HomeMy WebLinkAboutMANJCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Load Short Form Jun 15, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS036-230A** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 10259480 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.7 Sensible cooling Btuh24220 Heating output Btuh22895 Latent cooling Btuh10380 Temperature rise °F18 Total cooling Btuh34600 Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.052 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.77 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bed 4 161 1909 1361 99 68 Bed 3 154 1404 1127 73 56 Laundry 46 307 921 16 46 Bed 2 154 2740 1460 142 73 Bath 82 1764 663 91 33 M Bath 130 2486 1482 129 74 WIC 65 1051 418 54 21 Clst 18 0 0 0 0 M Hall 47 0 0 0 0 Master Bedroom 293 4217 2614 218 131 Foyer 74 721 378 37 19 Dining Rm 182 2510 1961 130 98 Kitchen 193 420 3481 22 174 Pantry 6 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 2 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N Hall 63 0 0 0 0 Living Room 378 2745 7176 142 359 House d 2045 22275 23040 1153 1153 Other equip loads 1847 981 Equip. @ 0.95 RSM 22916 Latent cooling 7301 TOTALS 2045 24122 30217 1153 1153 2020-Jun-15 13:47:48 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Building Analysis Jun 15, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 17.141252.7Walls 6.916699.1Glazing 0.61523.7Doors 8.420201.0Ceilings 20.048332.42.4Floors 12.630282.1Infiltration 26.76448Ducts 00Piping 00Humidification 7.71847Ventilation0Adjustments 100.024122Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 10.424901.6Walls 16.2390121.3Glazing 0.61533.7Doors 12.429811.5Ceilings 000Floors 3.38040.6Infiltration 30.07211Ducts 4.1981Ventilation 22.95500Internal gains 00Blower 0Adjustments 100.024021Total Latent Cooling Load = 7301 Btuh Overall U-value = 0.075 Btuh/ft²-°F Data entries checked. 2020-Jun-15 13:47:48 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Component Constructions Jun 15, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block R-9 Wall: Blk Wall, Stucco Ext, 8" Thk, R-9 Foam Fill, 1/2" DW 9922.589.00.089385n 6341.65 3891.656072.589.00.089236e 3711.655802.589.00.089225s 5811.659092.589.00.089353w 19751.6530882.589.00.0891199all Partitions Frm Wall, 1/2" DW Ext, R-11 Cav Ins, 1/2" DW Int Fnsh, 2"x4" Wood Frm, 16" OC STUD 5151.4610372.9411.00.101353 Windows Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 1097.021408.9900.31016n 4289.154218.9900.31047s 32220.61408.9900.31016w 85911.07018.9900.31078all Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 50522.02008.7000.30023e Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 7.6 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 2119.172008.7000.30023e Impact: Impact; NFRC rated (SHGC=0.26); foreground = green grass (0.23); 1 ft overhang (6.6 ft window ht, 1 ft sep.); 6.8 ft head ht 190532.15689.5700.33059w Doors Door, Mtl Fbrgl Type 783.73773.697.00.12721n 753.73743.697.00.12720e 1533.731523.697.00.12741all Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 5/8" DW 2045 29811.4620200.9930.00.034 Floors 2020-Jun-15 13:47:48 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 2 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N On Grade Depth, Tile Flr Fnsh 00483328.700.989169 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Project Summary Jun 15, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor:TBD S Brocksmith Rd, Ft Pierce, FL 34945 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh15826 Structure Btuh15829 Ducts Btuh6448 Ducts Btuh7211Central vent (58 cfm) 1847 Btuh Central vent (58 cfm) Btuh981 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh24122 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh22916 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2836 Ducts Btuh2226Central vent (58 cfm) Btuh2240 CoolingHeating Outside air20452045Area (ft²) Equipment latent load Btuh7301 1781517815Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh30217 Equiv. AVF (cfm) 4895 Req. total capacity at 0.70 SHR ton2.7 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACXS036-230A**AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 10259480Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.7 Sensible cooling Btuh24220Heating output Btuh22895 Latent cooling Btuh10380 Temperature rise °F18 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.052 Air flow factor cfm/Btuh0.050Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.77 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Bed 4 2 Exposed wall 168.5 ft 11.5 ft 3 Room height 8.7 dft 8.0 heat/coolft 4 Room dimensions ft11.5x14.0 5 Room area 2045.4 ft²161.