HomeMy WebLinkAboutProduct Specifications20/22 kW
INCLUDES:
• True Power'" Electrical Technology
• Two-line multilingual digital LCD Evolution" controller
(English/SpanisWFrench/Poduguese)
• 200 amp service rated smarl switch transfer switch available
• Electronic governor
• Standard Wi-Fi® connectivity
• System status & maintenance interval LED indicators
• Sound attenuated enclosure
• Flexible fuel line connector
• Natural gas or LP gas operation
• 5 Year limited warranty
• Listed and labeled by the Southwest Research Institute allowing
installation as close as 18 in (457 mm) to a structure.'
'Must be located awayliom doors, windows, and fresh air intakes and in
accordance with local codes.
hhps.11assels.swd.orp/libt&yl0iredoryOtiistedProductsl
Conshuctionlnduslry/973_OoC 204_13204-M-01_Rev9.pol
FEATURES
O INNOVATIVE ENGINE DESIGN & RIGOROUS TESTING are at the heart of Gen-
erac's success in providing the most reliable generators possible. Generac's G-
Force engine lineup offers added peace of mind and reliability for when it's needed
the most. The G-Force series engines are purpose built and designed to handle the
rigors of extended run times in high temperatures and extreme operating conditions.
O TRUE POWER" ELECTRICAL TECHNOLOGY: Superior harmonics and sine wave
form produce less than 5% Total Harmonic Distortion for utility quality power. This
allows confident operation of sensitive electronic equipment and micro -chip based
appliances, such as variable speed HVAC systems.
O TEST CRITERIA
PROTOTYPE TESTED NEMA MG7.22 EVALUATION
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
O MOBILE LINK" CONNECTIVITY: FREE with select Guardian Series Home standby
generators, Mobile Link WI-Fi allows users to monitor generator status from any-
where in the world using a smarlphone, tablet, or PC. Easily access information such
as the current operating status and maintenance alerts. Users can connect an
account to an authorized service dealer for fast, friendly, and proactive service. With
Mobile Link, users are taken care of before the next power outage.
GENERACx
GUARDIAN° SERIES
Residential Standby Generators
Air -Cooled Gas Engine
Standby Power Rating
G( OiWS I ::007o3b I Lrd PD38 3. G007039 3 (Ala inmu Bicgbw) - 20 kW 00! V
G007042-[. GC07043-2. G(xi7M2.3. G007043-3 tNUr:inam Dc:Gaal 22 kW 00 H,
c(M.
or COOS QU1 O
LISTED
Note: CETL or CUL certification only appplies to unbundled units and units packaged
with limited circuit switches. Units panted with the Sman Switch are E1L nr UL
certified In the USA only.
O SOLID-STATE. FREQUENCY COMPENSATED VOLTAGE REGULATIONS This
state-of-the-art power maximizing regulation system is standard on all Generac mod-
els. It provides optimized FAST RESPONSE to changing load conditions and MAXI-
MUM MOTOR STARTING CAPABILITY by electronically torque -matching the surge
loads to the engine. Digital voltage regulation at .1%.
O SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer network
provides pans and service know-how for the entire unit, from the engine to the small-
est electronic component.
O GENERAC TRANSFER SWITCHES: Long life and reliability are synonymous with
GENERAL POWER SYSTEMS. One reason for this confidence is that the GENERAC
product line is offered with its own transfer systems and controls for total system
compatibility.
GENERAL
PROMISE
GENERAC
20/22 kW
Features and Benefits
Engine
•
Generac G-Force design
Maximizes engine "breathing" for increased fuel efficiency. Plateau honed cylinder walls and plasma moly
rings help the engine run cooler, reducing oil consumption and resulting in longer engine life.
•
"Spiny-lok" cast iron cylinder walls
Rigid construction and added durability provide long engine life.
•
Electronic ignition/spark advance
These features combine to assure smooth, quick starting every time.
•
Full pressure lubrication system
Pressurized lubrication to all vital bearings means better performance, less maintenance, and longer engine
life. Now featuring up to a 2 year/200 hour oil change interval.
•
Low oil pressure shutdown system
Shutdown protection prevents catastrophic engine damage due to low oil.
•
High temperature shutdown
Prevents damage due to overheating.
Generator
-._---_.-�_.., .-- ...-_...._..._..
•
Revolving field
Allows for a smaller, light weight unit that operates 25%more efficiently than a revolving armature generator.
