HomeMy WebLinkAboutManual J & Energy Code Comp Package 7-16-20JB’s A/C & Electrical, Inc. 2090 N.W. Federal Highway Stuart, FL 34994 | 772.634.6315 | jbrowningac@gmail.com
July 16, 2020 In reference to: Brown Residence Mini-Split Addition Saint Lucie County 10851 S Ocean Drive 137 Hutchinson Island South, FL 34957
Included within this document:
• HVAC Mini-Split Installation Layout Floor plan layout including location of existing system and new system Window & Door schedule Heating & Cooling load schedule New HVAC system specifications 2017 FBC, Energy Conservation Code conformance statement
• ACCA Manual J, Heating & Cooling load calculations
• AHRI Certificate 9,000 (nominal) Btuh Mitsubishi Mini-Split
• 2017 Energy Performance Level (EPL) Display Card for Brown residence after addition of Mini-Split
• 2017 Energy Performance Level (EPL) Display Card for Brown residence in original state
Residential System Sizing Calculation
Summary
William, Coretta Brown
10851 S Ocean Drive 137
Hutchinson Island South, FL 34957
Project Title:
Brown Residence - Windmill Village
7/16/2020
Location for weather data: Fort Pierce, FL - Defaults: L a t i t u d e ( 2 7 . 4 8 ) Altitude(25 ft.) Temp Range(L)
Humidity data: Interior RH (50%) Outdoor wet bulb (78F) Humidity difference(62gr.)
Winter design temperature(TMY3 99%) 40 F Summer design temperature(TMY3 99%) 91 F
Winter setpoint 70 F Summer setpoint 75 F
Winter temperature difference 30 F Summer temperature difference 16 F
Total heating load calculation 7180 Btuh Total cooling load calculation 8976 Btuh
Submitted heating capacity % of calc Btuh Submitted cooling capacity % of calc Btuh
Total (Electric Heat Pump) 125.3 9000 Sensible (SHR = 0.75)87.5 7500
Heat Pump + Auxiliary(0.0kW) 125.3 9000 L a t e n t 625.0 2500
T o t a l (Electric Heat Pump) 111.4 10000
WINTER CALCULATIONS
Winter Heating Load (for 422 sqft)
Load component Load
Window total 142 sqft 3701 Btuh
Wall total 610 sqft 2432 Btuh
Door total 20 sqft 276 Btuh
Ceiling total 422 sqft 317 Btuh
Floor total 422 sqft 453 Btuh
Infiltration 0 cfm 0 Btuh
Duct loss 0 Btuh
Subtotal 7180 Btuh
Ventilation 0 cfm 0 Btuh
TOTAL HEAT LOSS 7180 Btuh
Summer Cooling Load (for 422 sqft)
Load component Load
Window total 142 sqft 3609 Btuh
Wall total 610 sqft 2554 Btuh
Door total 20 sqft 285 Btuh
Ceiling total 422 sqft 241 Btuh
Floor total 227 Btuh
Infiltration 0 cfm 0 Btuh
Internal gain 1660 Btuh
Duct gain 0 Btuh
Sens. Ventilation 0 cfm 0 Btuh
Blower Load 0 Btuh
Total sensible gain 8576 Btuh
Latent gain(ducts)0 Btuh
Latent gain(infiltration)0 Btuh
Latent gain(ventilation)0 Btuh
Latent gain(internal/occupants/other) 400 Btuh
Total latent gain 400 Btuh
TOTAL HEAT GAIN 8976 Btuh
EnergyGauge® / USRCZB v6.1.04
SUMMER CALCULATIONS
8th Edition
EnergyGauge® System Sizing
PREPARED BY: _________________________________
DATE: ________________________________________
EcoInnovative - Kathleen Connolly
July 16, 2020
System Sizing Calculations - Winter
Residential Load - Whole House Component Details
William, Coretta Brown
10851 S Ocean Drive 137
Hutchinson Island South, FL 34957
Project Title:
Brown Residence - Windmill Village
Building Type: User
7/16/2020
Reference City: Fort Pierce, FL ( D e f a u l t s ) Winter Temperature Difference: 30.0 F (TMY3 99%)
Component Loads for Whole House
Window Frame UP a n e s / T y p e Orientation Area(sqft) X HTM=L o a d
1 2, Tint Metal 0.87 N 9.3 26.1 244 Btuh
2 2, Tint Metal 0.87 E 9.3 26.1 244 Btuh
3 2, Tint Metal 0.87 S 39.6 26.1 1033 Btuh
4 2, Tint Metal 0.87 W 26.1 26.1 682 Btuh
5 2, Tint Metal 0.87 W 12.7 26.1 331 Btuh
6 2, Tint Metal 0.87 W 4.8 26.1 125 Btuh
7 2, Clear Metal 0.87 E 40.0 26.1 1044 Btuh
Window Total 141.8(sqft)3701 Btuh
Walls Ornt.Ueff.R-ValueT y p e Area X HTM=L o a d
( C a v / S h )
1 Frame - Wood - Ext (0.133)5.0/0.0 102 3.99 406 Btuh
2 Frame - Wood - Ext (0.133)5.0/0.0 205 3.99 819 Btuh
