_0 0 0 0 0 0 410 u„_430 0 0 _�� 0 122 30 18 0 --.0 0 _ 0 0 0 .0 410 _ =7 0 0 ._ 6 48g 325 325 0 -_0 0 -0 0 0 m,„ --0 367 --"-Erl6 0 0 _.__. 0. ' 267 268 268 0 --0 0 0 0 0 0 �...,_ -0 656 �-0 l W 0 0 • 40 �a 118 .= 456 a C `F= 22{rtpt -= ` 1358 0 6 c)AED exourslon -28 -99 Emelope loss/gain 1566 751 2374 1541 12 a) Infiltration b) Roomventilation 226 0 60 0 320 0 86 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 400 0 0 2600 Subtotal (lines 6to 13) 1792 1212 2694 4227 14 15 Less external load Less transfer Redistribution Subtotal Duct leads 29"/ 47% 0 0 456 2248 658 0 0 252 1464 694 29 47% 0 0 319 3012 882 0 0 175 4402 2087 Total room load Air required(cfm) 2906 127197 2158 3894 171 6469 290 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. �, -FW wrr9„�+tso�ft� 2020-May-2213:45:38 A&A Right-SuiteSLFI226 Universal20191 Cale M.18RSUF01 Page5 ...ft INACWDAMS HMS-8108 AMALFI 2265 MODELA.mO Cale = MJB Front Door faces: N wrightsoft' Right-M Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Far. 772-466-6796 Email: OUICKCALCS@40L.COM 1 2 3 4 5 Room rate E posed wall Room height Room dimensions Room area BREAKFAST 8.2 it 10.0 it heatfccol 1.0 x 61.0 it 61.0 ft2 KITCHEN 0 it 10.0 it heat/ccol 14.0 x 15.0 it 210.0 ft2 Ty Construction number U-value (BtuhlfP-°F) Or HTM (Btuwf.) Area ((t2) or perimeter (it) Load (Btuh) Area (it) or perimeter (0) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 134-0acs 2 gluing cir lave 2 glazing, cir lowe 2 glazing clr lowe 2 glazing clr lave -11D0�.�,, --- 13A-4ocs 2 glazing, clr lcw-e 2 olazinq clr lowe 13A4ocs 2glazing clrlowe 2.gIa;J gluing,, cltlow-e_.._- 2 glaiag cir lowe 2glazi - 13A4ocs 2 glazire clr low-e 2 gluing clr lave 2gluing cir low- 2glazing„clr lower, 16B80ad 0143 0:650 0.650 0.650 0.650 -0:390 0.143 0.650 0650 -0143 0.650 0.650 -,_0.650 0.143 0.650 0.143 0.650 0.650 .__0.650 0.032 ,_,?,, :358 `n n n n In -n_ a a a s - s s ,_s,.- sw sw _w- w w ew_ - 2 00 1820 18.20 1820 18.20 mg 10.68, 10.68 1068 10.68 0 0- 0 0 0 `.a._.s.._ 0 "-0 0'' 0 0 0 0 0 0 0 ., 0 "'"�0 '0. 0 0 , 0 -0 -'0 0 0 0 0 --' 0 0 0 0.. 0 '��0 0 0 0 0 -0 0 0 0 ' .: 0 0 W -10.92 4.00 18.20 1820 " 4.00 1820 18 20 18.20 4.00 18.20 4 00 18.20 1820 `18 20 0.90 .a38 U v_10.34 Z19 32.42 3276 219 14.99 11 27 _ 11,27 2.19 14.20 2:19 23.79 20.23 .�„20.42 1.60 0 0 0 '�'- 40 •, 0 12 --0 42 8 - -'0 0, 0 ;v`;0 �.,_,.,-:0 0 0 0 �"" 28 0' - 12 -0 34 5 -,..-,..,,__,0 0 0 0 112 0 218 � -0 138 146 F-.0 0 0,':. 0 0 0 0 - -�-61 0 135 __.__ -0 75 114 ---0 0 0 __,_„_;.0 0 0 0 -0 0 , -_.0 0 0 0 0 ---0 0 0' 210 .,_,--0 0 0 0 --=-0 �0 0 0 -.._ 0 0 0 --'0 0 10' 0_.,�0 --„,.0 0 0 0 - ----" 0 0 0 0 �. 0 0 0 --70 0 . 0 0 0 0 --""""- b 0 + 0 ' 0 � _0 0 0 --0 0 10 _ W Y-G -0_.;._ 0, 0 0 b13AA6cs- C 61 61 55 311 �.0 98 210 188 -_____ 336 bW ',"_e=M _'=8_„,� ,.,:_..