•
Skewed stator
Produces a smooth output waveform for compatibility with electronic equipment.
•
Displaced phase excitation
Maximizes motor starting capability.
•
Automatic voltage regulation
Regulating output voltage to ±1 % prevents damaging voltage spikes.
•
UL 2200 listed
For your safety.
Transfer Switch (If applicable)
•
Fully automatic
Transfers vital electrical loads to the energized source of power.
•
NEMA 3R
Can be installed inside or outside for maximum flexibility.
•
Remote mounting
Mounts near an existing distribution panel for simple, low-cost installation.
Evolution" Controls
•
AUTO/MANUAUOFF illuminated buttons
Selects the operating mode and provides easy, at -a -glance status indication in any condition.
•
Two-line multilingual LCD display
Provides homeowners easily visible logs of history, maintenance, and events up to 50 occurrences.
•
Sealed, raised buttons
Smooth, weather -resistant user interface for programming and operations.
•
Utility voltage sensing
Constantly monitors utility voltage, selpoints 65% dropout, 80% pick-up, of standard voltage.
•
Generator voltage sensing
Constantly monitors generator voltage to verity the cleanest power delivered to the home.
•
Utility interrupt delay
Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default selling of 5
seconds by a qualified dealer
• Engine warm-up Verifies engine is ready to assume the load, setpoint approximately 5 seconds.
• Engine cool -down Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
• Programmable exercise Operates engine to prevent oil seal drying and damage between power outages by running the generator for
5 minutes every other week. Also offers a selectable setting for weekly or monthly operation providing
flexibility and potentially lower fuel costs to the owner.
• Smart battery charger Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
Compatible with lead acid and AGM -style batteries.
• Main line circuit breaker Protects generator from overload.
• Electronic governor Maintains constant 60 Hz frequency.
Unit
• SAE weather protective enclosure Sound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding
winds up to 150 mph (241 km/h). Hinged key locking roof panel for security. Lift -out front for easy access
to all routine maintenance items. Electrostatically applied textured epoxy paint for added durability.
• Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
• Small, compact, attractive Makes for an easy, eye appealing installation, as close as 18 in (457 mm) away from a structure.
GENERAC'
20/22 kW
Features and Benefits
w..rallation System
• 14 in (35.6 cm) flexible fuel line connector Listed ANSI Z21.75/CSA 6.27 outdoor appliance connector for the required connection to the gas supply
piping.
• Integral sediment bap Meets IFGC and NFPA 54 installation requirements.
Connectivity (WI-Fi equipped models only)
• Ability to view generator status
• Ability to view generator Exercise/Run and Total Hours
• Ability to view generator maintenance information
• Monthly report with previous month's activity
• Ability to view generator battery information
• Weather information
Monitor generator with a smartphone, tablet, or computer at any time via the Mobile Link application for
complete peace of mind.
Review the generator's complete protection profile for exercise hours and total hours.
Provides maintenance information for the specific model generator when scheduled maintenance is due.
Detailed monthly reports provide historical generator information.
Built in battery diagnostics displaying current state of the battery.
Provides detailed local ambient weather conditions for generator location.
