HomeMy WebLinkAboutModular structure, 36'X60'MODULAR STRUCTURE FOR: MECHANICAL NOTES: 1. ALL SUPPLY AIR REGISTERS SHALL BE 101NCHES X 10 INCHES ADJUSTABLE w/ 10 INCHES X 20 INCHES (INSIDE) OVERHEAD FIBERGLASS DUCT, UNLESS OTHERWISE SPECIFIED, DUCTS LOCATED IN VENILATED ATTIC SPACE$ $HALL HAVE AN R-6 INSULATION VALUE. DUCTS LOCATED IN UNCONDITIONED INTERIOR SPACE. INTERIOR SPACES SHALL HAVE AN R-4.2 INSULATION VALUE. 2. RESTROOM VENT FANS SHALL PROVIDE 50 CFM MINIMUM PER WATER CLOSET AND /OR URINAL. 3. VENT FANS SHALL BE DUCTED TO THE EXTERIOR AND TERMINATE AT AN APPROVED VENT CAP. 4. HVAC EQUIPMENT SHALL BE EQUIPPED WIVH OUTSIDE FRESH INTAKES PROVIDING 20 CFM FOR EACH OCCUPANT OR 50 CFM FOR EACH WATER HEATER CLOSET AND EACH URINAL, WHICH EVER IS GREATER. PLUMBING NOTES: 1. CUSTOMER ASSUMES ALL RESPONSIBILITY FOR DRINKING WATER FACILITIES AND SERVICE SINK WHEN NOT SHOWN ON THE FLOOR PLAN. 2. TOILETS SHALL BE ELONGATED WITH NON -ABSORBENT OPEN FRONT SEAT. 3. RESTROOMS WALL$ $HALL BE COVERED WITH NON -ABSORBENT MATERIAL TO A MINIMUM HEIGHT OF 72 INCHES A.F.F. 4. ALL PLUMBING FIXTURES SHALL HAVE SEPARATE SHUT-OFF VALVES. 5. WATER HEATER SHALL HAVE SAFTV PAN WITH 1 INCH DRAIN TO EXTERIOR, T & P RELIEF VALVE WITH DRAIN TO EXTERIOR, AND A SHUT OFF VALVE WITHIN 3 FEET ON A COLD WATER SUPPLY LINE. 6. DW V SYSTEM SHALL BE EITHER ABS OR PVC - DWV. 7. WATER SUPPLY LINES SHALL BE POLYBUTYLLENE,CPVC, OR COPPER; WHEN POLYBUTYLENE SUP PLY LINES ARE INSTALLED THE MAXIMUM WATER HEATER TEMPERATURE SETTING IS 180' F. THE POLY- BUTYLENE PIPE $HALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURES LIMITATIONS AND INSTRUCTIONS. 8. WATER CLOSETS ARE TANK TYPE AND URINALS ARE FLUSH TANK TYPE UNLESS OTHERWISE SPECIFIED. 9. BUILDING DRAIN AND CLEANOUTS ARE DESIGNED AND SITE INSTALLED BY OTHERS. SUBJECT TO LOCAL JURISDICTION APPROVAL. 10. SHOWERS SHALL BE CONTROLLED BY AN APPROVED MIXING VALVE WITH A MAXIMUM WATER OUTLET TEMPERATURE OF 120" F (48.8- C). 11. THERMAL EXPANSION DEVICE, IF REQUIRED BY WATER HEATER INSTALLED, AND IF NOT SHOWN ON PLUMBING PLAN, IS DESIGNED AND SITE INSTALLED BY OTHER$, SUBJECT TO LOCAL JURISDICTION AND APPROVAL. AS -BUILT BUILDING NOTES: THESE PLANS HAVE NOT BEEN PREPARED BASED ON THE CURRENT CODES, BUT THE CODES THAT WERE IN EFFECT AT THE TIME OF INITIAL CONSTRUCTION. THE ARCHITECT OR ENGINEERS ARE NOT RESPONSIBLE FOR ANY DAMAGE TO OR ALTERATOINS IN THE BUILDING, BUILDING DESIGN, OR CODE REVISIONS THAT WERE MADE AFTER THE INITIAL APPROVAL OF THE BUILDING. IF THE STATE LABEL HAS BEEN LOST REMOVED OR STOLEN THEN IT IS UP TO THE LOCAL JURISDICTION TO REVIEW AND APPROVE THE ATTACHED BUILDING PLANS. THIS BUILDING WAS DESIGNED APPROVED AND CONSTRUCTED UNDER THE THEN CURRENT BUILDING CODES TO A NOMINAL DESIGN WIND SPEED OF 146 MPH. THE FBC, 6TH ED. NOW USES ULTIMATE DESIGN WIND SPEED, TABLE 1609.3.1 PROVIDES WIND SPEED CONVERSION$, WHERE THE NOMINAL DESIGN WIND SPEED AND THE ULTIMATE DESIGN SPEEDS ARE COMPARED. THE 146 MPH NOMINAL DESIGN WIND SPEED IS EQUAL TO THE 188 MPH ULTIMATE DESIGN WIND SPEED. THIS IS A SET OF STOCK AS -BUILT APPROVED BUILDING PLAN$. THE ORIGINAL SET OF APPROVED PLANS IS NO LONGER AVAILIABLE, THEREFORE THIS SET HAS BEEN PROVIDED FOR ACQUIRING A BUILDING PERMIT. PER FLORIDA STATUTE RULE 913-1. E GENERAL NOTES: 1. ACCESS TO BUILDING FOR PERSONS IN WHEELCHAIRS IS DESIGNED BY AND FIELD BUILT BY OTHERS AND SUBJECT TO ALL LOCAL JURISDICTIONS. AT LEAST 50%OF PUBLIC ENTRANCES (INCLUDUNG PRIMARY ENTRANCE) AND ALL REQUIRED EXITS MUST BE ACCESSABLE. 2. ALL DOORS SHALL BE OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY, TOOL SPECIAL KNOWLEDGE OR EFORT. MANUALLY OPERATED FLUSH BOLTS OR SURFACE BLOTS SHALL NOT BE USED. 3. ALL GLAZING WITHIN A 48 INCH ARC OF DOOM, WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE FLOOR, AND ALL GLAZING IN DOORS SHALL BE SAFTY, TEMPERED OR ACRYLIC PLASTIC SHEET. 4. FLOOR DESIGN LIVE LOAD-100 PSF ( LOBBIES & CORRIDORS ); 50 PSF( REMAINDER ). 5. MAXIMUM WIND LOAD-146 Vasd/ 188 Vult MPH(HVHZ) 6. OCCUPANCY IS BUSINESS, 7. OCCUPANT LOAD: 21 PEOPLE. BASED ON 1 PERSON PER 100 SQUARE FEET OF BUSINESS AREA). 8. CONSTRUCTION IS TYPE V-B. 9. ALL STEEL STRAPS REFERENCED S FLOOR PLAN $HALL BE 1.5INCH X N GA.EACH END O GA. X 7/16 INCH CROWN X 1 'IDTH IS STAPLES W ITH A MINIMUM OF 1"PENETRATION EACH END OF STRAP OR 10. MIN. CORRIDOR WIDTH IS 44 INCHES. 12. MIN. CORRIDOR FINISH IS CLASS B (GYPSUM). 12. WINDOW AND DOOR HIGH WIND STORM COVERING$ PER CODE TO BE SUPPLIED AND SITE INSTALLED BY OTHERS SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 13. PLAN REVIEW AND INSPECTION REQUIRED BY CHAPTER 633 F.S. TO BE DONE BY THE LOCAL FIRE SAFETY INSPECTOR. 