-o '~210 =-,-P =,_:0 ---0 6 c)AED excursion 5 -35 Emelope loss/gain 979 488 188 301 12 a) Infiltration b) Room ventilation 1 155 0 42 0 0 0 0 0 13 Internet gains: Occupants @ 230 Appllances/other 0 0 900 0 0 1200 Subtotal (Ines 6to 13) 1134 1429 188 1501 14 15 Less eMemal load Less transfer Redistribution Subtotal Duct loads 29% 47% 0 0 0 1134 332 0 0 0 1429 678 29% 47% 0 0 22 211 62 0 0 39 1540 730 Total room load Air required (cfm) 1466 64 2107 94 272 12 2270 102 Calculations approved bV ACCA to meet all requirements of Manual J 8th Ed. c w�1gtilso�T-t- 2020-May-2213:45:38 A RigALFI 226 Universal .rup 19.0.08 RSU08101 Page 6 .-.ft HVACUIOAMS HMS. 8108 AMALFI 2265 MODELA.rup Calc = MJB Front Door faces: N wrightsoft' Rig ht-J@Worksheet Job: 2265 MODEL- GAR LEFT Entire House Date: MAY 22, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Far 772466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name E�osed wall Room height Room dimensions Room area RATH3 15.0 ft 8.0 ft heat/cool 1.0 x 100.5 ft 100.5 fP HALLWAY 0 ft 8.0 It heat/cool 14.0 x 3.0 ft 42.0 W Ty Construction number U-value (Btu[Vft? °F) Or HTM (Btutvft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (fl2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Coal Gross N/P/S Heat Cool 8 11 1f3A-4acs 2 glazing, clr low-e 2 glazing, clr lowe 2glazing, clrlow-e 2 glazing, Grlcw-e 0,143 0.650 0.650 0.650 0.650 �-01390 0.143 0.650 0.650 0.143 0.650 0.650 0.650 _-0.650 0.143 0.650 0.143 0.650 10.650 �0.650 0.032 n n i n n n _n_ a a a -a-, s s s� -s_ sw sw -"w" w w .._w_ - "' 4 W - 18.20 18.20 1820 18.20 J,1092 4.00 18.20 �10 20 ' 400 18 20 18.20 18.20 _.18 20 4.00 18.20 400 1820 11 1820 -__18.20 0.90 .,_„_3802 2-19 10.68 10.68 10.68 10.68 ,_...10.34 2.19 32.42 32.76 219 14.99 14.99 11.27 _---11.27 2.19 14.20 219 23.79' 20.23 ,,,,_2042 1.60 „-r0.00 -- , 0 0 0. , 0 ._0 -'-"0 , :0 0 0 0 0 ""- o 0 0 0 e 0. __�__..-0 0 0 0 -""`" 288-7150 0 0 0 _A 0 0 130 - 0' 0 ,_285 90 , 0 0 0 0 0 a.Y,._O 0 0 90 0 ` 0 0 �_0 0 0 ` -71 0. 0 �319 161 -' U ,0 0 -0 , 0 -0 0 0 0 ` 0 0 01 0 -0 0 0 •0 0 0 - 0 0 0 0 0 0 -0 W 13A4ocs 2glazing, clr low-e 2 glminq clr low-e 13A-0ocs 2 glazing clr low- 2 glazing clr low-e 2 glazing clr 1=4 .2 glazing, clr low:e-.- 13AAms 2 glazing clr low_e 13A4 cs 2glazing clr low-e 2g1azing clrlow-e 2glazing, clir,i a ., 16B30ad 0 0 0 0 0 0 -""�72 0- 0 � 0� --0 0 0 --32._'- 10 0 0 0 0 0 0 0 "'-0 0 0 0 _-0 0 0 M,._ .-0.` 0 0 0 38 0 0 0 "--'�"�-0 0 0 ' 0 ,_-0 0 0 -6 t0 0 L�---GG 4y �C. "``-"-72 0 0. 0 -0 0 0 "-` 48 0 ', •• -0 0 0 . g 0 .r_.__0 0 0 '---0 0 0 0 0 0 0 __ '-o 0 0 ---0 . 0 0' I��-ICC' Yy T-C t-C C -.___'-_:16 101 =01 101 ..`u...,....:.15 _0 42 ,0 42 ,-0 67 .2.-�.�,_0 :.,.�,.,...42 .�.;,_,,...,0 ,,,_:�.:_,.0 �0. 6 c)AED excursion 165 -2 Envelope loss/gain 1363 874 38 66 12 a) Infiltration b) Room ventilation 226 0 60 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1589 934 38 66 14 15 Less Wemal load Less transfer Redistribution Subtotal Duct loads 29% 47% 0 0 0 1589 465 0 0 0 934 443 29% 47% 0 0 -38 0 0 0 0 -66 0 0 Total mom load Air required (cfm) 211 g0 1377 62 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -fl - wrl9r+mofC- 2020-May-2213:45:38 .