Intelligent Addressable FACP
with Built-In Communicator
Addressable Fire Alarm Control Panel
DF-60601:A1 • A1-60
52422cov.jpgGeneral
The Fire•Lite MS-9200UDLS Rev 3 with Version 5.0 firmware
is a combination FACP (Fire Alarm Control Panel) and DACT
(Digital Alarm Communicator/Transmitter) all on one circuit
board. This compact intelligent addressable control panel has
an extensive list of powerful features.
While the MS-9200UDLS Rev 3 may be used with an SLC
configured in the CLIP (Classic Loop Interface Protocol) mode,
it can also operate in LiteSpeed™ mode—Fire•Lite’s latest
polling technology—for a quicker device response time.
LiteSpeed’s patented technology polls 10 devices at a time.
This improvement allows a fully-loaded panel with up to 198
devices to report an incident and activate the notification cir-
cuits in under 10 seconds. With Litespeed polling, devices can
be wired on standard twisted, unshielded wire up to a distance
of 10,000 feet.
The MS-9200UDLS Rev 3’s quick-remove chassis protects the
electronics during construction. The backbox can be installed
allowing field wiring to be pulled. When construction is com-
pleted, the electronics can be quickly installed with just two
bolts.
New features for Rev 3 with Version 5.0 firmware include
removable terminal blocks, improved transient protection,
additional secondary ANN-BUS, and increased power for the
resettable and remote sync outputs.
Available accessories include ANN-BUS devices as well as
ACS LED, graphic and LCD annunciators, and reverse polar-
ity/city box transmitter.
The integral DACT transmits system status (alarms, superviso-
ries, troubles, AC loss, etc.) to a Central Station via the public
switched telephone network. It also allows remote and local
programming of the control panel using the PS-Tools Upload/
Download utility. In addition, the control panel may be pro-
grammed or interrogated off-site via the public switched tele-
phone network. Any personal computer with Windows® XP or
greater, a compatible modem, and PS-Tools—the Fire•Lite
Upload/Download software kit—may serve as a Service Termi-
nal. This allows download of the entire program or upload of
the entire program, history file, walktest data, current status
and system voltages. The panel can also be programmed
through the FACP’s keypad or via a standard PS-2 computer
keyboard, which can be plugged directly into the printed circuit
board. This permits easy typing of address labels and other
programming information.
Version 5.0 firmware supports the following: Primary and Sec-
ondary ANN-bus devices, AD355 (LiteSpeed), USB port, NAC
circuit diagnostics, a new report has been added to the walk-
test that lists untested devices, new device types added: audio
telephone type code for ACC 25/50ZST, Photo Supervisory
and auto-resettable Drill (non-latching).
The FireWatch Series internet monitoring modules IPDACT-2
and IPDACT-2UD permit monitoring of alarm signals over the
Internet saving the monthly cost of two dedicated business
telephone lines. Although not required, the secondary tele-
phone line may be retained providing backup communication
over the public switched telephone line.
NOTE: Unless otherwise specified, the term MS-9200UDLS is
used in this document to refer to both the MS-9200UDLS and the
MS-9200UDLS(E) FACPs (Fire Alarm Control Panels).
Features
• Listed to UL standard 864, 9th edition.
• On-board DACT.
• Remote site or local USB port upload/download, using PS-
Tools.
• Four (4) Style Y (Class B) NAC circuits, which can be con-
verted to four (4) Style Z (Class A) circuits with optional
ZNAC-92 converter module. (Up to 6.0 amps total NAC
power when using optional XRM-24B.)
• Selectable strobe synchronization for System Sensor,
Wheelock, and Gentex devices.
• Remote Acknowledge, Silence, Reset and Drill via address-
able monitor modules or LCD-80F, ANN-80 or Legacy ACS
Annunciators.