14. PORTABLE FIRE EXTINGUISHER PER N.F.P.A._ 101 INSTALLED BY OTHERS ON SITE, AND SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 15 THIS BUILDING REQUIRES A FIRE SEPARATION DISTANCE IN ACCORDANCE WITH TABLE 6020E THE FLORIDA BUILDING CODE, 6TH EDITION (2017). T 1 6. BE EN REQUIRED, SIDE OF ROOFPROVIDESAND SUBJECT TOHAN LOCAL JURISDICTION. GUTTERS AND DOWNSPOUTS WILL BE REQUIRED, SITE INSTALLED AND SUBJECT TO ZINGS ALL B CTION. 17. IN WIND BORNE DEBRIS REGIONS, EXTERIOR GLAZING SHALL BE PROTECTED WITH AND IMPACT RESISTANT COVERINGORWITH MINIMUM OVE WOOD STRUCTURAL PANELS PER SECTION T HARD A THE EBC.PANELSSHALL 9. PRECUT TOCOVERTHE GLAZEDOPENINGS WITH ATTACHMENT HARDWARE PROVIDED PER TABLE N SITE THE IMPACT RESISTANT COVERING IS WOOD STRUCTURAL PANELS ARE TO R PROVIDED E SITE BROTHERS. WITHINSUBJECTONE LOCAL JURISDICTIONAND APPROVAL . WIND BORNE DEBRIS REGIONS ARE AREAS WITHIN ONE MILE OF THE COASTAL MEAN HIGH WATER LINE WHERE THE ULTIMATE DESIGN WIND SPEED IS 130 MPH OR GREATER AND AREAS WHERE THE ULTIMATE DESIGN WIND SPEED IS 140 GREATER. 18TH . ALL MATERIALS USED IN THE CONSTRUCTION OFU THE BUILDING WHICH ARE COVERED R THE FLORIDA BUILDING COMMISSION CHAPTER FLORIDA BUILDING RULES $HALL HAVE CURRENT FLORIDA PRODUCT APPROVAL. 20. THESE PLANS COMPLY WITH THE ARE OA BUILDING CODE, 6TH EDITION (2017). 20. THE RAISED SEAL SET OF PLANS ARE ON FILE IN THE THIRD PARTY AGENCY'S OFFICE AS DIRECTED BY DBPR. 21. EMERGENCY LIGHTING SHALL BE CAPABLE OF PROVIDING INITIAL ILLUMINATION THAT IS ATLEAST AN AVERAGE OF 1 FOOT-CANDLE AND A MIN. OF A FC MEASURED ALONG THE EGRESS AT THE FLOOR LEVEL. ILLUMINATION LEVELS SHALL BE PERMITTED TO DECLINE TO .6 C AVERAGE AND A MINIMUM AT ANY POINT O .06 FC AT THE END OF THE EMERGENCY LIGHT TIME DURATION. A MAXIMUM -TO -MINIMUM ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE EXCEEDED. THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OF NOT LESS THAN 90 MINUTES. ELECTRICAL NOTES: 1. ALL CIRCUITS AND EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH THE APPROPRIATE ARTICLES OF THE NATIONAL ELECTRICAL CODES (NEC). 2. WHEN LIGHT FIXTURES ARE INSTALLED IN CLOSETS THEY SHALL BE SURFACE MOUNTED OR RECESSED. INCANDESCENT FIXTURES $HALL HAVE COMPLETELY ENCLOSED LAMP$. $URFACEMOUNTED INCANDESCENT FIXTURES SHALL HAVE A MINIMUM CLEARANCE OF 12 INCHES AND ALL OTHER FIXTURES SHALL HAVE A MININMUM CLEARANCE OF 6INCHES FROM" STORAGE AREA" AS DEFINED By NEC 410-8 1.) 3. WHEN WATER HEATERS ARE INSTALLED THEY SHALL BE PROVIDED WITH READILY ACCESSIBLE DISCONNECTS ADJACENT TO THE WATER HEATERS SERVED. THE BRANCH CIRCUIT SWITCH OR CIRCUIT BREAKER SHALL BE PERMITTED TO SERVE AS THE DISCONNECTING MEANS ONLY WHERE THE SWITCH OR CIRCUIT BREAKER IS WITHIN SIGHT FROM THE WATER HEATER OR IS CAPABLE OF BEING LOCKED IN THE OPEN POSION. 4. HVAC EQUIPMENT SHALL BE PROVIDED WITH READILY ACCESSIBLE DISCONNECTS ADJACENT TO THE EQUIPMENT SERVED. A UNIT SWITCH WITH A MARKED" OFF" POSITION THAT IS APART OF THE HVAC EQUIPMENT AND DISCONNECTS ALL UNGROUNDED CONDUCTORS SHALL BE PERMITTED AS THE DISCONNECTING MEANS WHERE OTHER DISCONNECTING MEANS ARE ALSO PROVIDED BY A READILY ACCESSIBLE CIRCUIT BREAKER. 5. PRIOR TO ENERGIZING THE ELECTRICAL SYSTEM THE INTERRUPTING RATING OF THE MAIN BREAKER MUST BE DESIGNED AND VERIFIED AS BEING IN COMPLIANCE WITH SECTION 110-9 OF THE NEC BY LOCAL ELECTRICAL CONSULTANT. 6. THE MAIN ELECTRICAL PANEL AND FEEDERS ARE DESIGNED BY OTHERS, SITE INSTALLED AND SUBJECT TO LOCAL JURISDICTION APPROVAL. T ALL CIRCUITS CROSSING OVER MODULE MATING LINE(S) SHALL BE SITE CONNECTED WITH APPROVED ACCESSIBLE JUNCTION BOXES OR CABLE CONNECTOR$. 8. REFERENCE STATE APPROVED PACKAGE FOR ELECTRICAL RISER DIAGRAM. 9. FIRE ALARM PULL STATION OPERABLE DEVICE SHALL BE LOCATED 42 TO 45 INCHES ABOVE THE FLOOR. FIRE ALARM HORN / STROBE DEVICE SHALL BE WALL MOUNTED WTH THE BOTTOM EDGE 80 INCHES ABOVE THE FLOOR. 10. EXTERIOR LIGHTS NOT INTENDED FOR 24 HOUR USE AND SHALL BE CONNECTED TO A PHOTOCELL OR TIMER. 11. ALL RECEPTICALS INSTALLED IN WET LOCATIONS (EXTERIOR) SHALL BE IN WEATHER PROOF (W.P.) ENCLOSURES. THE INTEGRITY OF WHICH IS NOT AFFECTED WHEN AN ATTACHMENT PLUG CAP IS INSERTED OR REMOVED. 12. WHEN NOT SHOWN ON THE PLANS PROVISIONS FOR EXIT DISCHARGE LIGHTING (INCLUDING EXIT DISCHARGE EMEGENCV LIGHTING) ARE DESIGNED BY OTHERS AND THE RESPONSIBILITY OF THE BUILDINGS OWNER AND SUBJECT TO LOCAL JURISDICTION APPROVAL. TM ACCESSIBILITY NOTES: 1. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGN SHALL BE DISPLAYED AT ALL ACCESSIBLE RESTROOM FACILITIES AND AT ACCESSIBLE BUILDING ENTRANCES UNLESS ALL ENTRANCES ARE ACCESSIBLE. INACCESSIBLE ENTRANCE$ $HALL HAVE DIRECTIONAL SIGNS INDICATING THE ROUTE TO THE NEAREST ACCESSIBILE ENTRANCE. 2. ACCESSIBLE DRINKING FOUNTAINS SHALL HAVE A SPOUT HEIGHT NO HIGHER THAN 36 INCHES ABOVE THE FLOOR AND EDGE OF BASIN NO HIGHER THAN 34 INCHES ABOVE THE FLOOR FOR INDIVIDUALS IN WHEEL- CHAIRS. ADDITIONALLY, DRINKING WATER PROVISIONS SHALL BE MADE FOR INDIVIDUALS WHO HAVE DIFFICULTY IN BENDING. 3. WHERE STORAGE FACILITIES SUCH AS CABINETS, SHELVES, CLOSETS, AND DRAWERS ARE PROVIDED AT LEAST ONE OF EACH TYPE PROVIDED SHALL CONTAIN STORAGE SPACE COMPLYING WITH THE FOLLOWING: DOOR$ ETC. TO SUCH SPACES $HALL BE ACCESSIBLE ie. TOUCH LATCHES U-SHAPED PULL$ : SPACES SHALL BE WITHIN 15 INCHES MINIMUM AND M, OF E MAXIMUM OF THE FLOOR FOR FORWARD REACH OR A MIMES MINIMUM AND 54 INCHES MAXIMUM OF THE FLOOR FOR SIDE REACH' CLOTHES RODS SHALL IBE R A MINIMUM DS 54 INCHES ABOVE THE FLOOR 48 INCHES MAXIMUM WHEN DISTANCE FROM WHEELCHAIR TO ( ROD EXCEEDS 10 INCHES) 4. CONTROLS, DISPENSERS, RECEPTACLES AND OTHER OPERABLE EQUIPMENT SHALL BE NO HIGHER THAN R INCHES ABOVE THE FLOOR FOR FRONT APPROACH OR ANINCHES15 INCHES ABOVE THE FLOOR FOR SIDE APPROACH. RECEPTACLES IO WALLS SHALL BE MOUNTED NO LESS THAN SPECIAL EQUIP ABOVE THE FLOOR. EXCEPTION: HEIGHT LIMITATIONS DO EPT APPLY LES WHERE THE USE OF SPECIAL EQUIPMENT DICTATES OTHERWISE OR WHERE ELECTRICAL RECEPTACLES ARE NOT NORMALLY INTENDED FOR USE BY BUILDING OCCUPANTS. 5. WHERE EMERGENCY WARING SYSTEMS ARE PROVIDED, THEY SHALL INCLUDE BOTH AUDIBLE AND VISUAL ALARMS. THE VISUAL ALARMS SHALL BE LOCATED THROUGHOUT, INCLUDING RESTROOMS, AND PLACED BO INCHES ABOVE THE FLOORPA ES SHALL BELOW CEILING, WHICHEVER A IS LOWER. 6. DOORS TO ALL ACCESSIBLE SPACES SHALL HAVE ACCESSIBLE HARDWARE R. LEVER -OPERATED, PUSH TYPE, DOORS U - SHAPED) MOUNTED NO HIGHER THAN 48 FFORT. TH ABOVE THE FLOOR. ]. SHALLNOT EXCEED INGING.THESAND5 UBORCER ALL SLIDING, OPEN A LDING, OR AND SHALL NOT EXCEED 8.5 LBS. FOR EXTERIOR SWINGING DOORS AND 5 LBS. FOR ALL SLIDING, FOLDING, AND INTERIOR SWINGING DOORS. 8. FLOOR SURFACES SHALL BE STABLE, FIRM, AND SLIP-REATER T. CHANGES IN LEVEL BETWEEN E0.25 ATERCHA AND 0CH RE $HALL BE BEVELED WITH A SLOPE ES GREATER THAN INC CHANGES IN LEVEL GREATER THAN 0.5 INCH REQUIRE RAMPS. CARPET PILE THICKNESS SHALL EC ION.DOORWAY MAX. GRATINGS IN FLOOR SHALL HAVE SPACES NO GREATER THAN 0.5 INCH WIDE IN ONE DIRECTION. DOORWAY THRESHOLDS SHALL NOT EXCEED 0.51NCH IN HEIGHT. 9. ACCESSIBILE WATER CLOSETS $HALL BE 17 INCHES FROM THE FLOOR R THE TOP OF THE SEAT. GRAB BARS SHALL BE LOCATED ES ALONG MINIMUM WHEN LOCAWATER CLOSET, E T, A THE WATER MOUNT D 3 421N. & 39 M MAX.NINUM FROM WHEN LOCATED ALONG THE SIDE OF THE WATER CLOSET, AND SHALL BE MOUNTED 33" MIN.B 36" AX. FROM FLOOR THE TOPTHE RAIL. 0. ACCESSIBLE URINALS $HALL BE STALL -TYPE OR WALL HUNG WITH ELONGATED RIMS AT MAXIMUM OF 17 INCHES ABOVE THE FLOOR. 1. ACCESSIBLE LAVATORIES SHALL BE MOUNTED WITH THE RIM NO HIGHER THAN 34 INCHES ABOVE THE FLOOR AND A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE FLOOR TO THE BOTTOM OF THE APRON. 2. ACCESSIBLE SINKS SHALL BEMOUNTED WITH RIM HIGHER THAN 3CHESDINCHES ABOVE THE FLOOR TSINK.AND A CLEARANCE OF AT LEAST 6.5INCHESINCHES HIGH, 30 MUM.INCHES WIDE, AND 191NCHES DEEP UNDERNEAT SINK. THE SINK DEPTH SHALL BE ES UNDER N HER MAXIMUM. 3. HOT WATER AND DRAIN PIPES UNDE CTC CONTACT. INSULATION R D SINKSPROTECTION ION MAT INSULATED B SI OTHERWISE CONFIGURED TO PROTECT CONTACT. INSULATION OR PROTECTION MATE LAVATORIES IE SITE INSTALLED. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER ACCESSIBLE LAVATORIES AND SINKS. 4. ACCESSIBLE LAVATORIES AND SINKS SHALL HAVE ACCESSIBLE FAUCETS (ie. LEVER. OPERATED, PUSH -TYPE, ELECTRONICALLY CONTROLLED). 5 WHERE MIRRORS ARE TO BE PROVIDED ABOVE A LAVORITORYHER THAN COUNTERTOP, IT SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING SURFACE NO HIGHER SHALL B LOCATED ABOVE FINISHED FLOOR. 6 WHERE MEDICINE CABINETS ARE PROVIDED AT LEAST ONE SHALL BE LOCATED WITH A USABLE SHELF NO HIGHER THAN 44 INCHES ABOVE THE FLOOR. 7. GRAB BARS REQUIRED FOR ACCESSIBILITY SHALL BE 1.251NCHE5 TO 21NCHES IN DIAMETER WIRH 1.5INCHES CLEAR SPACE BETWEEN THE BAR AND THE WALL. 8. TOILET STALL DOORS SHALL BE THE SELF -CLOSING TYPE. 9. WATER C DISET CER FLUSH BE LOCATED SSHALL BE JACENT MOUNTED ON T ACCESSIBLE LAVATORIES. :0. WATER CLOSET FLUSH CONTROL SHALL BE MOUNTED ON THE WIDE SIDE OF THE CLOSET. ORB/ Julio `�J�; ''VIGENSF '• lS/% Orbegoso No.38769 2020.06.23 ,�3p� •, STATE OF (C/� F40RIDP.