&P. Right -Suite® Universal 2019 19.0.08 RS008101 Page 7 ...B HVACIHDAMS HMS- 8108 AMALFI 2265 MODELA.mp CaIc=MJ8 Front Doorfaces: N * wrightsof , Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 77246&6796 Email: OUICKCALCS@AOL.COM Job: 2265 MODEL- GAR LEFT Date: MAY 22, 2020 By: 1 2 3 4 5 Room name F_lgosed wall Room height Room dimensions Room area AHU CLST 0 ft 8.0 ft heat/cool 4.0 x 5.0 ft 20.0 ft' UTILITY 0 ft 8.0 ft heat/cool 1.0 x 68.0 ft 68.0 ft' Ty Construction number U-value (BtulVftMF) Or HTM (Btuldit') Area (0') or perimeter (ft) Load (Btuh) Area (0') or perimeter (ft) Load (Btuh) Heal Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 0343 '0650 0.650 0.650 0.650 __„„_0.390 0.143 0.650 0650 0143 0.650 0.650 0.650 _._--_0:650 0.143 0.650 0.143 0.650 0.650 „�M,0.650 0.032 n n n n n _n_ a a a 'a s s s _s_ sw sw -'w' w w _w- _ 4'00 1820 18.20 18.20 1820 1092 4.00 18.20 1820 '4.00 18 20 1820 1620 _18.20 4.00 18.20 -4 00 a 18.20 111.20 _,._18 20 0.90 239' 1068 10.68 10.68 10.68 -_,..10.34 2.19 32.42 3276 2 19 14.99 1499 11.27 -11.27 219 14.20 2:19 23.79 20.23 _,,,,20.42 1.60 0 0 D 0 0 :.,.,._..._0 0 0 0 - 0--0 0 0 ; 0 -0 0 0 -- 0 0 '0 .._„„�--0 20 `-' 0 0 0 0 0 -0 0 0 0 0 0 .0 _-0 0 0 - �. 0 0 ' 0 o - �0 0 0 '. 0 0 i40 0 0. .0 0 13A-0acs 2glazing clr low-b 2 glazing clr love 2 g1mi g clr lave 2glazing clr lave M000 .�...._ m- 13A-4ocs 2 glazing, clr low-e 2glazmq clr low_e 13A-0 s 2 glazing clr lowe 2 glazing clr low-e 2.glazing, clr low-e 2.glazing, clr,lowe- 13A-4ocs 2 glaiinq clr low-_e 13A-0acs ." '-' 2 glazing clr love 2 glazing clr lave 2:glazng, clr low:e 16B-30ad __-T-.O 0 0 0 0 ',_„__,,,,._0 ..:; 0 0 0 0 0 3 0 0 0 0 0 --70 0 0 0 0 W ------ 0 0 0 --0 0 0 0 ._;_.___0 0 -�, 0 0 0 0 „�.--0 18 �,_,.-0 -,__;„_--D 0 0 0 0 0 0 ,-0-'0 0 0 0 0 0 0 '-O - 0 0 0 , -0. 0 0 0 0 . 0-0 0 .. 0 _,_.-.._0 0 '0 0 __.0 0 0 0 0, -0 0 0 0 0 -0 Vy �-_-G, G 0 0 - -._0 0 0 -_.---0 32 0 0 _0 0 0 .__.v o 68 0 0 0 ,.. 0 0 0 68 0 0 -0 0- 0 �.__7___0 61 0 0 `-0 0 ' 0 --„�.-0 109 y C _ F_' � _,�___ 20 ==0 22A-tpli _ 1.358 „+ 7-38.02 =-0.00 Z_-,_20 ,=0 ==_68 �-0 0 =:=0 61 c)AED excursion -1 -16 Envelope loss/gain 18 31 61 93 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 600 Subtotal (lines 6 to 13) 18 31 61 693 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 1 29% 47% 0 0 -18 0 0 0 0 -31 0 0 29% 47% 0 0 17 77 23 0 0 29 721 342 Total room load Air required (cfm) 0 0 0 0 100 4 1063 48 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. f wrfghfso�T^t- 2020-May-2213:45:38 p RlghtSuile® Universal 2019 19.0.08 RSU08101 Page 8 ...fl WACIADAMS HMS- 8108 AMALFI 2265 MODEL A.rup Calc = MJB Front Door faces: N wrightsoft• Right-M Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By- 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 7724666799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Bqoosed wall Room height Room dimensions Room area BATH 2 0 It 8.0 it heat/cool 6.0 x 9.0 0 54.0 fP CLST 2 2.0 ft 8.0 it heat/cool 11.0 x 2.0 it 22.0 N' Ty Construction number U-value (BtuhHt?