HomeMy WebLinkAboutMS5210UDDF-51492 • 07/12/04 — Page 1 of 3
GENERALGENERALGENERALGENERALGENERAL
The Fire•Lite MS-5210UD is a 24-volt, ten-zone fire alarm
control panel with built-in communicator and remote-site
Upload/Download capability (requires panel software revi-
sion #MS52103.0 or greater). The integral communicator
transmits event information (alarms, troubles, supervi-
sories, faults, etc.) to a UL listed central station. Select-
able transmission formats allow the MS-5210UD to com-
municate to virtually all central stations.
FEATURESFEATURESFEATURESFEATURESFEATURES
• Ten programmable Initiating Device Circuits (zones).
Each zone may be programmed for:
Two-wire smoke detectors.
N.O. contact devices (pull, heat).
Four-wire smoke detectors.
Waterflow operation (silenceable or nonsilenceable).
Supervisory operation.
Auto-reset supervisory operation.
Remote switch for Reset, Drill, Silence and Acknowl-
edge.
Auto-reset or latching, critical and noncritical process
monitoring.
• Zones programmed for process monitoring require a
contact closure for activation and can be used to monitor:
Temperature (high/low temp).
Water level.
Refrigeration.
Gas detection.
Tamper (non-fire).
Loss of air flow.
Open/Close.
• Two built-in, Class B (Style Y) Notification Appliance
Circuits (NACs) — expandable to four.
• Notification Appliance Circuits may be programmed:
Silenceable.
Non-Silenceable (a strobe circuit can keep flashing
after the panel is silenced).
Auto-Silence (program 5 to 30 minutes).
Silence Inhibit (60 seconds).
Coding (March Time, Temporal, California).
• 3.0 Amps of Notification Appliance power, expandable to
6.0 amps (meets the critical power requirements for ADA
and UL-1971 devices).
• Two built-in, fully programmable Form-A relays - expand-
able to four with two Form-C relays.
• Dual-line rotary- or Touch-Tone®-dial DACT interfaces to
public telephone network (leased phone lines are not
required).
• 24-Volt operation.
MEA
122-96-E
• Built-in voltmeter measures:
Zone voltage.
Primary AC line voltage.
Battery voltage.
Notification Appliance Circuit(s) voltage.
Resettable 24-volt power.
• Surface Mount Technology (SMT).
• Fully programmable via built-in keypad (no costly exter-
nal programmers necessary).
• Complies with NFPA 72 (Local, Central Station and
Remote Station [DACT only - not polarity reversal] Fire
Alarm Systems).
• Reporting Formats include Ademco Contact ID and 14
others.
• Integral battery charger for up to 60 hours of standby
power.
• Fuseless, power-limited technology meets new UL power-
limiting requirements, effective May 1, 1995.
• Programmable Alarm Presignal Timer, Alarm Verifica-
tion Timer and Optional Trouble Reminder.
• Single-person walk test with 256-event walk-test buffer.
• Fire drill function.
• Zone disable capability (software).
• 256-Event history buffer with time and date stamp, stored
in permanent memory.
• Accurate real-time clock/calendar.
7165-0075:177
CaliforniaState FireMarshal
FCC
1W6USA-
20723-AL-E
INDUSTRY
CANADA
21325785A
MSMSMSMSMS -5210UD(C/E)-5210UD(C/E)-5210UD(C/E)-5210UD(C/E)-5210UD(C/E)
Fire Alarm Control Panel with built-in DACTFire Alarm Control Panel with built-in DACTFire Alarm Control Panel with built-in DACTFire Alarm Control Panel with built-in DACTFire Alarm Control Panel with built-in DACT
and remote-site Upload/Download capabilityand remote-site Upload/Download capabilityand remote-site Upload/Download capabilityand remote-site Upload/Download capabilityand remote-site Upload/Download capability
DF-51492 • A3-400July 12, 2004
Section: Control/Communicators
MS-5210UD ms5210ud.jpgS5624
This document is not intended to be used for installation purposes. We try to keep
our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to change
without notice. For more information, contact Fire•Lite Alarms, One Fire-Lite Place,
Northford, Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105,
Website: www.firelite.com Made in the U.S.A.
Page 2 of 3 — DF-51492 • 07/12/04
REMOTE SITE UPLOAD/DOWNLOADREMOTE SITE UPLOAD/DOWNLOADREMOTE SITE UPLOAD/DOWNLOADREMOTE SITE UPLOAD/DOWNLOADREMOTE SITE UPLOAD/DOWNLOAD
The MS-5210UD may be downloaded or uploaded (requires
panel software revision #MS52103.0 or greater) without
compromising the system fire protection at the protected
premises.
• Download system programming.
• Upload key system information:
Current system status, history + walk test files.
Zone, AC line, NAC1, 2, 3 and 4, resettable power
and battery voltages.
System programming.
• Upload or download within one minute without affecting
normal fire panel functions.
• Multiple security techniques.