3 Frame - Wood - Ext (0.133)5.0/0.0 71 3.99 285 Btuh
4 Frame - Wood - Ext (0.133)5.0/0.0 231 3.99 922 Btuh
Wall Total 610(sqft)2432 Btuh
Doors Storm Ueff.Type Area X HTM=L o a d
1 Insulated - Exterior,n (0.460) 20 13.8 276 Btuh
Door Total 20(sqft)276Btuh
Ceilings Ueff.T y p e / C o l o r / S u r f a c e R - V a l u e Area X HTM=L o a d
1 Unvent Attic/L/M e t a l (0.025)19.0/20.0 422 0.8 317 Btuh
Ceiling Total 422(sqft)317Btuh
Floors Ueff.T y p e R - V a l u e Size X HTM=L o a d
1 Raised - Open ( 0 . 0 3 6 )30.0 421.5 s q f t 1.1 453 Btuh
Floor Total 422 s q f t 453 Btuh
Envelope Subtotal: 7180 Btuh
Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM=
Natural 0.00 3372 1.00 0.0 0 Btuh
Duct load NA, R0.0, Supply(), Return()(DLM of 0.000)0 Btuh
All Zones Sensible Subtotal All Zones 7180 Btuh
EnergyGauge® / USRCZB v6.1.04 Page 1
Manual J Winter Calculations
Residential Load - Component Details (continued)
William, Coretta Brown
10851 S Ocean Drive 137
Hutchinson Island South, FL 34957
Project Title:
Brown Residence - Windmill Village
Building Type: User
7/16/2020
WHOLE HOUSE TOTALS
Subtotal Sensible Heat Loss 7180 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 7180 Btuh
EQUIPMENT
1. Electric Heat Pump Mitsubishi #MUZ-WR09NA-U1 9000 Btuh
Key: Window types - NFRC (Requires U-Factor and Shading coefficient(SHGC) of glass as numerical values)
or - Glass as 'Clear' or 'Tint' (Uses U-Factor and SHGC defaults)
U - (Window U-Factor)
HTM - (ManualJ Heat Transfer Multiplier)
Version 8
EnergyGauge® / USRCZB v6.1.04 Page 2
System Sizing Calculations - Summer
Residential Load - Whole House Component Details
William, Coretta Brown
10851 S Ocean Drive 137
Hutchinson Island South, FL 34957
Project Title:
Brown Residence - Windmill Village
7/16/2020
Reference City: Fort Pierce, FL Temperature Difference: 16.0F(TMY3 99%) Humidity difference: 62gr.
Component Loads for Whole House
Type*Overhang Window Area(sqft) HTM L o a d
Window Panes SHGC U InSh IS O r n t Len Hgt Gross Shaded Unshaded Shaded Unshaded
1 2 Tint 0 . 4 4 , 0.87 B-L No N 1.0ft. 0.7ft. 9.3 0.0 9.3 17 17 162 Btuh
2 2 Tint 0 . 4 4 , 0.87 B-L No E 11.0f 0.7ft. 9.3 9.3 0.0 17 35 162 Btuh
3 2 Tint 0 . 4 4 , 0.87 B-L No S 1.0ft. 0.2ft. 39.6 39.6 0.0 17 19 686 Btuh
4 2 Tint 0 . 4 4 , 0.87 B-L No W 1.0ft. 1.3ft. 26.1 0.0 26.1 17 35 927 Btuh
5 2 Tint 0 . 4 4 , 0.87 B-L No W 1.0ft. 1.3ft. 12.7 0.0 12.7 17 35 449 Btuh
6 2 Tint 0 . 4 4 , 0.87 B-L No W 1.0ft. 0.7ft. 4.8 0.2 4.6 17 35 165 Btuh
7 2 Clear 0 . 6 5 , 0.87 B-L No E 11.0f 0.7ft. 40.0 40.0 0.0 19 48 770 Btuh
E x c u r s i o n 288 Btuh
Window Total 142 ( s q f t ) 3609 Btuh
Walls Type U-Value R-Value Area(sqft)HTM Load
Cav/Sheath
1 Frame - Wood - Ext 0.13 5.0/0.0 101.7 4.2 426 Btuh
2 Frame - Wood - Ext 0.13 5.0/0.0 205.3 4.2 860 Btuh
3 Frame - Wood - Ext 0.13 5.0/0.0 71.4 4.2 299 Btuh
4 Frame - Wood - Ext 0.13 5.0/0.0 231.1 4.2 968 Btuh
Wall Total 610 ( s q f t )2554 Btuh
Doors Type Area (sqft)HTM Load
1 Insulated - Exterior 20.0 14.3 285 Btuh
Door Total 20 ( s q f t )285 Btuh
Ceilings U-Value R-ValueType/Color/Surface Area(sqft)HTM Load
1 Unvented Attic/Light/Metal 0.025 19.0/20.0 421.5 0.57 241 Btuh
Ceiling Total 422 ( s q f t )241 Btuh
Floors R-ValueType Size HTM Load
1 Raised - Open 30.0 422 ( s q f t )0.5 227 Btuh
Floor Total 421.5 ( s q f t )227 Btuh
Envelope Subtotal: 6916 Btuh
Infiltration AverageType A C H Volume(cuft) Wall Ratio CFM= Load
Natural 0.00 3372 1 0.0 0 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 2 X 230 + 1200 1660 Btuh
Sensible Envelope Load: 8576 Btuh
Duct load N A , Supply(R0.0-None), Return(R0.0-None)(DGM of 0.000) 0 Btuh
Sensible Load All Zones 8576 Btuh
EnergyGauge® / USRCZB v6.1.04 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
William, Coretta Brown
10851 S Ocean Drive 137
Hutchinson Island South, FL 34957
Project Title:
Brown Residence - Windmill Village