°F) Or HTM (BtuhRP) Area (0') or perimeter (it) I-nad (Btuh) Area (f(2) or perimeter (0) Load (Btuh) He Cool Gross NIPIS Heat Cool Gross NIPIS Heat Cool 6 11 13A-035 2 glazing,'cir Iawe 2 glazing, clr lav-e 2 glazing, clr low-e 2 glazing, clr lovwe J1DO 13AAccs 2 glazing, clr low-e 2 gluma clr low_e 13A46cs 2 glazing clr lcwre 2glazing clr low-e 2 glazing, clr lade 2'glazing, clr low-e__ 13A-0acs 2 glazing clr low-e 13A-0acs`� `. 2 glazing cir lows 2 glazing clr lowe 2glazeg ,clr„lavt_e_,,,� 16B-30ad 0143 0.650 0.650 0.650'n 0.650 .,.,.„Y0,390 0.143 0.650 0.650 0.143 0.650 0.650 0.650 ____-.0.650 0.143 0.650 0:143 0.650 0.650 0,650 0.032 n n n n -,"n„ a a a s s s s., ..s., sw sw w w w w. - 4 00 1820 1820 1820 1820 u- 10 92 400 18.20 18 20 400 1820 1820 1820 _-18.20 4.00 18.20 4.00 18.20 18.20 _1.8.20 0.90 219 1068. 10.68 10.68 10.68 _�10.34 2.19 3242 32.76 2.-19 14.99 14.99. 11.27 -71.27 219 14 20 219 23.79 2023 __20.42 1.60 (fOO -- -"0 0 0 0-' 0 -0 0 0 0 0' 0 0 0 _._ __.O 0 0 -"�"-0 0 0 0'' 0 ---0 -0 .0 0 0' 0 0 --0 0' 0 0 0. --0 "-"-0 10 0 0 0 _ 0 0 0 0 0 '0 ,„-, O "'-`�0 0 0 0 0 __ 0 -0 0 0 ..0 0 �_......�_. , 0 4y Vl�r�-CG �C 0 0 0 0 0 0 0 -,-0 0 0 .V-""' 0'' 0 0 ._______O 54 0 0 0 0 0 0 0 0 0 0 --____0 0 0 16 0 0 16 0 0 64 0 0 -0 0 0 0. -0 0 0 ---0 0 0 '0 35 0 0 6 0 '0 0 ----,--0 0 0 `---- -o . 0 0 ,�__O 35 - 0-- .. 0 - 0 0 -0 0 0 0 '0 - 0 -0-0-0 48 -'0 0 0 0. --0 0 0 0 .0 0 0'- 0 0 0-'-' 0 0 �G W t-G -0 0 0 '0 54 0 0 0 0 0 0 0 C 86 22 72 20 F 22A-t`ph� 1:358 :„_ =38 02 l54 _=_0 '=0 0 =22 2 =76 =.._0 6 c)AED excursion -2 -2 Eaelope loss/gain 148 84 160 68 12 a) Infiltration b) Room ventilation 0 0 0 0 30 0 8 0 13 Internal gains: Occupants @ 230 Applienceslother 0 0 0 0 0 0 Subtotal (Ines 6to 13) 48 84 ISO 76 14 15 Less eodemal load Less transfer Redistribution Subtotal Duct loads 29% 47% 0 0 8 56 16 0 0 13 98 46 29% 47% 0 0 _190 0 0 0 0 _76 0 0 Total mom load Air required Won) 72 3 144 6 0 0 0 0 Calculations approved bvACCA to meet all requirements of Manual J Sth Ed. 2020-MaY-2213:45:38 A RighLFI 226 Universal .rup 19.0.08 RSU08101 Page 9 ...ft HVACIADAMS HMS- 8108 AMALFI 2265 MODELA.mp Calo = MJ8 Front Door hoes: N P�wrightsoft Right-MWorksheet Job: 2265 MODEL- GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By, 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 FaX 772-466-6795 Email: QUICKCALCS@ADL.COM 1 2 3 4 5 Room name Fposed wall Room height Room dimensions Room area BEDROOM 2 12.0 it 8.0 It heat/cool 11.0 x 12.0 It 132.0 fN BEDROOM 3 11.0 It 8.0 It heat/cool 11.0 x 11.0 It 121.0 112 Ty I Construction number U-value (Btul0W) Or HTM (Btuhlft2) Area (ft2)Load or perimeter (ft) (Btuh) Area (ft2) or perimeter (ft) Lead (Stuh) Heat Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool 6 11 13A-0ocs 2 glazing, clnlow-e 2 glazing, clrlowe 2 glazing, clr low-e 2 glazing, clr low-e UDO_„_._..._a_____ 0:143 0,650 0.650 0.650 0.650 re._..0.390 n n n n n _n_ -" 6 00 '1820 1820 1620 .18 20 -10.92. 2'19 1068 10.68 10.68 10.68 _„„ 10.34 -0 0 '0 0 0 _,_„„,.„,0 0 .