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 422 385 992 634 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 16 0 140 109 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 21 21 77 78 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 302 236 607 389 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 23 0 200 505 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 23 23 200 211 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 20 20 74 75 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 272 225 580 371 92 76 197 126 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 47 40 421 428 16 13 140 143 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 428 353 909 581 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 16 0 140 322 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 59 0 568 1905 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 353 353 1037 515 112 112 329 163 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 2045 2045 2020 2981 161 161 159 235 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2045 169 4833 0 161 12 330 0 6 c) AED excursion 421 -42 Envelope loss/gain 12798 9525 1155 625 12 a) Infiltration 3028 804 196 52 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 4350 250 Subtotal (lines 6 to 13)15826 15829 1351 927 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 6 8 14 Subtotal 15826 15829 1356 935 15 Duct loads 41%46%6448 7211 41%46%553 426 Total room load 22275 23040 1909 1361 Air required (cfm)Air required (cfm)1153 1153 99 68 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 2... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 3 Laundry 2 Exposed wall 11.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft11.0x14.0 ft46.3x1.0 5 Room area 154.0 ft²46.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 88 72 187 119 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 16 13 140 143 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 56 56 165 82 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 154 154 152 224 46 46 46 67 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 154 11 315 0 46 0 0 0 6 c) AED excursion -34 -28 Envelope loss/gain 794 452 210 121 12 a) Infiltration 187 50 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 500 Subtotal (lines 6 to 13)982 752 210 621 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 16 22 8 12 14 Subtotal 997 774 218 632 15 Duct loads 41%46%406 353 41%46%89 288 Total room load 1404 1127 307 921 Air required (cfm)Air required (cfm)73 56 16 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 3... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 25.5 ft 17.3 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft153.5x1.0 ft81.9x1.0 5 Room area 153.5 ft²81.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 68 47 121 77 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 21 21 77 78 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 92 76 197 126 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 16 13 140 143 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 112 112 289 185 70 70 180 115 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 154 154 152 224 82 82 81 119 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 154 26 731 0 82 17 495 0 6 c) AED excursion -45 -20 Envelope loss/gain 1509 632 954 370 12 a) Infiltration 434 115 294 78 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1943 997 1248 448 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 4 6 5 7 14 Subtotal 1947 1003 1253 455 15 Duct loads 41%46%793 457 41%46%511 207 Total room load 2740 1460 1764 663 Air required (cfm)Air required (cfm)142 73 91 33 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 4... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name M Bath WIC 2 Exposed wall 23.0 ft 10.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft10.0x13.0 ft10.0x6.5 5 Room area 130.0 ft²65.