• ANN-BUS for connection to following optional modules (cannot
be used if ACS annunciators are used):
–ANN-80(-W) Remote LCD Annunciator
–ANN-I/O LED Driver
–ANN-S/PG Printer Module
–ANN-RLY Relay Module
–ANN-LED Annunciator Module
–ANN-RLED Annunciator Module alarms only
–ROME Relay Option Module Enclosure
•ACS/TERM:
–ACS Annunciators: Up to 32 Legacy ACM Series annun-
ciators (ACM-16AT or ACM-32 series). Cannot be used if
ANN-BUS devices are used.
–Terminal-mode Annunciators: Up to 32 Legacy LCD-80F
remote annunciators.
Page 2 of 6 — DF-60601:A1 • 12/07/2010
• EIA-232 printer/PC interface (variable baud rate) on main
circuit board, for use with optional UL-listed printer PRN-6F.
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight savings
control.
• Detector sensitivity test capability (NFPA 72 compliant).
• History file with 1,000-event capacity.
• Maintenance alert warns when smoke detector dust accu-
mulation is excessive.
• Automatic device type-code verification.
• One person audible or silent walk test with walk-test log and
printout.
• Point trouble identification.
• Waterflow (nonsilenceable) selection per monitor point.
• System alarm verification selection per detector point.
• PAS (Positive Alarm Sequence) and presignal delay per
point (NFPA 72 compliant).
NOTE: Only detectors may participate in PAS.
SLC LOOP:
• SLC can be configured for NFPA Style 4, 6, or 7 operation.
• SLC supports up to 198 addressable devices per loop (99
detectors and 99 monitor, control, or relay modules).
• SLC loop maximum length 10,000 ft. (3,000 m.).
See installation manual for wire tables.
NOTIFICATION APPLIANCE CIRCUITS (NACS):
• Four onboard NACs with additional NAC capability using
output control modules (CMF-300 or CMF-300-6). The four
Class B NACs can be converted to four Class A NACs with
optional ZNAC-92 converter module.
• Silence Inhibit and Auto Silence timer options.
• Continuous, March Time, Temporal or California code for
main circuit board NACs with two-stage capability.
• Selectable strobe synchronization per NAC.
• 2.5 amps maximum per each NAC circuit.
NOTE: Maximum 24VDC system power output is shared among
all NAC circuits and 24VDC special-application auxiliary power
outputs. Total available output is 3.0 amps. Using the optional
XRM-24B transformer increases 24VDC output to 6.0 amps.
PROGRAMMING AND SOFTWARE:
• Autoprogram (learn mode) reduces installation time.
• Custom English labels (per point) may be manually entered
or selected from an internal library file.
• Three Form-C relay outputs (two programmable).
• 99 software zones.
• Continuous fire protection during online programming at the
front panel.
• Program Check automatically catches common errors not
linked to any zone or input point.
•OFFLINE PROGRAMMING: Create the entire program in
your office using a Windows®-based software package
(order programming kit PS-Tools, separately). Upload/
download system programming locally to the MS-
9200UDLS Rev 3 in less than one minute.
• USB upload/download programming with standard Male-A
to Male-B cable.
User Interface
LED INDICATORS
• AC Power (green)
• Fire Alarm (red)
• Supervisory (yellow)
• Alarm Silenced (yellow)
• System Trouble (yellow)
• Maintenance/Presignal (yellow)
• Disabled (yellow)
• Battery Fault (yellow)
• Ground Fault (yellow)
KEYPAD CONTROLS
• Acknowledge/Step
• Alarm Silence
• Drill
• System Reset (lamp test)
• 16-key alpha-numeric pad (similar to telephone keypad)
• 4 cursor keys
•Enter
Product Line Information
MS-9200UDLS: 198-point addressable Fire Alarm Control
Panel, one SLC loop. Includes 80-character LCD display, sin-
gle printed circuit board mounted on chassis, and cabinet. 120
VAC operation.
MS-9200UDLSE: Same as MS-9200UDLS, except with 240
VAC operation.