• Requires PK-5210UD programming kit, which works with
most Hayes-compatible modems (consult factory for list-
ing).
SPECIFICATIONSSPECIFICATIONSSPECIFICATIONSSPECIFICATIONSSPECIFICATIONS
Single PC board design using Surface Mount Technology
(SMT). Two modular telephone jacks for connection to
RJ31X/Modules.
AC PowerAC PowerAC PowerAC PowerAC Power
• 120 VAC, 50/60 Hz, 2.3 amps.
• 230 VAC, 50 Hz, 1.2 amps (“E” suffix).
• Wire size: minimum 14 AWG with 600-volt insulation.
• Built-in brownout circuitry.
• Built-in voltmeter.
CommunicatorCommunicatorCommunicatorCommunicatorCommunicator
• One line-active indicator for each of two phone lines.
• “Kiss-Off” signal LED.
• Dual “low telephone voltage detect” circuitry.
• Programmable event codes per each format.
• Up to 100 transmitted events/messages.
• Selectable/deselectable transmissions of 100 events.
Communication FormatsCommunication FormatsCommunication FormatsCommunication FormatsCommunication Formats
Express and Ademco Contact ID formats allow complete
transaction to be communicated in under five seconds.
• Ademco Contact ID.
• 20 PPS, 3+1 standard and expanded.
• 20 PPS, 4+1 standard and expanded.
• 20 PPS, 4+2 standard and expanded.
• 4+1 and 4+2 Ademco Express.
INITIATING DEVICE CIRCUITS (ZONES)INITIATING DEVICE CIRCUITS (ZONES)INITIATING DEVICE CIRCUITS (ZONES)INITIATING DEVICE CIRCUITS (ZONES)INITIATING DEVICE CIRCUITS (ZONES)
The MS-5210UD includes ten programmable Class B Initi-
ating Device Circuits (zones). Use the CAC-10F Class A
converter module to convert all Class B IDC’s/NAC’s to
Class A.
Each zone may support two-wire smoke detectors. Pro-
gramming options include:
• Normally Open Contact devices (pull, heat).
• Four-wire smoke detectors.
• Waterflow (silenceable/non-silenceable) operation.
• Supervisory (standard/auto-reset) operation.
• Remote switch for Reset, Drill, Silence, Acknowledge.
• Critical and Noncritical Process Monitoring (standard/
auto-reset).
All circuits are power-limited and fully supervised. They
allow up to 100 ohms of line resistance and allow for use of
12 to 18 AWG wire.
NOTIFICATION APPLIANCE CIRCUITSNOTIFICATION APPLIANCE CIRCUITSNOTIFICATION APPLIANCE CIRCUITSNOTIFICATION APPLIANCE CIRCUITSNOTIFICATION APPLIANCE CIRCUITS
• Two Style Y (Class B) @ 3.0 amps each. Use the CAC-
10F Class A Converter Module to convert all Class B
NAC’s and IDC’s to Class A.
• Option module adds two Style Z (Class A) NACs @ 1.5
amps each.
• All circuits are fully power-limited and meet the new UL
power-limiting requirements effective May 1, 1995, using
fuseless technology.
AUXILIARY OUTPUTSAUXILIARY OUTPUTSAUXILIARY OUTPUTSAUXILIARY OUTPUTSAUXILIARY OUTPUTS
• Resettable four-wire smoke detector power @ 500 mA.
• Non-resettable power @ 500 mA.
• Two fully programmable Form-A/B relays.
• Option module adds two fully programmable Form-C
relays.
COMPATIBLE DEVICES, EIA-485 PORTCOMPATIBLE DEVICES, EIA-485 PORTCOMPATIBLE DEVICES, EIA-485 PORTCOMPATIBLE DEVICES, EIA-485 PORTCOMPATIBLE DEVICES, EIA-485 PORT
LED-10IM: EIA-485 Interface Module. Provides MS-
5210UD with EIA-485 output, capable of supporting up to
32 compatible EIA-485 devices (listed below).
LED-10 Series: LED-type fire annunciators capable of
displaying Alarm (red) and Trouble (yellow) LEDs for all ten
Initiating Device Circuits (IDCs). NOTE: For Canadian
Supervisory Service, use LED-10LS2 only.
AFM-16AF: LED-type fire annunciator capable of pro-
viding up to 16 zones of Alarm (red) annunciation and com-
mon system trouble LED. Mounts to 4-gang electrical box
ONLY.
LDM Series: Lamp Driver Module series for use with
custom graphic annunciators.
ACM-8RF: Remote Form-C relay module. Provides eight
mappable Form-C relays driven by EIA-485 for contact-by-
zone capability (two minimum required for contact-by-zone).
Each requires ABS-8RF for mounting.
NOTE: For more detailed information on Compatible EIA-485
Devices for use with the MS-5210UD, please refer to the LED-10,
AFM/AFM-X, LDM or ACM-8RF data sheets, document numbers
DF-51500, DF-51465, DF-51384, and DF-51555 respectively.