GENERAC
20/22 kW
Specifications
Generator
Model
G007038-1, G007039-1
G007042-2, G007043-2 G007038-3, G007039-3
G007042-3, G007043-3
(20 kW)
(22 kW) (20 ItW)
(22 kW)
Rated maximum continuous power capacity (LP)
20,000 Watts'
22,000 Wafts' 20,000 Wafts'
22,000 Walls'
Rated maximum continuous power capacity(NG)
18,000 Watts'
19,500 Wafts18,00DWati
19,500 Watts'
Rated voltage
240
Rated maximum continuous load current - 240 volts (LP/NG)
83.3 / 75.0
91.7 / 81.3 83.3 / 75.0
91.7 / 81.3
Total Harmonic Distortion
less than 5%
Main lire circuit breaker
90 amp
100 amp 90 amp
100 amp
Phase
1
Number of rotor poles
2
Haled AC frequency
60 Fe
Power factor
1.0
Battery requirement (not included)
12 Volts, Group 26R 540 CCA minimum or Group 35AGM 650 CCA minimum
Unit weight (Ito /kg)
448/203
466/211 436/198
4451202
Dimensions (Lx W x H) in / cm
48 x25x 29/ 121.9x 63.5 x 73.7
Sound output in dB(A) at 231t (7 m) with generator operating at normal two
67
67 67
67
Sound output in ill at 23 R (7 m) with generator in Quiet -Test" low -speed exercise mode"
55
57 55
57
Exercise duration
5 min
Engine
Engine type
GENERAC G-Force 1000 Series
Number of cylinders
2
Displacement
999 cc
Cylinder block
Aluminum w/ cast iron sleeve
Valve arrangement
Overhead valve
Ignition system
Solid-state w/ magneto
Governor system
Electronic
Compression ratio
9.5:1
Staler
12 VDC
OII capacity including filter
Apprpx 1.9 gt11.8 L
Operating rpm
3,600
Fuel consumption
Natural gas f r/hr (ma/hr)
1/2 Load 204 (5.78) 228 (6A6)
164 (4.64)
203 (5.75)
Full Load 301 (8.52) 327 (9.26)
287 (8.13)
306 (111
Liquid propane Ira tar (gaVhr) [Uhl
1/2 Load 87 (2.37) [8.991 92 (2.53)19.571
86 (2.36)18.951
92 (2.53) [9.b71
PoII Load 130 (3.56) [13.481 142 (3.90)114.771
136 (3.74)114.151
142 (3.90) [14.77]
Note: Fuel pipe must be theft for full load. Required fuel pressure to geneator fuel inlet at all load ranges - 3.5-7 in water column (0.87-1.74 kPa) for
NG, 10-12 in water column
(2.49-2.99 kPa) for LP gas.
for BTU content multiply fla/hr x 2500 (LP) or fta/hr x 1000 ING). For Megaloule content, multiply ms/hr x 93.15 LP) or mi x 37.26 (NG).
Twotineplain text multilingual LCO
Simple user interface lot ease of operation.
Mode buttons: AUTO
Automatic star) an utility failure. Weekly, BI-weekly, or Monthly selectable exerciser.
MANUAL
Sean with slater control, unit stays on. If utility fails, teal to load takes place.
OFF
Stops unit Power Is removed. Control and charger still operate.
Ready to RunfMaintenance messages
Standard
Engine nm hours indication
Standard
Programmable start delay canteen 2-1500 seconds
Standard (programmable by dealer only)
Utility Voltage Loss,4ieturn to Utility adjustable (brownout setting)
From 140-171 V/ 190-216 V
Future Set Capable E irciser/Enicise Set Error warning
Standard
RurVAtartVkAaintenarece logs
50 events each
Engine start sequence
Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter leek -out
Slater cannot re-engage until 5 sac after engine has slopped.
Seven Battery Charger
Standard
Charger Fault/Missing AC warring
Standard
Low Baltery/Baaery Problem Protection and Battery Condition indication
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection
Standard
Under-Frequency/Ovedcad/Steeper Oveaurrenl Potedion
Standard
Safety Fused/Fuse Problem Protection
Standard
Automatic Low Oil Pressure/High Oil Temperature Shuldown
Standard
Overconk70verspered (p 72 Hz)Apm Same Loss Shutdown
Standard
High Engine Temperature Shuldown
Standard
Internal FautAncomect Wiring protection
Standard
Common external fault capability
Standard
Held upgadable firmware
Standard
"Sand levels are taken tom the front of the generator. Sound levels taken Imm other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying
emergency power for the duraton of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514. IS03046 and DING271).' Maximum kilovolt amps and current are
subject to and limited by such lades as fuel BTLVmgajwle cement, ambient temperature, altitude, engine power and condition, e1c. Maximum power deaeases appnmdmately 3.5%fix each 1,000 it (304.8 m) above sea
level; and also will decrease apprmdmately 1%fa each 10 IF (6 °C) above 60 °F (16 °C).
20/22 kW
Service Hated Smart Switch Features
• Includes digital power management technology (DPM) standard.
• Intelligently manages up to lour air conditioner loads with no additional hardware.
• Up to eight additional large (240 VAC) loads can be managed when used in
conjunction with Smart Management Modules (SMMl
• Electrically operated, mechanically -held contacts for lasl, clean connections.
• Rated for all classes of load,100% equipment rated, both inductive and resistive.
• 2-pole, 250 VAC contaclors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA7UL 311 aluminum Outdoor enclosure allows for indoor or outdoor mounting
flexibility.