4XTMF Reverse Polarity Transmitter Module: Provides
supervised output for local energy municipal box transmitter,
alarm, and trouble.
ZNAC-92: Optional converter module which converts four (4)
Style Y (Class B) NAC circuits to four (4) Style Z (Class A) cir-
cuits.
PK-CD Programming software for Windows®-based PC com-
puter (cable not included), available on www.firelite.com.
DP-9692: Optional dress panel for MS-9200UDLS Rev 3.
TR-CE: Optional trim Ring for semi-flush mounting.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
BB-55F: Battery box, houses two 55 AH batteries.
CHG-75: Battery charger for lead-acid batteries with a rating
of 25 to 75 AH.
CHG-120F: Remote battery charging system for lead-acid bat-
teries with a rating of 55 to 120 AH. Requires additional BB-
55F for mounting.
BAT Series: Batteries, see data sheet DF-52397.
XRM-24B(E): Optional transformer. Increases system power
output to 6.0 amps. Use XRM-24BE with MS-9200UDLS Rev
3(E).
PRT/PK-CABLE: Cable printer/personal computer interface
cable; required for printer or for local upload/download pro-
gramming and updating panel firmware.
PRN-6F: UL listed compatible event printer. Uses tractor-fed
paper.
IPDACT-2/2UD, IPDACT Internet Monitoring Module:
Mounts in bottom of enclosure with optional mounting kit (PN
IPBRKT). Connects to primary and secondary DACT tele-
phone output ports for internet communications over customer
provided ethernet internet connection. Requires compatible
Teldat VisorALARM Central Station Receiver. Can use DHCP
or static IP. (See data sheet DF-60407 or DF-52424 for more
information.)
DF-60601:A1 • 12/07/2010 — Page 3 of 6
IPBRKT: Mounting kit for IPDACT-2/2UD in common enclo-
sure.
IPSPLT: Y-adaptor option allows connection of both panel
dialer outputs to one IPDACT-2/2UD cable input.
COMPATIBLE ANNUNCIATORS
ANN-80(-W): LCD Annunciator is a remote LCD annunciator
that mimics the information displayed on the FACP LCD dis-
play. Recommended wire type is un-shielded. (Basic model is
red; order -W version for white; see DF-52417.)
ANN-LED: Annunciator Module provides three LEDs for each
zone: Alarm, Trouble and Supervisory. Ships with red enclo-
sure (see DF-60241).
ANN-RLED: Provides alarm (red) indicators for up to 30 input
zones or addressable points. (See DF-60241).
ANN-RLY: Relay Module, which can be mounted inside the
cabinet, provides 10 programmable Form-C relays. (See DF-
52431.)
ROME: Relay Option Module Enclosure. Provides one ANN-
RLY Relay Module already installed. The ROME Series pro-
vides mounting space for one additional Relay Module or one
addressable Multi-module. (See Installation Sheet PN 53530.)
ANN-S/PG: Serial/Parallel Printer Gateway module provides a
connection for a serial or parallel printer. (See DF-52429.)
ANN-I/O: LED Driver Module provides connections to a user
supplied graphic annunciator. (See DF-52430.)
ACM-8RF: Relay module provides 8 Form-C 5.0 amp relays.
ACS-LED Zone Series: LED-type fire annunciators capable of
providing up to 99 software zones of annunciation. Available in
increments of 16 or 32 points to meet a variety of applications.
LDM Graphic Series: Lamp Driver Module series for use with
custom graphic annunciators.
LCD-80F (Liquid Crystal Display) point annunciator:
80-character, backlit LCD-type fire annunciators capable of
displaying English-language text.
NOTE: For more information on Compatible Annunciators for use
with the MS-9200UDLS Rev 3, see the following data sheets (doc-
ument numbers) ACM-8RF (DF-51555), ACS/ACMSeries (DF-
52378), LDM Series (DF-51384), LCD-80F (DF-52185).