-`o 16 :10: 5 3 �oNAL1E,, I I -04 00 STRUCTURAL LOAD LIMITATIONS: DESIGN CODES FLORIDA BUILDING CODE, 6TH EDITION (2017) ASCE 7-10 CODE BUILDING DEAD LOADS A. ROOF = 10 PSF B. FLOOR - 10 PSF C. WALLS PSF BUILDING LIVE LOADS A. ROOF = 30 PSF B. FLOOR - 50 PST CONCENTRATED LOAD. C. CORRIDOR = 100 PSF OVER 30 INCH C 20 INCH AREA LOCATED ANYWHERE ON FLOOR. ROOF SNOW LOAD: N/A WIND LOAD CRITERA: 1. 146 Vasd / 188 Vult MPH (HVHZ) WIND SPEED 2. II RISK CATEGORY 3. II BUILDING CATEGORY 4. ENCLOSURE CLASSIFICATION: ENCLOSED GCPI =0.18 INTERNALPRESSURE COEFFICIENT. 5. C EXPOSURE FACTOR 6. 0.85 WIND DIRECTIONALITY FACTOR(Kd) 7. 0.85 GUST RESPONSE FACTOR (Gh) 8. MAIN FRAME STRUCTURE OVERTURNING LOAD Pr - -93 PSF 9. COMPONENT & CLADDING LOAD: (ROOF) Pr = ZONE 1: 42.3 PSF, ZONE 2:71.0 PSF, ZONE 3:106.9 PSF ( WALL) PW = ZONE 4: 45.9 PSF, ZONE 5: 56.6 PSF 10. ENCLOSED BUILDING ENCLOSURE CLASSIFICATION 11. THIS BUILDING IS NOT DESIGNED FOR PLACEMENT ON THE UPPER HALF OF A HILL OR ESCARPMENT EXCEEDING 15 FEET IN HEIGHT, SEISMIC LOAD: N/A FLOOD LOAD: THIS BUILDING IS NOT DESIGNED TO BE SUBMERGED OR SUBJECTED TO WAVE ACTION WHEN LOCATED IN A FLOOD PRONE OR ZONE AREA. FINISH FLOOR ELEVATION MUST BE LOCATED ABOVE THE BUILDING SITE FLOOD PLANE LEVEL. SITE INSTALLED NOTES: NOTE THAT THIS LIST DOES NOT NECESSARILY LIMITS THE ITEMS OF WORK AND MATERIALS THAT MAY BE REQUIRED FOR A COMPLETE INSULATION. ALL SITE RELATED ITEMS ARE SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 1. THE COMPLETE FOUNDATION SUPPORT AND TIE DOWN SYSTEM. 2. RAMPS, STAIRS AND GENERAL ACCESS TO THE BUILDING. 3. PORTABLE FIRE EXTINGUISHERS (S). 4. DRINKING FOUNTAIN, BUILDING DRAINS, CLEAN -OUTS, AND HOOK- UP TO PLUMBING SYSTEM. 5. ELECTRICAL SERVICE HOOK-UP ( INCLUDING FEEDERS) TO THE BUILDING. 6. THE MAIN ELECTRICAL PANEL AND SUB -FEEDERS MULTI -UNITS ONLY . ].CONNECTION OFELECTRICAL CIRCUITS CROSSING OVER MODULE (S MATING LINES (S) - ( MULTI -UNITS ONLY). 8. STRUCTURAL AND AESTHETIC INTERCONNECTIONS BETWEEN 9. WINDOW AND DOOR HIGH WINDSTORM COVERINGS PER CODE. 10. GUTTERS AND DOWNSPOUTS (IF APPLICABLE). 11. SINK AND CABINETS. 12. FIRE ALARM SYSTEM, WIRING, ETC. 13. THERMAL EXPANSION DEVICE IF REQUIRED. STATE CODES: FLORIDA FLORIDA BUILDING CODE, 6TH EDITION (2017) FLORIDA MECHANICAL CODE 6TH EDITION (2017) FLORIDA PLUMBING CODE 6TH EDITION (2017) FUEL GAS CODE 6TH EDITION (2017) 2014 NATIONAL ELECTRIC CODE FLORIDA ACCESSIBILITY CODE 6TH EDITION (2017) FLORIDA FIRE PREVENTION CODE 6TH EDITION (2017) OCCUPANCY BUSINESS CONSTRUCTION TYPE V-B DRAWING INDEX: C1 COVER SHEET Al FLOOR PLAN A1.1 ELECTRICAL PLAN A2 ELEVATIONS A3 CROSS SECTION A4 FOUNDATION PLAN ELEVATION NOTES (TYP. ) 1.) SEE CROSS SECTION FOR METHOD OF ROOF VENTILATION 2.) HANDICAP RAM(S), STAIRS (S), AND HANDRAILS ARE TO BE DESIGNED AND SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL JURISDICTION AND APPROVAL. 3.) FOUNDATION ENCLOSURE ( WHEN PROVIDED) MUST HAVE 1 SQUARE FOOT NET VENT AREA PER 1/11/150N OF THE FLOOR AREA, AND AN IB"X24"MINIMUM CRAWL SPACE ACCESS, SITE INSTALLED BY OTHERS, SUBJECT TO LOCAL JURISDICTION AND APPROVAL. " NOTICE " PLEASE REVIEW PLANS COMPLETELY, ANY COMPONENTS CROSSING MATE. LINES WILL BE SITE INSTALLED BY SET UP CREW. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIO ORBEGOSO, P.E. ON THE DATE AND/OR TIME STAMP SHOWN USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES MUST BE VERIFIED ON ANY ELECTRONIC COPIES. "NOTICE" THESE DOCUMENTS WILL NO LONGER BE VALID 21 DAYS AFTER THE DATE SIGNED VALID THRU : JULY 14TH, 2020 REVISION DATE: CONSULTING ENGINEER JULIO ORBEGOSO 202 DORIS DR. LAKELAND,FL 33813 PE LICENSE #38769 L O LL LU 0" D U �D I..I- VNJ I..L D 0 5O G DATE: 05-20-2019 DRAWN: R.L.G. JOB #: CPX-114722 C1 U TYPICAL DOOR FRAMING HEADER STRAP i— EQUAL TO HUGHES HLSTA 24 (1260# UPLIFT) swm - X O 16 4 O.C. STUD HURRICANE ANCHOR EQUAL (1250# UPLIFT) TYPICAL FRAMING SCALE: 3/8" = P-O" III MAX � vlhqh \ ( -LX4 111f2 2 -2X4 SYPf2 2 -2X4 SYPf2 O f6' O.C. TYPICAL WINDOW FRAMING FLOOR PLAN SCALE: 1 /4" = F-0" LAV LAV SUPPLY LINE IS BASED ON AN ASSUMED AVAILABLE PRESSURE OF 46 TO 60 PSI AT MAIN INLET. ALL STUB -UPS 1/2' SUPPLY COLUMN STRAPPING SCHEDULE A INDICATES TYPE OF STUD TI INDICATES TYPE OF TIE DOWN STRAP INDICATES WITH RIDGE BEAM BEARING ■ STIFFENER ( SEE RIDGE BEAM NOTES FOR SPECIFICATIONS) COLUMN STRAPPING SCHEDULE 0(2) 2x4 SPF #2 THIS HALF O(2) 2x4 SPF #2 EACH HALF 0(3) 2x4 SPF #2 THIS HALF &3) 2x4 SPF #2 EACH HALF 0(4) 2x4 SPF #2 THIS HALF F&4) 2x4 SPF #2 EACH HALF (0, (5) 2x4 SPF #2 THIS HALF D(5> 2x4 SPF #2 EACH HALF (6> 2x4 SPF #2 THIS HALF 0(6> 2x4 SPF #2 EACH HALF 0(7) 2x4 SPF #2 THIS HALF L&7) 2x4 SPF #2 EACH HALF M (8) 2x4 SPF #2 THIS HALF N&8) 2x4 SPF #2 EACH HALF NOTES - I, ALL COLUMN STUDS SHALL BE NAILED TOGETHER PER NDS AND FASTENED TOGETHER WITH 100% PVA GLUE COVERAGE. 