- 0 0 0 0 -0 --l0 •• 0 0 0• 0 „0 ' -- 0 0 0 0 0 _0 --0 0 0 -0 0 -._,_0 -" 0 0 0 0 0 _ o --0 0 0 0 0 _ --0 -o 0 0 0 0 ,..,v o y/ I�-GG 13A flocs 2 glazing, cir love 2 glazing clr Igw e 13A46cs` `'2 glazing clrlow-e 2 glazing, clr low-e 2glazmg, clr,low-e 2glazin clr,low-e- 13A-0acs 2 glazing cir lower 13A4&s 2 glazing, cir loiw a 2gluig clr lower 2 glazng clr low;e_ 168.30ad _ 0.143 0.650 0.650 0143 0.650 0650 0650 _ ___0.'650 0.143 0:650 0:143 0.650 0.650 _-0.650 0.032 1.359� . _ . a a a s - s- s s __s_ sw sw -i w w -w_ - - 4.00 18.20 18 20 4 00 1820 1820 , ,1820 ._-1&20 4.00 18.20 -•406 18.20 ,1820 18.20 0.90 =38 02 2.19 32.42 32.76 219 14.99 14.99 11.27 _ 11.27 2.19 14.20 =2:19 23.79 20.23 a20.42 1.60 - -0,00 -_ 96 15 0 "- 81 1 0 ,sue 0 0 0 01 ______0 0 0 - 0 0 0 0 132 -12 324 273 0 177 486 0 �`- 0 0 0 0 _0 0 0 „-..0 0 0 __0 211 .�0- 88 15 0 --0 0 0 0' ____v0 0 0 -`0 0 0 73 1 0 `-0 0 0 0 __�,0 0 0 ., .,...e. 0 0. 0 0 292 273 0 -1-0 0 0 0 ___0 0 0 , 0 0 0 0 160 486 0 1 `0 0 '0 ,_,._,.....0 0 0 `0 0 . -'0 0 0 0 °. 0• _0 0 0 "-'-'0 _ 0 0 ___0 118 �- 45G -0 0 '0 0 '_,_�0 0 0 -" o 0 • -0 ---0 194 W t-C V�hl--G I---G II-CG C -0 132 - �1 � 32 _0 121 _..�� 21 121 - 108 - 11 '�`-` e48 �__,,-' O ----_ _ _ 6 c)AED excursion _24 _25 Envelope loss/gain 1172 850 1092 815 12 a) Infiltration b) Room ventilation 181 0 48 0 166 0 44 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 500 0 0 550 Subtotal(lines 6to 13) 1353 1399 1258 1409 74 15 Less eodemal load Less transfer Redistribution Subtotal Duct loads 29% 47% 0 0 194 1546 453 0 0 83 1482 703 29% 47% 0 0 188 1445 423 0 0 72 1482 702 Total room load Air required (dm) 1999 88 2184 98 1868 82 2184 98 Calculations approved byACCA to meet all requirements of Manual J 8th Ed y}F wrl9ti�o�'t' 2020-May-2213:45:38 A Right -Suite® Universal 2019 19.0.08 RSU08101 Page 10 ...it HVAC\ADAMS HMS- 8108 AMALFI 2265 MODELA.mp Cale =MJ8 Front Door faces: N I I wrightsoft Right-M Worksheet Job: 2265 MODEL- GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772A66-6799 F= 772A66-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name E)qosed wall Room height Room dimensions Room area CLST3 20 It 8.0 ft heat/cool 6.0 x 20 it 12.0 ft- LINEN 0 it 8.0 It heat/cool 1.0 x 4.0 It 4.0 W Ty Construction number U-value (Btuh/f(? °F) Or HTM (Btuh/0') Area (fP) or perimeter (ft) Load (8tuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat CMI Gross N/PIS Heat Cool 6 1t . VIl I�----GG W�-G �G IL-fG' IN - ' 13A:2 - 2glazing cir lower 2 glazing cir low-e 2glazing, cir low-e 2glazing, cir low-e 13A-0acs 2 glazing, cir Icve 2 glazing cir low_e 13A-flocs 2.glazing cir lower, 2glazing cir low-e 2glazing cir lave 2glazing-cir low:e_ _ 13A-4ocs 2glazing cir law-e 13A-0gcs 2 glazing cir lwFe 2glazing, cirlow-e 2 glazing; cir Irnv:e__ 16830ad 22A-tph�___ 07143 0650 -0.650 0.650 0.650 ..,a,.0.390 0.143 0,650 0.650 0143 0 650 0.650 -0.650 -0.850 0.143 0.,650 --0.'143 0.650 0.650 _,0.650 0.032 1 .358 n n n n n _n_ a a a s s s s, -s_ sw sw_ w w w _w_ - 400 1820 18.20 1820 1820 10.92 4.00 18.20 18.20 4.00 18.20 1820 1820 --18.20 4.00 18.20 4.06 18.20 18.20 -18.20 0.90 =38.02 2-19' 1068 10.68 1068 1068 ,,,„„t0,34 219 32A2 32.76 219 14.99 14.99 11.27 -11.27 2.19 1420 - 2.19 23.79 20.23' -20,42 1.60 -0.00 -- 0''0 -.0 '0 -0 0 _ D,.._._..,,,.0 16 0 0 0 0 0 0 16 0 0 0 0 0 -_.0 0 0 --0 0 0 --0 0 0 - 0 0 -v.w..:.w._0 64 0 0 0 ,0 0 0 -„a_0 0 0 ._...