LITESPEED COMPATIBLE ADDRESSABLE DEVICES
All feature a polling LED and rotary switches for addressing.
CP355: Addressable low-profile ionization smoke detector.
SD355: Addressable low-profile photoelectric smoke detector.
SD355T: Addressable low-profile photoelectric smoke detec-
tor with thermal sensor.
SD355R: Addressable remote test capable detector for use
with D355PL or DNR(W) duct smoke detector housings.
H355: Fast-response, low-profile heat detector.
H355R: Fast-response, low-profile heat detector with rate-of-
rise option.
H355HT: Fixed high-temperature detector that activates at
190F/88C.
AD355(A): Low-profile, intelligent, “Adapt” multi-sensor detec-
tor (B350LP base included).
BEAM355: Intelligent beam smoke detector.
BEAM355S: Intelligent beam smoke detector with integral
sensitivity test.
D355PL: Innovair Flex low-flow non-relay duct-detector hous-
ing. SD355R included.
DNRW: Innovair Flex low-flow non-relay duct-detector hous-
ing, with NEMA-4 rating. Watertight. (Order SD355R sepa-
rately.)
MMF-300: Addressable Monitor Module for one zone of nor-
mally-open dry-contact initiating devices. Mounts in standard
4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-
line resistor. Module may be configured for either a Style B
(Class B) or Style D (Class A) IDC.
MDF-300: Dual Monitor Module. Same as MMF-300 except it
provides two Style B (Class B) only IDCs.
MMF-301: Miniature version of MMF-300. Excludes LED and
Style D option. Connects with wire pigtails. May mount in
device backbox.
MMF-302: Similar to MMF-300, but may monitor up to 20 con-
ventional two-wire detectors. Requires resettable 24 VDC
power. Consult factory for compatible smoke detectors.
Page 4 of 6 — DF-60601:A1 • 12/07/2010
CMF-300: Addressable Control Module for one Style Y/Z
(Class B/A) zone of supervised polarized Notification Appli-
ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.
Notification Appliance Circuit option requires external 24 VDC
to power notification appliances.
CRF-300: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
Mounts directly to a 4.0" (10.16 cm.) box, surface mount using
the SMB500.
BG-12LX: Addressable manual pull station with interface mod-
ule mounted inside.
I300: Fault Isolator Module. This module isolates the SLC loop
from short circuit conditions (required for Style 6 or 7 opera-
tion).
SMB500: Used to mount all modules except the MMF-301 and
M301.
MMF-300-10: Ten-input monitor module. Mount one or two
modules in a BB-2F cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a BB-6F.
MMF-302-6: Six-zone interface module for compatible conven-
tional two-wire detectors. Mount one or two modules in a BB-
2F cabinet (optional). Mount up to six modules on a CHS-6
chassis in a BB-6F.
CMF-300-6: Six-circuit supervised control module. Mount one
or two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
CRF-300-6: Six Form-C relay control module. Mount one or
two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
NOTE: 1) For more information on Compatible Addressable
Devices for use with the MS-9200UDLS Rev 3, see the following
data sheets (document numbers): AD355 (DF-52324), BG-12LX
(DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-60379),
CMF/CRF Series (DF-52130), CP355 (DF-52383), D355PL (DF-
52398), H355 Series (DF-52385), I300 (DF-52389), MMF-300
Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-
302-6 (DF-52356), SD355/SD355T (DF-52384). 2) Legacy 300
Series detection devices such as the CP300/CP350, SD300(T)/
SD350(T) and older modules such as the M300, M301, M302,
C304, and BG-10LX are not compatible with LiteSpeed polling. If
the SLC contains one of these devices, polling must be set for
standard LiteSpeed protocol. Please consult factory for further
information on previous 300 Series devices.