Dimensions
200 Amps 120/240,1e
Open Transl0on Service Rated
Height
Widdl
H1
H2
W1
Y42
Depth
in
26.75
30.1
10.5
13.5
1 6.91
Cell
67.95
76.45
1 26.67
34.29
1 17.55
Wire Ranges
Conductor Lug
Neutral Lug
Ground lug
400MGM -#4
350MGM -#6
210-#14
GENERAC'
Switch Options
0007039-1 (20 kW)
Model
G007043-2 (22 kW)
6007039-3 (20 kW)
G007043-3 (22 kW)
No. of pales
2
Current rating (amps)
200
Voltage rating (VAC)
120/240,10
Utility voltage monitor (lixed)'
-Pick-up
60%
-Dropout
65%
Return to U61W
Approx. 13 sec
Exercises bi-weekly lot 5 minutes'
Standard
ETL or uL listed
Standard
Enclosure type
NEMAAIL 3R
Cimuit breaker protected
22,000
Lug range
250 MCM - #6
'Functlon of Evolution controller
Exercise can be set to weekly or monthly
20/22 M
Model # Product
G005819-0 26R Wet Cell Battery
G007101-0 Battery Pad Warmer
G007102-0 Oil Warmer
G007103.1 Breather Warmer
G005621.0 Auxiliary Transfer Switch
Contact Kit
G007027-0 - Bisque Fascia Base Wrap Kit
(Standard on 22 kW)
GENERAC
Available Accessories
Description
Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet cell battery
for use with all air-cooled standby product (excluding PowerPact®).
Pad wanner rests under the battery. Recommended for use if temperature regularly falls below 0 °F (-18 cC). (Not
necessary for use with AGM -style batteries).
Oil warmer slips directly over the oil fitter. Recommended for use it temperature regularly falls below 0 °F (-18 °C).
Breather warmer is for use in extreme cold weather applications. For use with Evolution controllers only in climates
where heavy Icing occurs.
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load that may not
be needed. Not compatible with 50 amp pre -wired switches.
The fascia base wrap snaps together around the bottom of the new air-cooled generators. This offers a sleek, con-
toured appearance as well as offering protection from rodents and insects by covering the liking holes located in the
base.
G005703.0 - Bisque Touch -Up Paint Kit If the generator enclosure is scratched or damaged, it is important to touch up the paint to protect from future corro-
sion. The touch-up paint kit Includes the necessary paint to correctly maintain or touch up a generator enclosure.
G006485-0 Scheduled Maintenance Kit Generac's scheduled maintenance kit provides all the items necessary to perform complete routine maintenance on a
Generac automatic standby generator (oil not included).
G007005-0 Wi-Fi LP Tank Fuel Level The Wi-Fi enabled LP tank fuel level monitor provides constant monitoring of the connected LP fuel tank. Monitoring
Monitor the LP tank s fuel level is an important step in verifying the generator is ready to run during an unexpected powerfailure.
Status alerts are available through a free application to notify users when the LP tank is in need of a refill.
G007000-0 (50 amp) Smart Management Module Smart Management Modules (SMM) are used to optimize the performance of a standby generator. It manages large
G007006-0 (100 electrical loads upon startup and sheds them to aid in recovery when overloaded. In many cases, using SMM's can
amp) reduce the overall size and cost of the system.
G007169-0 Mobile Link® Cellular The Mobile Link family of Cellular Accessories allows users to monitor generator status from anywhere in the world,
Accessories using a smart phone, tablet, or PC. Easily access information such as the current operating status and maintenance
alerts. Users can connect an account with an authorized service dealer for fast, friendly, and proactive service. With
.. Mobile Link, users are taken care of before the next power outage.
Model
UPC
G007038-1
696471074185
G007038-3
696471074185
G007039-1
696471074192
G007039-3
696471074192
G007042-2
696471074208
G007042-3
696471074208
G007043-2
696471074215
G007043-3
696471W4215
GENERAC`
.--Mmm -
LEFT SIDE VIEW
Dimensions & UPCs
FROM VIEW
Dimensions shown areapprmdma e. See nstalWtion manual toroad dimensions. W NOT USE THESE DIMENSIONS
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
02020 Generac Power Systems, Inc. All rights mserved AN specificadons are sublectto charge without notice. Part No. AODD02212ee Rev.0 05/282020
Automatic
Transfer Switches
GENER
Service and non-Servic
Automatic Smart Transfer SI
100 - 400 Amps, Single Phase
C @us
LISTED
' UL only applies to non -service raled switches
Description
General; Automatic Transfer Switches are designed for use with single phase generators that utilize an Evolution'" or Nexus'"
Controller. The 100, 200, and 400 amp open transition switches are available in single phase in both service equipment rated and
non -service equipment rated configurations. The 150 and 300 amp open transition switches are only available in a service rated
equipment configuration.