-.,.._.-�D _ 0 0. -",0 0 0 0 0 ---0 35 0 0 . 0 0 0 0 0 -0 0 0 0 0 0 0 0 0 : __o 0 0 0 -�0 0 0 0 _..-..0 0 0 ..--.._ 0 �. -.0 0 ---0 0 0 0 0 0 0 0 0 --0 0 0 0 0 .,,.�.0 0 0 0 -0--0 0 0 0 0 0 '.--'--,._,..0 0 0 �"-"'0 0 0 0 -0 0 0 -'-0 . 01 0"" 0 ; 0 0 0 -__.0 0 0 _..-.-_..._..0 0 0 '��` 6-0 . 0 0 0 --0 0 0 .�. -0 0 0 '' 0 0 0 ._.v._0 0 0 -...._.__-0 0 0 C -0 12 �„12 -_0 12 2 _-,I) 11 w -0 19 '��-78 0 ___,0 4 _0 4 _.-_0 _0 6 �'� 4 ____"0 _ __4 __0 L---0 6 c)AED excursion -1 0 Emelope lossfgam 151 53 4 6 12 a) In90ratlon b) Room ventilation 30 0 8 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 181 fii 4 6 14 15 Less e)demal load Less transfer Redistribution Subtotal Duct loads 1 29% 47% 0 0 -181 0 0 0 0 -fii 0 0 29% 47% 0 0 A 0 0 0 0 -6 0 0 Totel room load Air required (dm) 0 0 0 0 0 0 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -91t• wrl9titsoii- 2020-MaY-2213:46:38 -' RighlSuite® Universal 201919.0.08 RSU08101 Page 11 ...d HVACIADAMS HMS- 8108 AMALFI 2265 MODEL A.mp Calc = MJ8 Front Door faces: N #wrightsoft' Right-M Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By, 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-066-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area CLST 4 2.0 ft 8.0 ft beat/cool 6.0 x 2.0 ft 12.0 W HALL 0 It 8.0 It heat/cool 4.0 x 4.0 it 16.0 fP Ty Construction number Ll-value (Btuh/ft? °F) Or HTM (Btuh/ft') Area (ft') or perimeter (it) Load (Btuh) Area (w) a perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 11 2 glazing clr,lowe 2 glazing clr low-e 2 glazing, cli lcw-e 2glazing, clr low-e .11D0,�,,,.,,, 0143 0.650 0.650 0.650 :0.650 ,_,�:0,390 n n n n n -n_ '- 4 00 18.20 1820 , 1820 1820 -1092 2.19 10.68 1068 10.68 10.68 -10.34.-0 - 0 . 0 " '0 .0 ` b --0 '0 0 0 0 --,,.__.0 0 0 0 0 " '0 _,_._0 0 0 0 '0 0 0 -0 0 0 0 0 _,._„_,-0 -0 0 '0 0. •0 _0 --0 0 0 0 0 _0 --0 0 0 0 = 0 ,_,_0 V)1 13A-0ocs 2 glazing, clr low-e 2 olazinq clr low-e 13A4ocs 2 glazing dr low-e 2 glazing clr low- 2 glazing clr low-e 2.glazing, chlow-e--_- 13A-4ocs 2 glazing clr Ivy_e 13A-0ocs ,. , 2glazlrig clr laws 2 glazing, clr low-e 2 glazing clr I=,,e ,,-.. 16B30ad 22A-tDh� 0.143 0.650 0.650 0:143 0.650 0.650 0.650 _._,_.0.650 0.143 0.650 0.143 0.650 0.650 _,d,_0.650 0.032 ::=l.358 a a a s s s s' _a- sw sw w w w _,w_ - _. 4.00 18.20 18 20 4.00 1820 16.20 1820 -18.20 4.00 _ 18.20 400 1820 18 20 -,._18 20 0.90 _3802 2.19 32.42 32 .76 219 1499 14.99 1127 -11':27 2.19 14.20 2.19 23:79' 20.23 20.42 1.60 =A.00 16 0 0 `� 0 0: 0; 0 _,-__,_0 0 0 `---a 0 _ 0 --0-' 12 �.a.12 16 0 0 �'-v0 0 0 0 __0 0 0 -�---0 0 . 0 12 g_2 64 0 0 �'� 0 -' 0 0 0 -,.._..--0 0 0 �P"-0:M-'-`0 0 .. 0 0 35 0 0 --0 0 0 ,0 -_-0 0 0 0 0 0 -0 0 • 0 +0 _.._-_0 0 0 `-"-.'