HomeMy WebLinkAboutBuilding permit detials , REPORTSummary of repairs performed at KITTERMAN WOODS APARTMENTS,6600 WOODS
ISLAND CIRCLE, PORT ST LUCIE.
On or about 05/28/2020 the property experienced significant damage consistent with a power
surge from a lightning strike. The main fire panel that supervises the entire property fire alarm
system, devices on the data loop and individual building fire panels were damaged.
- Clubhouse — main FACP MS9200UDLS was replaced, programmed, and tested.
- Monitor modules (MMF-301) replaced on buildings 2, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14,
15, 16 & 17. 2 modules per building — 30 modules total.
- 120vac surge suppressors (DTK120HW) replaced on buildings 4, 5, 6, 7, 9, 10,11,15 &
16. 9 120vac surge total.
- Data loop surge suppressors (DTK4LVLP-LV) replaced on buildings 4, 5, 7, 8, 11, 14,
15, 16, 17 and in the junction boxes leaving the Clubhouse (x2). I 1 low voltage surges
total.
- Isolation modules (I300) replaced in both junction boxes leaving the Clubhouse. 2 ISO
mods total.
- Replaced, programmed and tested Firelite MS 1 OUD board only building 14.
- Replaced, programmed and tested Firelite MS5210UD board only building 4.
- Replaced, programmed and tested Firelite MS5210UD board only building 5.
- Replaced, programmed and tested Firelite MS5210UD board only building 10.
- Replaced, programmed and tested Firelite MS52I OUD board only building 15.
- Replaced, programmed and tested Firelite MS5210UD board only building 16.
- Replaced, programmed and tested Firelite MS5210UD board only building 17.
- Replaced, programmed and tested NACREM accessory board building 16 & 17. 2
expander modules total.
All fire panels, monitor modules, surge suppressors, isolation modules and expander modules
were like for like replacements. No devices were added or deleted from the existing alarm
system.