Climate:FL_VERO_BEACH_MUNICIPAL_A
7/16/2020
WHOLE HOUSE TOTALS
Sensible Envelope Load All Zones 8576 Btuh
Sensible Duct Load 0 Btuh
Total Sensible Zone Loads 8576 Btuh
Sensible ventilation 0 Btuh
B l o w e r 0 Btuh
Whole House Total sensible gain 8576 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference)0 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 0 Btuh
Latent occupant gain (2.0 people @ 200 Btuh per person) 400 Btuh
Latent other gain 0 Btuh
Latent total gain 400 Btuh
TOTAL GAIN 8976 Btuh
EQUIPMENT
1. Central Unit Mitsubishi #MUZ-WR09NA-U1 10000 Btuh
*Key: Window types (Panes - Number and type of panes of glass)
(SHGC - Shading coefficient of glass as SHGC numerical value)
(U - Window U-Factor)
(InSh - Interior shading device: none(No), Blinds(B), Draperies(D) or Roller Shades(R))
- For Blinds: Assume medium color, half closed
For Draperies: Assume medium weave, half closed
For Roller shades: Assume translucent, half closed
(IS - Insect screen: none(N), Full(F) or Half(½))
(Ornt - compass orientation)
Version 8
EnergyGauge® / USRCZB v6.1.04 Page 2
Certificate of Product Ratings
†
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
© Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.:
Date : 07-16-2020
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating.
†"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being
marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
2020
AHRI Certified Reference Number : 202397877 Model Status : Active
AHRI Type : HRCU-A-CB-O (Mini-Split Heat Pump, with Remote Outdoor Unit Air-Source, Free Delivery)
Series Name : M-Series
Outdoor Unit Brand Name : Mitsubishi Electric
Outdoor Unit Model Number : MUZ-WR09NA-U1
Indoor Type : Mini-Splits (Non-Ducted)
Indoor Model Number(s) : MSZ-WR09NA-U1
Rated as follows in accordance with the latest edition of AHRI 210/240 with Addendum 1, Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump Equipment and subject to rating accuracy by AHRI-sponsored, independent, third party testing:
Cooling Capacity (95F) : 9000
EER (95F) : 11.00
SEER : 16.00
High Heat (47F) : 10900
Low Heat (17F) : 6700
HSPF : 8.50
Sold in? : USA, Canada
Eligible For Federal Tax Credit (installed between 2/17/09 and 12/1/16)
132394046128953530
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 119
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition 1. __________ Existing (Confirmed)
2. Single-family or multiple-family 2. __________ Single-family
3. No. of units (if multiple-family)3. __________1
4. Number of bedrooms 4. __________1
5. Is this a worst case? (yes/no)5. __________No
6. Conditioned floor area (sq. ft.)6. __________422
7. Windows, type and area
a) U-factor:(weighted average)7a._________0.800
b) Solar Heat Gain Coefficient (SHGC) 7b._________0.628
c) Area 7c._________141.8
8. Skylights
a) U-factor:(weighted average)8a._________NA
b) Solar Heat Gain Coefficient (SHGC) 8b._________NA
9. Floor type, insulation level:
a) Slab-on-grade (R-value)9a._________
b) Wood, raised (R-value)9b._________30.0
c) Concrete, raised (R-value)9c._________
10. Wall type and insulation:
A. Exterior:
1. Wood frame (Insulation R-value) 10A1.________5.0
2. Masonry (Insulation R-value)10A2.________
B. Adjacent:
1. Wood frame (Insulation R-value) 10B1.________
2. Masonry (Insulation R-value)10B2.________
11. Ceiling type and insulation level
a) Under attic 11a.________19.0
b) Single assembly 11b.________
c) Knee walls/skylight walls 11c.________
d) Radiant barrier installed 11d.________No
12. Ducts, location & insulation level
a) Supply ducts R_______
b) Return ducts R_______
c) AHU location
13. Cooling system: Capacity_______10.0
a) Split system SEER_______
b) Single package SEER_______
c) Ground/water source SEER/COP_______
d) Room unit/PTAC EER_______
e) Other __________16.0
14. Heating system: Capacity_______10.9
a) Split system heat pump HSPF_______