2. COLUMN STUDS SHALL NOT BE NOTCHED OR BORED. 3. INSTALL ONE TIE DOWN STRAP FROM RIDGE BEAM TO COLUMN AND FROM COLUMN TO FLOOR RIM JOIST FOR EACH STUD OF COLUMNS. (le- 3 STUD COLUMN WILL REQUIRE 4 TIE DOWN STRAPS) 4. STRAPS SHALL NOT BE OVERLAPPED OR DOUBLED UNLESS SPECIFIE OTHERWISE. TIE DOWN STRAP DESCRIPTION TI 20 GA. X I - 1/2' GALV. STEEL STRAP WITH (7) 0.148'OX3' NAILS EACH END. TWO 26 GA. X 1.5' GALV. STEEL STRAPS MAY BE SUBSTITUTED FOR ONE 20 GA. X I - 1/2' STRAP. NAILS MUST PENETRATE 2' MININUM INTO ALL MEMBERS. PENETRATION MAY BE REDUCED TO I - 1/2' IF 8 NAILS ARE USED IN LIEU OF 7. IN NO CASE SHALL SPLITTING OF WOOD BE PERMITTED. 2' VTR 1 SINK 3, INSTALL e FACTORY 3' 3' TO WASTE 3' TO WASTE 3' TO WASTE TERMINAL TERMINAL TERMINAL AALLLL SINK 6 LAV'S PROVIDEED WITH 1 1/2' TRAPS WITH SLIP JOINT CONNECTIONS. DWV PLUMBING RISER SCALE: 3/8" = F-0" e " NOTICE " THESE DOCUMENTS WILL NO LONGER BE VALID 21 DAYS AFTER THE DATE SIGNED VALID THIRD: JULY 14TH, 2020 IY O LL LNU of o D D co V °E�sEP°so= Julio Orbegoso J - No.38769 / ) 1 co 2020.06.23 V/ J ! �� STATE of TF OP 16:11:08-04'00' Q �'s`SfONAL J THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIO ORBEGOSO, P.E. ON THE DATE AND/OR TIME STAMP SHOWN USING A 0 DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENTARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES MUST BE O VERIFIED ON ANY ELECTRONIC COPIES. CONSULTING ENGINEER JULIO ORBEGOSO 202 DORIS DR. LAKELAND, FL 33813 PE LICENSE #38769 REVISION DATE: DATE: 05-20-2O19 DRAWN: R.L.G. JOB #. CPX-114722 0 SHEET NO. Al ELECTRICAL PANEL 'A' SIZING DESCRIPTION, .0035 KW SF X 672 SF X 1.25 2.94 1 HVAC 2 10.9 KW 10.9 12 RECEIPTS B 180 VA / 1000 2.16 1 WATER HEATER E 1.9 KW x 1.25 6.50 2 FANS 2 .3 KW X 1.25 .75 TOTAL 23_25 KW TOTAL / 240 X 1000 9688 AMPS INSTALL 100 AMP PANEL 120 / 240V 10 ELECTRICAL SCHEDULE CIRCUIT NOMENCLATURE BREAKER (AMPS) WIRE SIZE CU. NM. W/G. 1 & 3 HVAC 160A 2P 6-2 2 LIGHTING 20A IP 12-2 4,6 RECEPTS 20A IP 12-2 5 & 7 EEMAX 30A 1P 10-2 ALL PORTABLE APPLIANCES, INCLUDING W/H. TO HAVE DISCONNECT IF NOT WITHIN VIEW OF ELECTRIC PANEL \ I I _ r•L, iH —�� r•:y1 Ali` � IH - W ►ter ►� r�� ►� ELECTRICAL PLAN SCALE: 1/4" = 1'-0" ELECTRICAL PANEL 'B' SIZING DESCRIPTION- .0035 KW SF X 672 SF X 1.25 2.94 1 HVAC E10.9 KW 10.9 10 RECEIPTS 8 180 VA / 1000 1.80 TOTAL 15_64 KW TOTAL / 240 X 1000 6517 AMPS INSTALL 100 AMP PANEL 120 / 240V 10 ELECTRICAL SCHEDULE CIRCUIT NOMENCLATURE BREAKER (AMPS) WIRE SIZE CU. NM. W/G. 1 & 3 HVAC 60A 2P 6-2 2 LIGHTING 20A 1P 12-2 4,6 RECEIPTS 20A 1P 12-2 ALL PORTABLE APPLIANCES, INCLUDING W/H. TO HAVE DISCONNECT IF NOT WITHIN VIEW OF ELECTRIC PANEL 3T� woo a-0 Pryl� T�p[p MOM INTN(E. CRT t1,3H �fi1PSIt4(T1TJ 3 TRI HVAC V/10 KV IfAT 2 ., NV/iC UNIT mPRO Ev VIIH FRESH AIR INTAKE. CRT *IX ELECTRICAL PANEL 'C' SIZING DESCRIPTION- .0035 KW SF X 672 SF X 1.25 2.94 1 HVAC E 10.9 KW 10.9 14 RECEIPTS 8 180 VA / 1000 2.52 TOTAL 16_36 KW TOTAL / 240 X 1000 6817 AMPS INSTALL 100 AMP PANEL 120 / 240V 10 ELECTRICAL SCHEDULE CIRCUIT NOMENCLATURE BREAKER (AMPS) WIRE SIZE CU. NM, W/G. 1 & 3 HVAC 60A 2P 6-2 2 LIGHTING 20A IP 12-2 4,6 RECEPTS 20A IP 12-2 ALL PORTABLE APPLIANCES, INCLUDING W/H. TO HAVE DISCONNECT IF NOT WITHIN VIEW OF ELECTRIC PANEL I ELECTRICAL LEGEND I &DUPLEX RECEPT 0 16" A.F.F. DUPLEX RECEPT 0 42" A.F.F. @ERECEPT 220 VOLT $ SNITCH PHONE JACK 0 42" A.F.F. p PHONE JACK 0 16" A.F.F. C) THERMOSTAT +INCANDESCENT UGHT 15/25W MAX +EYEBALL UGHT 4OW MAX (4EXHAUST FAN ® EXHAUST FAN / UGHT EMERGENCY LIGHT Q J BOX FOR MANUAL PULL STATION ® 12" X 12" SUPPLY AIR REGISTER ® 12" X 12" RETURN AIR GRILLE 4V EMERGENCY EXIT LIGHTING ® FLUORESCENT FIXTURE 87.6W. MAX UGHT 4OW MAX OOF PORCH UGHT 60W. MAX = EEMAX W/H mi I " NOTICE " THESE DOCUMENTS WILL NO LONGER BE VALID 21 DAYS AFTER THE DATE SIGNED VALID THRU:JULY 14TH, 2020 ``III ORB ITS// Julio Orbegoso - No.BBTB9 = 2020.06.23 Q'... STATE OF �[[/� 1 6: 1 1: 1 7 ''4ORMI". G\�� -�!,`\ I 1 -04 00 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIO ORBEGOSO, P.E. ON THE DATE AND/OR TIME STAMP SHOWN USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES MUST BE VERIFIED ON ANY ELECTRONIC COPIES. REVISION DATE: CONSULTING ENGINEER JULIO ORBEGOSO 202 DORIS DR. LAKELAND,FL 33813 PE LICENSE #38769 L"1_ IO L.L W D O DU Q0 U) X U J CO J D 0 O 2 DATE: 05-20-2019 DRAWN: R.L.G. JOB #: CPX-114722 SHEET NO. A1.1 LEFT SIDE ELEVATION SCALE: 1/4" = F-0" RIGHT SIDE ELEVATION SCALE: 1/4" =1'-0" FRONT ELEVATION SCALE: 1/4" = l'-0" ° = Julio Orbegoso Na.36769 2020.06.23 STATEOF :• �(/�� 16:11:26-04'00' F<ORIDP.