�-0 0 '0 0 0 00 0 0 0 0 0 -0 - 0 0 •0 ---0 0 0 0 0. 0 •- 0 -0 0 0 0 - 0 0 0 __.-„..0 0 0 � '-`-0 0 0 0 14 =-0 _ Vd Y-C WI-1' �C. LC C •F„�_ '0 0 - 0 19 =u.-_,.0 0 0 -0 -0 16 = 0 -,"0 0 0 ___,_,_0 26 ==0 11 :-76 -0 16 =98 6 c)AED excursion -1 -1 Envelope loss/gain 151 53 14 25 12 a) Infiltration b) Room ventilation 30 0 8 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appllances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 181 61 14 25 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 29% 47"/ 0 0 -181 0 0 0 0 -61 0 0 29% 47% 0 0 -14 0 0 0 0 -25 0 0 Total room load Air required (cfm) I 1 0 0 0 01 1 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. c t• =Ioftt cwt- 2020-May-2213:45:38 Right -Suite® Universal 2019 19.0.08 RSU08101 Page 12 ...t HVACIADAMS HMS- 8108 AMALFI 2265 MODEL A.mp Calc = MJB Front Door faces: N wrightsofC Right-M) Worksheet Job: 2265 MODEL -GAR LEFT Entire House Date: MAY 22, 2020 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: DUICKCALCS@AOL.COM 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Roorn area BEDROOM 24.0 ft 8.0 It heat(cool 11.0 x 13.0 It 143.0 1? OWNERSBEDROOM 39.0 It 8.0 ft heattcool 14.0 x 16.0 ft 224.0 f 2 Ty Construction number U-value (BtuWfP-°F) Or HTM (BtuWft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft-) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P!S Heat Cool Gross N/P/S Heat cool 6 11 r13A'-069 2 glazing, clrim-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e J1D0 400 1820 18.20 1820 1820 `10.92 219' 1068 10.68 1068 410.68 -._10.34 00 , 0 0 0, 0 -__-0 0 0 0 0 •-0 " 0 0 0 0 0 _._.0 0'-'-'-0-`�"0 -0 0 0 -,0 0 0 0 0 ,. 0 -0 0.143 0.650 0.650 0.650 0,650 -0.390 n n n n n -0_ 0 0 0 _ 0 -0 - 0 0 0 0 0 0 - •0 .0 0 0 .0 ___--__0 _�... V+1 13AAcos 2 glazing, clr lox-e 2 clazlrw clr Im-e 13A4acs 2 glazing, clr ow-e 2 glazing clr low-e 2 glazing, clr love a 2.g1mi g, or 13A4ocs 2glazinq clr lowe 13A466s - 2 glazing clr lovv-e 2 glazing, clr lowe 2 glazing..clr,lowe.----. 16BJOad 0.143 0.650 0.650 -0..143 0.650 0.650 0.650 ---0.650 0.143 0.650 "0143 0.650 0.650 _o.650 0.032 a a a s •• s s s „.s.;. sw sw w w w ,_w_ - 4.00 18.20 18.20 4 00 18.20 18.20 18,20 ._._.18.20 4.00 1820 `400 18.20 1820 ,,. _182o 0.90 �_38 02 2.19 3242 32.76 219 14.99 14.99 11.27 _._r11.27 2.19 1420 219' 23.79 20.23 _,,,-20.42 1.60 _--Z-0.00 104 0 0 7 -88 0 0 , 0 ._„_,__15�15 0 0 �WO - 0 0 _�;;.:.0'-,. 143 :=--143 104 0 0 73 - 0 0 0 0 0 416 0 0 '392 0 0 0 273 0 0 228 0 0 160 0 0• 0 :-.,.w._169-0 0 0 72 0 18 54 0 1 -82 30 0 0 -_..O..W._-. 0 0 `28 "`� 1 0 0' . 0 217 0 325 -328 546 0 0 () 0 0 --513 0 0 '_0 118 0 585 -179 450 '0 -0 -,...._.,_0 0 _ 0 280 '0 •0 0 112 '"30 0 0 0 0 128 0 0 o . W -G -' ­ 0 0 0 o 143 0 ' . 0 0 0 --0 .. 0 0 4-C . C 128 -'- -,;-_0 229 „_ 224 =224 224 =39 201 =4n -w_,_„ 358 �=_0 F_-- 22A-tp6-_ :. „. =1.358 _,.;;„ ;_.=..