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 80 80 206 132 80 80 206 132 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 104 88 228 146 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 16 0 140 322 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 130 130 128 189 65 65 64 95 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 130 23 660 0 65 10 287 0 6 c) AED excursion 108 -12 Envelope loss/gain 1362 896 557 215 12 a) Infiltration 392 104 170 45 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1754 1000 727 260 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 13 18 19 27 14 Subtotal 1766 1018 747 287 15 Duct loads 41%46%720 464 41%46%304 131 Total room load 2486 1482 1051 418 Air required (cfm)Air required (cfm)129 74 54 21 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 5... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Clst M Hall 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x3.0 ft47.0x1.0 5 Room area 18.0 ft²47.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 18 18 18 26 47 47 46 68 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 18 0 0 0 47 0 0 0 6 c) AED excursion -1 -3 Envelope loss/gain 18 25 46 66 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)18 25 46 66 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -18 -25 -46 -66 14 Subtotal 0 0 0 0 15 Duct loads 41%46%0 0 41%46%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 6... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bedroom Foyer 2 Exposed wall 35.5 ft 5.5 ft 3 Room height 8.6 heat/coolft 10.0 heat/coolft 4 Room dimensions ft22.5x13.0 ft13.5x5.5 5 Room area 292.5 ft²74.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 194 178 458 293 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 16 0 140 109 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 112 89 229 146 55 35 90 58 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 23 23 200 211 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 20 20 74 75 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 293 293 289 426 74 74 73 108 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 293 36 1018 0 74 6 158 0 6 c) AED excursion -81 -12 Envelope loss/gain 2334 1105 395 229 12 a) Infiltration 650 172 117 31 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)2984 1778 512 260 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 13 18 0 0 14 Subtotal 2997 1796 512 260 15 Duct loads 41%46%1221 818 41%46%209 118 Total room load 4217 2614 721 378 Air required (cfm)Air required (cfm)218 131 37 19 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 7... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Dining Rm Kitchen 2 Exposed wall 13.5 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft13.5x13.5 ft11.0x17.5 5 Room area 182.3 ft²192.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 135 112 289 185 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 23 0 200 505 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 150 150 441 219 35 35 103 51 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 182 182 180 266 193 193 190 281 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 182 14 387 0 193 0 0 0 6 c) AED excursion 97 -108 Envelope loss/gain 1496 1271 293 223 12 a) Infiltration 287 76 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)1784 1347 293 2383 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 5 8 14 Subtotal 1784 1347 298 2391 15 Duct loads 41%46%727 614 41%46%122 1089 Total room load 2510 1961 420 3481 Air required (cfm)Air required (cfm)130 98 22 174 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 8... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry Hall 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.5x2.5 ft18.0x3.5 5 Room area 6.3 ft²63.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 6 6 6 9 63 63 62 92 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 6 0 0 0 63 0 0 0 6 c) AED excursion 0 -4 Envelope loss/gain 6 9 62 88 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)6 9 62 88 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -6 -9 -62 -88 14 Subtotal 0 0 0 0 15 Duct loads 41%46%0 0 41%46%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-15 13:47:48Right-Suite® Universal 2019 19.0.19 RSU27054 Page 9... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Jun 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Living Room 2 Exposed wall 15.8 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft18.0x21.0 5 Room area 378.