•'G�� THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIO ORBEGOSO, P.E. ON THE DATE AND/OR TIME STAMP SHOWN USING A DIGITAL SIGNATURE, PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES MUST BE VERIFIED ON ANY ELECTRONIC COPIES. CONSULTING ENGINEER JULIO ORBEGOSO 202 DORIS DR. LAKELAND, FL 33813 PE LICENSE #38769 REVISION DATE: �Dc W 0 LL LU D O .. DU Q0 v! x U) J C'M J 0 O 2 DATE: 05-20-2019 DRAWN: R.L.G. JOB #: CPX-114722 BACK ELEVATION SCALE: 1/4" - F-0" " NOTICE " THESE DOCUMENTS WILL NO LONGER BE VALID 21 DAYS AFTER THE DATE SIGNED VALID THRU : JULY 14TH, 2020 A OOT�RliIO�N IIM� �i m A2 2) MI 32FI IFUROOF R.-It�MNC, DETAIL CONNECT EACH TRUSS WITH SIMPSON H10 HURRICANE TIE FASTENED WITH 8d 1 S1 22" NAROIpI-SMaFS8 INT�L�pp TRUSS, WW1& 8 JN;rO TOP STAPLE S 6PER STR++AD T(Y ICAL"SI/WALLS) 110 -10" 50 102"-0" ROOF R U.ATION WINDOW HEADER, SEE SVOPV CHART TYP. WINDOW, SEE SHEET 5EIT ppSILL PLATE 2x4 SPF g2 INSULATIONAFTBACK WALL 2 X 4 SPF #2 WALL STUDS 0 16" 2 X 4 SPF /2 BOTTOM PLATE --_ IN R-11 FLOOR INSULATION u a a n woLc mrcnrrinu (V N �FLpppR. pR LUp� gg 100r_0. ABOVE(TYP�WTRiRIG � - - - - - - W]ROGC#R AND CROSSNEMBER SPACING 4 BLOCKING TYP. \\ -- �j / \ PLYWOOD ROOF SHEATHING NAILING PATTERN 5/8- PLYWOOD SHEATHING SHALL BE BLOCKED A— =1- WITH 2x NOMINAL LUMBER OF THE SAME SPECIE AND GRADE AS TRUSS TOP CHORD FOR A DISTANCE OF 4'-O' FROM EACH END WALL WITH ROOF BOUNDARIES NAILED AT 4'-0" O.C. AND OTHER BLOCKED EDGES NAILED AT 6' O.C. AND UNBLOCKED EDGES AT 6" O.C.. NAIL FIELD LOCATIONS AS FOLLOWS 4" O.C. IN AREAS WITHIN 4'-0" OF BUILDING CORNERS 6" O.C. AT ALL OTHER LOCATIONS WITHIN 4'-0' OF EXTERIOR EDGES OF BUILDING 10" O.C. ELSEWHERE ALL NAILS SHALL BE 10d COMMON NAILS. INTERIOR FINISH MATERIAL CEILING: T-GRID INSTALLED PER MANUFACTURER'S SPECIFICATIONS WALL: 1/2" VINYL COVERED GYPSUM WALLBOARD; INSTALLED PER MANUFACTURER'S SPECS. FLOOR: BLOCK TILE IN BATHROOM AND WET AREAS FLOORING ALL OTHER AREA TO BE PROVIDED BY OTHERS. ]Su Q Y IAVF$ tt� CfEST PRODUCTS Inu nn 1� nn�u aarr�u D�uu 77Ep �3Rp�g� �Lpp TgCREyWpS� 01 O�LAG SCREWSOMUST MIN //- �pgT�N I GE g�p� Q 7�USS W77H N9�S5 THAN �8) 15 GA. STAPLES WITHPENETRATION VNCfOR M ANiib D O 1 3' INJIp�IEAAC�NM�F POST EQUNLANNNNTOFS7ENING Up 5 CI TIa 5 SECTION A -A x X AFA // RIM MEMBER 1x3 SYP #3SEE J >< I L TO WALLRFASTIINGAREO REQUIREMENTS. 7 1/2' MAX AA!! EXTERIOR WALL FINISH: ALUMINUM SIDING 77 difxx / y)� RRp2 XX55 y�ry/ N050 A,'k II �ASFPp� 151?`B$TRAP qSPSN ®15 GA X 1 1%2 $ A��TN MIN. 1 NET1R`�A�IONE. G�s?OUTRIGGER CH H SECTION O UNIT "AW n CEX7���p� E8A$ �8 8 � 8PTT8U MORDUNIT WALL STRUCTURAL BRACING SI IRMS: Z Q ��BRACI1�2"JJANI CONSIST OF A WITH ALL A PGE E(_Sj#Oj;FJ PFmAF 1-3 aQ Ua gMINMIMUM Epp GpNppp�,�INpAgL ELU p �THRREA� N� IEENGTH z THE WALLAHE ENTIRE Q a 55Lpp�� 75p RSE�pWFSOF 1 �� X LpAG SCREIYS MUST MODULE Po�AM g IF Mp-A L�:gp Epp I EXETX� p N E �d p�,�0ry p�Lg 7R16 XT N100X Z O ORTO UDJACENT TR SS p/�BAyPABOA� N0ILS 6" O.CG EDGESID��2Q.C� FlELCD YATH PER LU COVERAGE. 3" Q WALLS: ENDDwwwwwwwwwwww jAq� T �� G I R ,CQNTIN000SppFF �p�,� OR TO jl3}fp47}{MIGNIM�p7MGBI fRAIIM .LUM ERS THENGRADEES J Q N 2x8 PLATE P.T. _ BRACING ��ppggMATTpE��RIIAA�L 7Tgg���� gg GG X p �EEExXN , LOMON ORSGALVABOX RNAILSE4I1IOC. SEDGES ANDE�j,'' Fl a pQ . 0 1E EXISTING GRADE CROSSMEMEER SECTION O TYPICAL CROSS SECTION SCALE: 3/4" = 1'-0" RAIL AND RAIL FASTENING CHART WIND 15'-8" MODULE WIDTH 13'-8" MODULE WIDTH 11'-8' MODULE WIDTH SPEED (� C) MININUM RAIL SIZE STAPLES PER RAIL MININUM RAIL SIZE STAPLES PER RAIL MININUM RAIL SIZE STAPLES PER RAIL 188 MPH 2X10 8 2 X 8 7 2 X 8 6 NOTES: 1. THIS DESIGN IS BASED ON ASCE 7 - 02 WITH A ROOF ANGLE OF LESS THAN 10". 2. ALL RAILS ARE SYP /2 LUMBER OR BETTER. 