Wiring Requirements
While shielded wire is not required, it is recommended that all
SLC wiring be twisted-pair to minimize the effects of electrical
interference. Wire size should be no smaller than 18 AWG
(0.78 mm²) and no larger than 12 AWG (3.1 mm²). The wire
size depends on the length of the SLC circuit. Refer to the
panel manual for wiring details.
()
DF-60601:A1 • 12/07/2010 — Page 5 of 6
Page 6 of 6 — DF-60601:A1 • 12/07/2010
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Made in the U.S. A.
System Capacity
• Intelligent Signalling Line Circuits.......................................1
• Addressable device capacity..........................................198
• Programmable software zones.........................................99
• ACS Annunciators ............................................................32
• ANN-bus devices..............................................................16
Electrical Specifications
AC Power: MS-9200UDLS Rev 3: 120 VAC, 60 Hz, 3.0 amps.
MS-9200UDLS Rev 3E: 240 VAC, 5 0 Hz, 1.5 amps. Wire size:
minimum 14 AWG (2.00 mm²) with 600 V insulation.
Battery charger capacity: 7 AH - 18 AH batteries. Up to two
18 Ah batteries can be housed in the FACP cabinet. Larger
batteries require an external battery charger such as the CHG-
75 or CHG-120, and a separate battery cabinet such as the
BB-26 or NFS-LBB.
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Each terminal block pro-
vides connections for two Style Y (Class B) for a total of four
Style Y (Class B) or with an optional ZNAC-92 module con-
verts to four Style Z (Class A) NACs. Maximum signaling cur-
rent per circuit: 2.5 amps. End-of-Line Resistor: 4.7K ohm, 1/2
watt (P/N 71252 UL listed) for Style Y (Class B) NAC. Refer to
panel documentation and Fire•Lite Device Compatibility Docu-
ment for listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay:
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30
VAC (resistive). Form-C relays.
Special Application Non-resettable Power (24 VDC Nomi-
nal): Jumper selectable (JP4) for conversion to resettable
power output. Up to 1.0 amp total DC current available from
each output. Power-limited.
Special Application Resettable Power (24 VDC nominal):
Jumper selectable (JP6) for conversion to non-resettable
power. Up to 1.0 amp total DC current available. Refer to the
Fire•Lite Device Compatibility Document for listed compatible
devices.
Remote Sync Output: Remote power supply synchronization
output. Nominal special application power: 24 VDC. Maximum
current: 300 mA. End-of-Line Resistor: 4.7K ohm. Output
linked to NAC 1 control. Supervised and power-limited.
Telephone Interface: Unless used with Teldat VISORALARM,
requires dedicated business telephone number with a mini-
mum of 5 volts DC (off-hook voltage). Obtain dedicated phone
line directly from your local phone company. Do not use shared
phone lines or PBX (digital) type phone line extensions.
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring
(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.)
high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
NFPA Standards
The MS-9200UDLS Rev 3 complies with the following NFPA
72 Fire Alarm Systems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
–AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
– REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (Where a DACT is not accepted,
the alarm, trouble and supervisory relays may be con-
nected to UL 864 listed transmitters. For reverse polarity
signaling of alarm and trouble, 4XTMF is required.)
–PROPRIETARY (Automatic, Manual, Waterflow and
Sprinkler Supervisory).
– CENTRAL STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory).
–OT, PSDN (Other Technologies, Packet-switched Data
Network)
Agency Listings and Approvals
The listings and approvals below apply to the basic MS-
9200UDLS Rev 3 control panel. In some cases, certain mod-
ules may not be listed by certain approval agencies, or listing
may be in process. Consult factory for latest listing status.
• UL Listed: S624
•FM approved
•CSFM: 7165-0075:0208
•MEA: 120-06-E
For ULC-listed version, see DF-60599.
FireLite® Alarms® is a registered trademark of Honeywell International Inc.
Wheelock® is a registered trademark of and Exceder™ is a trademark of
Cooper Notification.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
SYSTEM SPECIFICATIONS