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Block R-9 Wall 0.089 n 2.58 1.65 0 0 0 0 .G Impact 0.310 n 8.99 7.02 0 0 0 0 .D Door, Mtl Fbrgl Type 0.127 n 3.69 3.73 0 0 0 0 .W Block R-9 Wall 0.089 e 2.58 1.65 0 0 0 0 11 G Impact 0.300 e 8.70 21.99 0 0 0 0 G Impact 0.300 e 8.70 9.17 0 0 0 0 D Door, Mtl Fbrgl Type 0.127 e 3.69 3.73 0 0 0 0 W Block R-9 Wall 0.089 s 2.58 1.65 0 0 0 0 G Impact 0.310 s 8.99 9.15 0 0 0 0 W Block R-9 Wall 0.089 w 2.58 1.65 142 82 212 136 G Impact 0.310 w 8.99 20.62 0 0 0 0 G Impact 0.330 w 9.57 32.07 59 0 568 1905 P Frm Wall, 1/2" DW Ex 0.101 -2.94 1.46 0 0 0 0 C Attic, Shngl Roof, R 0.034 -0.99 1.46 378 378 373 551 F On Grade Depth, Tile 0.989 -28.68 0.00 378 16 452 0 6 c) AED excursion 608 Envelope loss/gain 1606 3199 12 a) Infiltration 302 80 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 3 690 Appliances/other 900 Subtotal (lines 6 to 13)1907 4869 Less external load 0 0 Less transfer 0 0 Redistribution 43 61 14 Subtotal 1950 4930 15 Duct loads 41%46%795 2246 Total room load 2745 7176 Air required (cfm)142 359 2020-Jun-15 13:47:49 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Duct System Summary Jun 15, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.448 / 0.252 in H2O in H2O0.448 / 0.252 Lowest friction rate in/100ft0.129in/100ft0.129 Actual air flow cfm1153cfm1153 Total effective length (TEL) ft544 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st4300.033.3VlFx0x07.00.134401101764hBath st4300.033.1VlFx0x08.00.134881702740hBed 2 st4300.035.3VlFx0x06.00.13468871404hBed 3 st2200.013.1VlFx0x07.00.210821191909hBed 4 st1200.032.1VlFx0x07.00.1931181562510hDining Rm st1200.030.9VlFx0x04.00.1942345721hFoyer st1200.026.4VlFx0x06.00.198105131740cKitchen st1200.026.2VlFx0x06.00.198105131740cKitchen-A st2200.013.5VlFx0x05.00.2105519921cLaundry st4300.039.4VlFx0x09.00.132216853588cLiving Room st3300.047.7VlFx0x09.00.129216853588cLiving Room-A st3300.048.1VlFx0x08.00.129891542486hM Bath st1200.036.7VlFx0x07.00.189781312109hMaster Bedroom st3300.046.3VlFx0x07.00.129781312109hMaster Bedroom-A st3300.040.0VlFx0x05.00.13225651051hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 436 408 0.129 555 12.0 0x0 VinlFlx st1 st1 Peak AVF 794 836 0.129 599 16.0 0x0 VinlFlx st4 Peak AVF 452 411 0.132 576 12.0 0x0 VinlFlx st2 st2 Peak AVF 590 548 0.132 552 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2020-Jun-15 13:47:49 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 2 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 3270 182 196.2 0.129 600 10.0 x0 0 VlFx rt1 rb1 0x 6810 965 165.6 0.152 546 18.0 x0 0 VlFx rt1 rb4 0x 1700 88 169.8 0.149 488 8.0 x0 0 VlFx rt1 rb3 0x 870 68 163.9 0.154 444 6.0 x0 0 VlFx rt1 rb2 0x 1190 82 164.3 0.154 444 7.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1384 1384 0.129 634 20.0 0x0 VinlFlx 2020-Jun-15 13:47:49 Right-Suite® Universal 2019 19.0.19 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Manual S Compliance Report Jun 15, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh24021Sensible gain:°F90.4Outdoor design DB: °F64.1Entering coil WB:Btuh7301Latent gain:°F77.4Outdoor design WB: Btuh31322Total gain:°F75.0Indoor design DB: cfm1153Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACXS036-230A**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer: cfm1153Actual airflow: % of load101Btuh24220Sensible capacity: % of load142Btuh10380Latent capacity: %70SHR:% of load110Btuh34600Total capacity: Heating Equipment Design Conditions °F68.0Entering coil DB:Btuh24122Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1153Actual airflow: °F50Temp. rise:% of load95kW6.7Output capacity: Meets all requirements of ACCA Manual S. Job #: 751 Performed by Vicki Lynne Nisa for: Santana Autry Residence TBD S Brocksmith Rd Ft Pierce, FL 34945 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 244 Page 1 Right-Suite® Universal 2019 19.0.19 RSU27054 2020-Jun-15 13:48:38 ...cksmith Rd Santana Autry GBI.rup N Level 1 Garage Bed 4 Bed 3 Laundry Bed 2 Bath M Bath WIC Clst M Hall Master Bedroom FoyerDining Rm Kitchen Pantry Hall Living Room 12 x 12 216 cfm 10 x 6 65 cfm 8 x 8 105 cfm 6 x 6 55 cfm 12 x 12 119 cfm 12 x 12 87 cfm 12 x 12 170 cfm 24 x 18 965 cfm 12 x 8 119 cfm 10 x 6 87 cfm 12 x 8 170 cfm 8 x 4 45 cfm 14 x 14 327 cfm 10 x 10 131 cfm 10 x 10 131 cfm 8 x 8 110 cfm 10 x 10 154 cfm 8 x 8 105 cfm 12 x 12 216 cfm 12 x 8 156 cfm 20 " 7 " 6 " 8 " 18 " 10 " 7 "5 " 9 "6 " 7 " 8 " 14 " 16 " 7 "4 " 6 "6 " 7 " 12 " 9 " 12 " 8 " 5 " 7 "