b) Single package heat pumpHSPF_______
c) Electric resistance COP_______
d) Gas furnace, natural gas AFUE_______
e) Gas furnace, LPG AFUE_______
f) Other 8.50
15. Water heating system
a) Electric resistance EF_______
b) Gas fired, natural gas EF_______
c) Gas fired, LPG EF_______
d) Solar system with tank EF_______
e) Dedicated heat pump with tank EF_____
f) Heat recovery unit HeatRec%_______
g) Other
16. HVAC credits claimed (Performance Method)
a) Ceiling fans _________
b) Cross ventilation _________No
c) Whole house fan _________No
d) Multizone cooling credit _________
e) Multizone heating credit _________
f) Programmable thermostat _________No
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature:_________________________________________ Date:____________________________________
Address of New Home: ____________________________________ City/FL Zip: ________________________________10851 S Ocean Drive 137 Hutchinson Island South, FL 34957
7/16/2020 4:43:39 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Brown residence
10851 S Ocean Drive 137
Energy Performance after
addition of mini-split
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 158
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition 1. __________ Existing (Confirmed)
2. Single-family or multiple-family 2. __________ Single-family
3. No. of units (if multiple-family)3. __________1
4. Number of bedrooms 4. __________1
5. Is this a worst case? (yes/no)5. __________No
6. Conditioned floor area (sq. ft.)6. __________422
7. Windows, type and area
a) U-factor:(weighted average)7a._________0.800
b) Solar Heat Gain Coefficient (SHGC) 7b._________0.628
c) Area 7c._________141.8
8. Skylights
a) U-factor:(weighted average)8a._________NA
b) Solar Heat Gain Coefficient (SHGC) 8b._________NA
9. Floor type, insulation level:
a) Slab-on-grade (R-value)9a._________
b) Wood, raised (R-value)9b._________30.0
c) Concrete, raised (R-value)9c._________
10. Wall type and insulation:
A. Exterior:
1. Wood frame (Insulation R-value) 10A1.________5.0
2. Masonry (Insulation R-value)10A2.________
B. Adjacent:
1. Wood frame (Insulation R-value) 10B1.________
2. Masonry (Insulation R-value)10B2.________
11. Ceiling type and insulation level
a) Under attic 11a.________19.0
b) Single assembly 11b.________
c) Knee walls/skylight walls 11c.________
d) Radiant barrier installed 11d.________No
12. Ducts, location & insulation level
a) Supply ducts R_______
b) Return ducts R_______
c) AHU location
13. Cooling system: Capacity_______9.0
a) Split system SEER_______
b) Single package SEER_______
c) Ground/water source SEER/COP_______
d) Room unit/PTAC EER_______
e) Other __________11.2
14. Heating system: Capacity_______0.0
a) Split system heat pump HSPF_______
b) Single package heat pumpHSPF_______
c) Electric resistance COP_______
d) Gas furnace, natural gas AFUE_______
e) Gas furnace, LPG AFUE_______
f) Other
15. Water heating system
a) Electric resistance EF_______
b) Gas fired, natural gas EF_______
c) Gas fired, LPG EF_______
d) Solar system with tank EF_______
e) Dedicated heat pump with tank EF_____
f) Heat recovery unit HeatRec%_______
g) Other
16. HVAC credits claimed (Performance Method)
a) Ceiling fans _________
b) Cross ventilation _________No
c) Whole house fan _________No
d) Multizone cooling credit _________
e) Multizone heating credit _________
f) Programmable thermostat _________No
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature:_________________________________________ Date:____________________________________
Address of New Home: ____________________________________ City/FL Zip: ________________________________10851 S Ocean Drive 137 Hutchinson Island South, FL 34957
7/16/2020 4:48:16 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Brown residence
10851 S Ocean Drive 137
Energy Performance of
original house