Standard Features
Service rated (RXSW) General; Automatic Transfer Switches are housed in an aluminum NEMA/UL Type 3R enclosure% with
electrostatically applied and baked powder paint. The Heavy Duly General; Contactor is a UL recognized device, designed for
years of service. The controller at the generator handles all the timing, sensing, exercising functions, and transfer commands. All
switches are covered by a 5 year limited warranty.
' Non -service rated (RXSC) switches are housed in a steel enclosure.
DPM Technology
Through the use of digital power technology (DPM), these switches have the capability to manage up to 4 individual HVAC (24 VAC
controlled) loads with no additional hardware. When used in tandem with Smart Management Modules, up to 8 more loads can be
managed as well, providing the most instailation efficient power management options available.
ISO
nooc
z000
100-400 Amps, Single Phase
Fundions
All timing and sonsing lianchom migoule In the genaatal 0nea0u
Utility voltage dim -out
Timor to junimalor sun
Engine warm up delay
Standby voltage sensor —... _. _.
Utility voltage pickup - ....,._
Re-hanslel time delay ...__.._.... ._..
Engine cool -down limes
Ewerciser.... ....... .........................-...............................__................_.....
Ilia hanslol switch can be operaled manually without power applied.
'When used In conjunction with units unhimg Evolution" conlrnls
Specifications
GENERAL'
Automatic Smart Transfer Switches
• 65%
10 second laaory Sel adjustable oelween 2-1500 Seconds by a malitied dealeC
5seconds
........ 65% tin 5 seconds
I ._= 80%
15 seconds
_ ._ .,...... _....__ _. _.. 60 seconds
......................................... _..._5 or 12 mmmes adtustah)e weekly/ni-weekly/Moithty"
'Adjustable via the controller
Model
RXSCIOOA3
RXSW100A3
RXSWI SOA3
RXSC20OA3
RXSW20OA3
RXSW30OA3
RXSG400A3
RXSW400A3
Amps
10()
100
150
200
200
300
400
400
Voltage
1201240, to
120/240.19
120/240, to
120/240. to
120/240. to
120/240, 19
1201240,10
120/240, to
Load Transition Type
(Automatic)
Open Transition
Open Transition
Service Paled
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Opens Transition
Open Transition
Service Baled
Enclosure Type
NEMA/UL 3R
NEMA/UL 311
NEMA/UL 38
NEMA/UL 311
NEMA4)L 311
NEMAIUL 311
NEMA/UL 311
NEMA/UL 311
UL Rating
UUCUL
UL
UL
Ul/CIIL
UL
UL
UI/CUL
Ul
Withstand Rating
(Amps)
10.0m
10,00
22,000
10.000
22.000
22.000
22.000
22.000
Lug Range
1/0 - N 14
250 MCM - a6
600 MCM - 1114 at 1/0 - 250 MCM
Dimensions
Model IRIISC100A91R%SW100A3!HXSW15K-
H1
17.241437.9
17 24/437 9126 751679 4
Hei�A I
H2
201508
201500 30/7G2
.
W1
12/5/3115
1? 513115 to 512667
t42
1463708
i 146/3706 13:4123
lkplh (in/mm)
7.0971301
109.'1801 G V1601
Weight (Ib,kWs)
2019.07
225/m.21 3911769
M20M I RXSW200A31 RXSW30W
17 241437 91 26 /5VII 4'.42 91/108!
201508 A 767 4011219:
125M17 .- I fi9!423
14.61370 G '.... ,. ; 31 02/554
25/793 8
36/914.4 49112192
19,1814872 16 691423 9
24/609.6 21 821554 2
7.09i1 e01 ; ,. u,o 1 1006255510AM25551 100625s
I
201907 '.1 140/633 133/60.33 1401645
G E N E R AC General; Power Systems. Inc. - S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
- WMMN� '7017 Gercrne Pea'n 5ysw[ ', 0, to dlpds+ef ea Ae rplxa.m. are weM to [lu,pl aiO,oul roU, si1wn llX)Wtq Y159-A e62417