3. ALL FASTENERS ARE 15 GA. X 7/16- X 2 - 1/2" STAPLES OR EQUAL OF ALL FLANGESAND MiBS AT ALL OUTRIGGERS AND CROSSMEMBERS EXTERIOR FINISH MATERIAL ROOF: .45 MIL BLACK RUBBER ROOF COVERING (EPOM) INSTALLED PER MANUFACTURE'S SPECIFICATIONS. WALL: 0.19 ALUMINUM SIDING OVER APPROVED MOISTURE NAAIILSE0 4N OCR ACIN(EEDGGE)MAND 8 O.C. EWATERIAL, FASTEN .. Bd COMMON NOTE: ALL ROOF COVERINGS SHALL MEET CLASS C OR BETTER RED. ROOFING AND SIDING MATERIALS AND THERE FASTENINGS SHALL BE DESIGNED AND INSTALLED SO AS TO RESIST THE COMPONENT WIND LOAD SHOWN ON THE COVER SHEET. ALL ROOF COVERINGS SHALL MEET CLASS C OR BETTER REQUIREMENTS. WALL FINISH SHALL BE INSTALLED OVER APROVED MOISTURE PROTECTION AND BRACING MATERIAL MOISTURE PROTECTION BEHIND WALL COVERING SHALL B€ AS REWIRED BY EXTERIOR WALL FINISH MANUFACTURERS SPECIFICATIONS, BUT NOT LESS THAN ONE LAYER OF NO. 15 ASPHALT FELT, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT ATTACHED IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS WATER - RESISTIVE BARRIER BEHIND THE EXTERIOR WALL FINISH. GA OUTRIGGERS FRAME DETAIL SCALE: NOT TO SCALE GENERAL CROSS — SECTION NOTES: 1. UNLESS OTHERWISE SPECIFIED, ALL STEEL MUST COMPLY W/ ASTM A36, YIELD STRENGTH = 36 KSI. 2. ALL LAG SCREWS MUST COMPLY WITH ANSI / ASME B18,2,1, Fyb = 60 K.S.I. MIN. 3. TRUSS BOTTOM CHORDS MUST BE BRACED IN ACCORDANCE WITH SPECIALTY ENGINEERS DESIGN DRAWINGS. ��12'-10' _— FASTEN EACH RAIL TO EACH TRUSS (SEE CHART) EXTERIOR FINISH MATERIALS NOT SHOW 1 1011o'_—___ SIDE WALL FASTEN INSIDE RIM JOIST TO FLOOR JOIST WITH 3- 16D NAILS PER FLOOR JOIST. FASTEN OUTSIDE RIM JOIST TO INSIDE RIM JOIST WITH 16D NAILS SPACED 5" O.C. RAIL REQUIRED AT TOP AND BOTTOM, EXTENDING CONTINUOUS FLOOR JOIST' 4'-0" MINIMUM FROM END WALL WITH NO END JOINTS SCALER"=1'-0" SECTION A -A SCALER. 1/2" = V-0" FASTEN ROOF SHEATHING TO (2) 24 SYP. /2 TOP PLATE PATH BOUNDRY FASTENER SPACING. ROOF SHEATHING SEE ROOF SHEATHING DETAIL ROOF SHEATHING EXTEND END WALL SHEATHING CONT. BLOCKING TO ROOF SHEATHING AND FASTEN TO TOP PLATE WITH THE SAME FASTENER SIZE AND SPACING REQUIRED FOR THE END WALL (3)-15 GA x 7/16' x 2-1/2' STAPLES EACH END (3) -0.148 DIA x 3' NAILS FROM RAIL TO EACH STUD II (3GA x 7/16" x 2-1/2* STAPLES EACH END 2.6 FIRE STOP STOP SIT= FLOORR PLAN AN FOR ]0NG BETWEN ACTUAL OVERHANG LENGTH ALL STUDS AT CE]UNG LINE II --�-2x6 SYP 12 STUDS 016" O.C. ENDWALL DETAIL SCALE -I" = F-0" I RIDGE BEAM C❑NSTRUCTI❑N I 5 - PLYS/ 54LAYER,"48/24EACH HALLF CONTINUOUS ENTIRE I LENGTH OF BUILDING NOTES: 1. PLYWOOD FACE GRAINMUST BE PARALLEL TO THE RIDGE BEAM SPAN. 2. ALL PLYWOOD BUTT JOINTS MUST BE STAGGERED 24" MINIMUM. 3. ALL RIDGE BEAM PLYWOOD LAMINATIONS MUST BE THE SAME DEPTH, THICKNESS, AND GRADE OF PLYWOOD. NO LUMBER OR PLYWOOD FLANGES ARE PERMITTED. 4. PLYWOOD MUST BE MANUFACTURED IN ACCORDANCE W PSI - 95. 5. PLYWOOD LAMINATIONS IN EACH HALF OF THE UNITS UST BE GLUE NAILED TO ADJACENT LAYERS IN ACCORDANCE W/ POS SUPPLEMENT /5, W/ AN ADHESIVE COMPLYING W ASTM D2559, OR CA25-4. 6. PLYWOOD MUST NOT B TREATED W/ A FIRE RETARDANT PROCESS. 7. MOISTURE CONTENT MUST BE LESS 'THAN 16X 8. BEAMS MUST EXTEND CONTINUOUS OVER ENTIRE LENGTH OF ALL COLUMN SUPPORTS. 9. INSTALL (2 X 4 1 X 20" SPF t 3 RIDGE BEAM BEARING STIFFENER OVER SUPPORT COLUMNS. WHEN SPECIFIED ON FLOOR PLAN; FASTEN THE FACE �6) THE STIFFENER T THE RIDGE BEAM W/ 100% GLUE COVERAGE AND 15 GA. X 2 - 1%2' STAPLES. No. UM THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIO ,p0' SraTE or ORBEGOSO, P.E. ON THE DATE ANDAOR TIME STAMP SHOWN USING A :'tv�; DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES MUST BE VERIFIED ON ANY ELECTRONIC COPIES. Julio Orbegoso CONSULTING ENGINEER JULI DOREGOSO 2 0 2 0.0 6. 2 3 LAKELAND, FL 3 PE LICENSE #38 69769 16:11:36-04'00' " NOTICE " THESE DOCUMENTS WILL NO LONGER BE VALID 21 DAYS AFTER THE DATE SIGNED VALID THRU: JULY 14TH, 2020 REVISION DATE: DATE: 05-20-2019 DRAWN: R.L.G. JOB #: CPX-114722 A3 OAR lilO6Af 11M0Ill..i m FLORIDA BUILDING CODE. 6TH EDITION (2017) COMPLIANCE STATEMENT: 2 �— 180 MPH (HWZ) 2. II 3. C 4. INTERNAL PRESSURE COEFF.: t0.18 GROUND ANCHOR NOTE GENERAL NOTE: STABILIZER PLATES ARE NOT REWIRED PATH INSTALLATION. HOWEVER, ANY UNSTABLE SOIL CONDITIONS THAT MAY IMPACT THE GROUND ANCHORS ABIUTY TO RESIST UPUFT MUST BE BROUGHT TO THE ATTENTION OF THE ENGINEER. GROUND ANCHORS ARE TO BE INSTALLED PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. SYMBOLS VF.T. FRAME TIE -DOWN FASTENED TO GROUND ANCHOR FOUNDATION DIMENSIONS A. MODULE WIDTH B. PIER TO MODULE EDGE C. STEEL BEAM SPACING 11' - 8' N/A VARIES D. MAX. PIER SPACING MINIMUM SOIL BEARING CAPACITY 6' - 1" 2000 PSF I F.T. F.T. F.T. F.T. IN F.T. T. F.T. ----- F.T. ------ F.T. ------ F.T.