CABINET SPECIFICATIONSCABINET SPECIFICATIONSCABINET SPECIFICATIONSCABINET SPECIFICATIONSCABINET SPECIFICATIONS
The cabinet is red with a dark blue overlay. Knockouts on
the top, sides, and back provide ease of wire entry. The
cabinet can be surface or semi-flush mounted and is com-
pact in design.
Dimensions:
Door:17.11" high x 14.71" wide
(43.46 cm high x 37.36 cm wide).
Backbox:16.90" high x 14.50" wide x 4.50" deep
(42.93 cm high x 36.83 cm wide x 11.43 cm
deep).
Trim Ring:Part # TR-4-R, 20.020" high x 17.620" wide
(50.85 cm high x 44.75 cm wide).
• Electronics and operational controls fully enclosed in a
lockable cabinet capable of housing up to 12 AH batter-
ies.
• Optional LED-10 Series Remote Annunciators operate
off serial two-wire EIA-485 interface.
• Optional contact-by-zone module and printer interface
for on- or off-line printing.
• 230 VAC, 50 Hz international version available.
DF-51492 • 07/12/04 — Page 3 of 3
PRODUCT LINE INFORMATIONPRODUCT LINE INFORMATIONPRODUCT LINE INFORMATIONPRODUCT LINE INFORMATIONPRODUCT LINE INFORMATION
MS-5210UD Ten-zone, 24-volt Fire Alarm Control Com-
municator (includes backbox, transformer,
technical manual, and a frame & post op-
erating instruction sheet).
MS-5210UDC Same as above with ULC listing and DP-4-
R dress panel included.
MS-5210UDE Same as MS-5210UD with 230 VAC, 50 Hz
transformer (UL listed).
XRM-24 120 VAC, 100 VA transformer. Expands
NAC power from 3.0 to 6.0 amps and sys-
tem power from 3.6 amps to 6.6 amps.
NAC-REM Notification Appliance (Signal) Circuit, Re-
lay Expander Module. Adds two (Class A)
NACs and two Form-C relays.
CAC-10F Class A Converter Module. Converts all
Class B Initiating Device Circuits (zones)
and standard Notification Appliance Circuits
to Class A.
PRT-24 Printer Interface Module. Provides an EIA-
232 printer output. Includes cable, DB9F and
DB25 adapter.
PK-CD Contains programming software for Windows-
based PC computer.
DP-4-R Internal Dress Panel (included when order-
ing MS-5210UDC).
MCBL-7 DACT phone cord, 7 feet long (two required).
BB-17F UL listed battery backbox. Required for bat-
teries over 12 AH.
ABS-8RF Metal enclosure for mounting each ACM-8RF
module.
TR-4-R Trim ring.
BAT-1270 Battery, 12 volt, 7.0 AH (two required).
BAT-12120 Battery, 12 volt, 12.0 AH (two required).
BAT-12180 Battery, 12 volt, 18.0 AH (two required, re-
quires BB-17F backbox).
5210UDRB Replacement motherboard.
KEY:
(1)With 685-8 Line Card with Rev 4.4d software.
(2)With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software.
(3)Rev. 4.0 software.
(4)FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a memory card with Rev 3.8 software.
(5)Model 6500 with Rev 600 software.
(6)Model 6000 with Rev 204 software.
(7)With Rev B control card at Rev 1.4 software and Rev C line card at Rev 1.5 software.
(8)Model 2 only.
(9)Version 1.62 software.
ULULULULUL LISTED RECEIVERS LISTED RECEIVERS LISTED RECEIVERS LISTED RECEIVERS LISTED RECEIVERS
COMPATIBLE WITH THE MS-5210UDCOMPATIBLE WITH THE MS-5210UDCOMPATIBLE WITH THE MS-5210UDCOMPATIBLE WITH THE MS-5210UDCOMPATIBLE WITH THE MS-5210UD
Format #
(Addresses 16 & 42)
Ademco
685 (1)
Silent
Knight
9000
ITI
CS-4000
(3)
FBI
CP220FB
Osborne
Hoffman
Models
1 & 2
Radionics
6000/6500
(5)
Sescoa
3000R (7)
SurGuard
MLR-2 (9)
0 4+1 Ademco Express
1 4+2 Ademco Express
4 (8)
2 3+1/Standard/1800/2300
(2) (4) (5,6)
3 3+1/Expanded/1800/2300
(2) (4)
4 3+1/Standard/1900/1400
(2) (4)
5 3+1/Expanded/1900/1400
(2) (4)
6 4+1/Standard/1800/2300
(2) (4) (5)
7 4+1/Expanded/1800/2300
(2) (4)
8 4+1/Standard/1900/1400
(2) (4)
9 4+1/Expanded/1900/1400
(2) (4)
A 4+2/Standard/1800/2300
(2) (4) (5)
B 4+2/Expanded/1800/2300
(2) (4)
C 4+2/Standard/1900/1400
(2) (4)
D 4+2/Expanded/1900/1400
(2) (4)
E Ademco Contact ID