�24 = 913 ==0 Wpm 6 c)AED emulsion -33 -70 Envelope loss/gain 2022 752 3612 1902 12 a) Infiltration b) Room ventilation 361 0 97 0 587 0 157 0 13 Internal gains: Occupants Q 230 Appliances/other 0 0 5501 0 1 0 9D0 Subtotal (lines; 6to 13) 2384 1399 4200 2959 14 1151 Less eldemal load Less transfer Redistribution Subtotal Duct loads 29% 47% 0 0 188 2571 753 0 0 72 1471 698 291/6 47% 0 0 0 4200 1229 0 0 0 2959 14D3 Total nxxn load "required (rim) 3324 146 2169 97 5429 238 4362 195 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed I&-OW wrl9ti�o�T'_e- 2020-MaY-2213:45:38 N -' RighlSuite® Universal 201919.0.08 RSUC8101 Page 13 ...It HVAC1ADAMS HMS- 8108 AMALFI 2265 MODELA.nip Cale =MJ8 Front Door faces: N �- wrightsoft' Duct System Summary Entire House QUICK CALLS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34948 Phone: 772-466-6799 Fax 772466-6796 Email: OUICKCALCS@AOL.COM For. ADAMS HOMES 8108AMALFI CIRCLE, PORT ST LUCIE, FL 34951 Extemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.50010.500 in H2O 1.000 in/100ft 1383 cfm 204 Job: 2265 MODEL- GAR LEFT Date: MAY 22, 2020 By: Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1383 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH c 144 3 6 1.000 4.0 OxO VIFx 8.6 115.0 st2 BATH 3 h 2054 90 62 1.000 6.0 Ox 0 VIFx 33.4 155.0 st6 BEDROOM 2 c 2184 88 98 1.000 7.0 Ox0 VIFx 12.2 115.0 st2 BEDROOM 3 c 2184 82 98 1.000 7.0 OxO VIFx 20.6 135.0 St5 BEDROOM 4 h 3324 146 97 1.000 7.0 Ox0 VIFx 33.9 155.0 st6 BREAKFAST c 2107 64 94 1.000 7.0 OxO VIFx 30.0 135.0 st5 DINING ROOM h 2906 127 97 1.000 7.0 Ox0 VIFx 9.5 115.0 st2 FAMILY ROOM c 2163 57 97 1.000 7.0 Ox0 VIFX 48.7 155.0 st4 FAMILY ROOM -A c 2163 57 97 1.000 7.0 Ox0 VIFx 38.6 135.0 st3 FAMILY ROOM-B c 2163 57 97 1.000 7.0 Ox0 VIFx 26.6 115.0 stl KITCHEN c 2270 12 102 1.000 7.0 OxO VIFx 20.4 135.0 St5 LIVING ROOM h 5763 252 113 1.000 7.0 Ox0 VIFx 27.5 115.0 st1 •BATH h 969 42 42 1.000 5.0 OxO VIFx 33.8 135.0 st3 O LINEN h 463 20 8 1.000 4.0 OxO VIFx 32.3 115.0 SO O TOILET c 414 6 19 1.000 4.0 OxO VIFx 26.1 115.0 SO O wic 1 h 811 36 13 1.000 4.0 Ox 0 VIFx 37.4 135.0 st3 OWIO2 c 81 2 4 1.000 4.0 Ox0 VIFx 34.7 135.0 st3 OWNERS BEDROOM h 2714 119 98 1.000 7.0 OxO VIFx 43.8 155.0 st4 OWNERS BEDROOM.A h 2714 119 98 1.000 7.0 OX0 VIFx 45.7 155.0 st4 UTILITY c 1063 4 48 1.000 6.0 Ox0 VIFx 4.5 115.0 st2 .� -Fk wrighhsaf!^ 2020-May-2213:45:49 •...M-, »a•-.•�+-+ Right -Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...t HVACIADAMS HMS- 8108 AMALFI 2265 MODELA.nip Cale = MJ8 Front Doorfaces: N Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st4 Peak AVF 295 292 1.000 667 9.0 0 x 0 VinlFlx st3 st3 Peak AVF 431 447 1.000 678 11.0 0 x 0 VinlFlx st1 st1 Peak AVF 767 683 1.000 977 12.0 0 x 0 VinIFIX st6 Peak AVF 236 159 1.000 675 8.0 0 x 0 VinlFlx sty st5 Peak AVF 394 452 1.000 685 11.0 0 x 0 VinlFlx st2 st2 PeakAVF 616 700 1.000 892 12.0 0 x 0 VinlFlx Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1383 1383 0 1 0 0 0 Ox 0 1 VIFx t- * Wrightsaft- 2020-May-2213:45:49 •��r ~"--+a^.-+ Right -Suite® Universal 2019 19.0.08 RSUD8101 Page 2 ACM ...it HVACVADAMS HMS- 8108 AMALFI 2265 MODEL A.rup CaIc=MJ8 Front Doorfaces: N