------- NOTE: LESSEE/END USER IS RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND OBSTRUCTIONS NIX LESSEE D USER IS RESPONSIBLE FOR CONDUCTING A PULL TES IF REWIRED FOR PERMITTING. P.T. 2x8 SHIMS OPTIONAL CAP BLOCK 16"x18"x7/8" ABS PAD 8"z8"z16" BLOCK NOTE: MAXIMUM OF (2) LAYERS OF WOOD MAY BE USED. ePIER HAn SCALE: 3/4" = 1'-0" T SIDE WALL PERIMETER RAL 19 9 FRAME OUTRIGGER BEYOND 58, TIE -DOWN STRAP ti r3 EXISTING GRADE 6 F ui s 0 TYPICAL GROUND ANCHOR DETAIL SCALE: -NTS- F.T. wi NpTE IF SITE CONDITIONS/BUILDING CONSTRUCTION DICTATE ANY STATE OF FLORIDA APPROVED TIE -DOWN METHOD MAY BE USED IN LIEU OF THE DETAIL SHOWN. SM- CONTRACTOR TO FIELD VERIFY ALL COLUMN LOCATIONS TO INSURE CORRECT PLACEMENT OF SUPPORT PIERS. FOUNDATION PLAN SCALE: 1/4" — F-0" V-6" Y 1CX18"x3/4" ABS PAD (MINUTE MAN PRODUCT OR AN APPROVED EQUAL) FRAME DE —DOWN STRAP TO WRAP AROUND I —BEAM I -BEAM LCROSS MEMBER BEYOND 4. PIER TYPE A (TYP) TYP. GROUND ANCHOR ----------------- F.T. F.T. v v T.T. F.T. Lri LJ F.T. I I F.T. ---- F.T.------F.T-------F.TJI l'-6" i. 1'-6" P.T. 2x8 SHIMS 2 - Vx8"xl6" CAP BLOCK (3) 16"X18" ABS PADS 2 - 8"x8"x16" BLOCK NOTE: MAXIMUM OF (2) LAYERS 1 -6" I, 2'-8" I OF WOOD MAY BE USED. 3'-0" (3) 16"x18"x3/4" ABS PADS STACKED (MINUTE MAN PRODUCT OR AN APPROVED NOTE: EACH ADDITIONAL COURSE OF BLOCK EQUAL) MUST BE SET PERPINDICULAR TO THE PREVIOUS ePIER HBII COURSE SCALE: 114" = F-W SIDE WALL PERIMETER RAIL FRAME I-F-AM PIER TYPE B (TYP) TYPICAL STEEL RE -DOWN STRAP EDASRNG GRADE NOTE CRIMP STRAP OIH I z A LISTED STRAP CRIMP IXt J-H00K WRAPPED AROUND I -BEAM v TYP. GROUND ANCHOR FOUNDATION NOTES: MATERIAL SPECIFICATIONS: SOIL & SITE PREPARATION: 1. FOUNDATION DESIGN IS BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF 2000 PSF. ANY SOIL CONDITIONS THAT MAY DIFFER FROM THIS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT, 2. FOUNDATIONS SHALL BE BUILT ON UNDISTURBED SOIL OR PROPERLY COMPACT FILL MATERIAL. COMPACTED SOILS SHALL BE TESTED TO A MINIMUM OF 95 PROCTOR IN ACCORDANCE WITH ASTM D 1557. 3. EXCAVATIONS FOR FOUNDATIONS SHALL BE BACKFH,LED WITH SOIL WHICH IS FREE OF ORGANIC MATERIAL, CONSTRUCTION DEBRIS, AND LARGE ROCKS, 4. LESSEE/END USER IS RESPONSIBLE FOR INSURING THAT SITE/SOIL CONDITIONS MEET OR EXCEED THE REQUIREMENTS SHOWN. BASE PAD: 1. PIER FOOTING TYPE "A" SHALL BE 16"X18" ABS PAD OR 16"X16"X4", 2500 PSI CONCRETE PAD. PIER FOOTING TYPE "B" SHALL BE (3)16"X18" ABS PADS STACKED. 2. CONCRETE IN FOOTINGS SHALL HAVE A SPECIFIED COMPRESSIVE STRENGTH OF NO LESS THAN 2500 PSI AT 28 DAYS. MASONRY UNIT: 1. PIERS SHALL BE CONSTRUCTED WITH NOMINAL 8"X16"X4" CONCRETE MASONRY UNITS CONFORMING TO ASTM C-90. WOOD & SHIM MATERIAL: 1. ALL WOOD BLOCKING AND SHIMS SHALL BE CEDAR OR PRESSURE TREATED. GROUND ANCHORS: 1. GROUND ANCHORS SHALL HAVE 4725# MIN. ULTIMATE CAPACITY & SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS. TIE -DOWN STRAPS: 1. THE TIE -DOWN STRAPS SHALL BE I+ X 0.35" GALVANIZED STEEL QQS-781-H TYPE 1 FINISH-B, GRADE-1. TIE -DOWN STRAPS AND CONNECTING HARDWARE SHALL HAVE 4725# MIN. ULTIMATE CAPACITY. INSTALLATION SPECIFICATIONS: SOIL & SITE PREPARATION: 1. WHERE WATER IMPACTS THE GROUND FROM A ROOF VALLEY, DOWN SPOUT, SCUPPER, OR OTHER RAINWATER COLLECTION OR DIVERSION DEVICE, PROVISIONS SHALL BE MADE TO PREVENT SOIL EROSION AND DIRECT THE WATER AWAY FROM THE FOUNDATION. 2. FINISH GRADE SHALL BE SLOPED AWAY FROM THE FOUNDATION FOR DRAINAGE. THE AREA UNDER FOOTINGS, FOUNDATIONS, AND CONCRETE SLABS ON GRADE SHALL HAVE NO VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIAL REMOVED PRIOR TO THEIR CONSTRUCTION. FILL MATERIAL SHALL BE FREE OF VEGETATION AND FOREIGN MATERIAL. MASONRY UNIT: 1. LONG DIMENSION OF ALL PIERS MAY BE INSTALLED PERPENDICULAR OR PARALLEL TO THE FRAME. MAXIMUM OF (4) COURSES, (32" HIGH) UNLESS OTHERWISE NOTED. 2. CONCRETE MASONRY UNITS SHALL CONFORM TO THE ASTM C 90 STANDARDS. 3. CONSTRUCTION OF DRY -STACKED, SURFACE BONDED MASONRY WALLS WHEN SPECIFIED, INCLUDING STACKING AND LEVELING OF ALL UNITS, MIXING AND THE APPLICATION OF MORTAR, CURING AND PROTECTION SHALL COMPLY WITH ASTM C 946. TIE -DOWN STRAPS: I. THE FIRST TIE -DOWN STRAP FROM THE ENDWALL SHALL NOT EXCEED 2'-6", UNLESS OTHERWISE SHOWN. 2. REFER TO ANCHOR & STRAPPING SCHEDULE FOR MINIMUM NUMBER OF GROUND ANCHORS. " NOTICE " THESE DOCUMENTS WILL NO LONGER BE VALID 21 DAYS AFTER THE DATE SIGNED VALID THRU : JULY 14TH, 2020 Julio Orbegoso N.. W769 * *= 2020.06.23 0' STATE OF : 4(/�� I I .;�ORIDP,.: °,� 16:1 1:45 -04 00 :,gSSA EN ONAL I�" THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIO ORBEGOSO, P.E. ON THE DATE AND/OR TIME STAMP SHOWN USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES MUST BE VERIFIED ON ANY ELECTRONIC COPIES. REVISION DATE: CONSULTING ENGINEER JULIO ORBEGOSO 202 DORIS DR. LAKELAND, FL 33813 PE LICENSE #38769 L O IL LU 1 D O D CU^) v / x U) J M J 0 2 DATE: 05-20-2019 DRAWN: R.L.G. JOB #: CPX-114722 eSECTION TIE DOWN, SIDEWALL (TYP.) SCALE: 114" — V-0" eD SECTION TIE DOWN, MATELINE (TYP.) SCALE: 3/4" = 1'-0" OAR liIOBAR AA7. na CL Ul