HomeMy WebLinkAboutSigned DERBIN-FULL-R0DATE BY DESCRIPTION INITIAL DESIGN T.01 SCALE: NTS PAPER: ARCHB VER 01 VACINITY MAP NTS01 SHEET INDEX COVER PAGE ROOF PLAN & PV LAYOUT ATTACHMENT DETAILS ELECTRICAL SLD LABELS DATASHEET (STRUCTURAL) DATASHEET (ELECTRICAL) T.01 S.01 S.02-S.03 E.01 L.01 D.01-D.02 D.03-D.04 PROJECT INFORMATION AUTHORITY HAVING JURISDICTION BUILDING: DESIGN SPECS WIND EXPOSURE: WIND SPEED (MPH): GOVERNING CODES BUILDING: ELECTRICAL: FIRE: SYSTEM SIZE (KWDC): # PANELS: PANEL: INVERTER: VOLTAGE: AERIAL VIEW NTS02 A B C D E F 1 2 3 4 5 6 7 8 9 MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 ST. LUCIE COUNTY B 160 FBC 2017 NEC 2014 2015 NFPA 1 9.92 31 MISSION 320 ENPHASE IQ7 120/240 R.G.07.16.20 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS PLAN VIEW01 M I S SOLAR DISCONNECT INVERTER METER BUILDING/ROOF DATA03 MEAN ROOF HEIGHT, h (FT)14 ROOF FACE LEAST HORIZONTAL DIM 22 ROOF PITCH, θ (DEG)<27 ROOF TYPE SHINGLE SUPPORT SPACING 16" OR 24" 10% LEAST HORIZONTAL DIM (FT)2.2 0.4h (FT)5.6 4% LEAST HORIZONTAL DIM (FT)1.2 WIND PERIMETER, a (FT)3 a: 10 percent of least horizontal dimension or 0.4h, whichever is smaller, but not less than either 4% of least horizontal dimension or 3 ft (0.9 m). h: Mean roof height, in feet (meters), except that eave height shall be used for θ ≤ 10°. θ: Angle of plane of roof from horizontal, in degrees. RAIL SYSTEM04 MAKE IRONRIDGE MODEL XR100 # PER PANEL 2 PER SPAN TABLES (IN): Z1, Z2 94 70 MAX CANTILEVER (IN), Z1, Z2 38 28 ADJ SPAN: 24" SPACING (IN): Z1, Z2 48 48 ADJ SPAN: 16" SPACING (IN): Z1, Z2 48 48 ATTACHMENT SYSTEM02 MAKE SRH MODEL QUICKBOLT MIN # ATTACH POINTS (24" SPACING)56 MIN # ATTACH POINTS (16" SPACING)56 FINAL PLACEMENT OF PANELS TO BE DETERMINED BY SUPPORT PLACEMENT AND UNIDENTIFIED OBSTRUCTIONS 31 MISSION 320 KEY: ( ) P INTERCONNECTION PNL/MAIN DISC ZONE 1 ZONE 2 26' 42.4' 15' 9.1' 16' 51.5' 4' 3' 3' 3' 3' DATE BY DESCRIPTION INITIAL DESIGN S.01 SCALE: NTS PAPER: ARCHB VER 01 A B C D E F 1 2 3 4 5 6 7 8 9 R.G.07.16.20 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS PV MODULE FRAME IRONRIDGE RAIL IRONRIDGE UFOEND CLAMP END CLAMP PLAN END CLAMP FRONT PV MODULE FRAMEIRONRIDGE UNIVERSALFASTENING OBJECT PV MODULE FRAME IRONRIDGE RAIL MID CLAMP PLAN MID CLAMP FRONTSS L FOOT SIDE VIEW HANGAR BOLT SIDE VIEW GENERAL 1.1. DESIGN CONFORMS WITH 2017 FLORIDA BUILDING CODE 6TH EDITION CRITERIA FOR WIND FORCES PER ASCE/SEI 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS & OTHER STRUCTURES 1.2. RAILS SHALL BE MOUNTED PERPENDICULAR AND NOT CANTILEVER BEYOND OUTSIDE END OF ROOF ATTACHMENT 1.3. MODULES SHALL BE FASTENED USING MID-CLAMPS & END CLAMPS 1.4. CONTRACTOR SHALL CHANGE/ADJUST THIS PLAN TO SATISFY FBC, AHJ, JOBSITE CONSTRAINTS & OEM DOCUMENTATION 1.5. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONDITION CHANGES MOUNTING 2.1. EACH MODULE SHALL HAVE A MIN. OF (4) CLAMPS EACH 2.2. RAILS SHALL MOUNT TO L-FOOT/FLASH-FOOT 2.3. MODULES SHALL NOT OVERHANG ANY RIDGE LINE. 2.4. SYSTEM DEAD LOAD IS LESS THAN 4LBs PER SQ. FT. ATTACHMENT/L-FOOT/FLASHING DETAILS04NTS .66" .46" 1.99"2.44" 2.34" .58" 1.25" RAIL DETAILS05NTS QUICKBOLT XR-100 NOTES03 CLAMP DETAILS06NTS IRONRIDGE UNIVERSALFASTENING OBJECT IN IN MISSION 320 65.51 39.33 PANEL DETAILS01NTS RUBBERIZED CAULK 5/16-18 X 5.25" 304 SS REMOVABLE HANGAR BOLT 4.15" 0.75" SS L FOOT TOP VIEW 40MM 40MM ø9MM 85MM 40MM 4MM ø3' MICROFLASHING TOP VIEW 5/16-18 X 5.25" SS HANGAR BOLT 3" MIN EMBEDMENT 5/16" SERRATED HEX FLANGE NUT BOLT, 3/8-16" X 1" HEX SS NUT, 3/8-16" FLANGE SS 3" MICROFLASHING SS L-FOOT XR-100 RAIL PV MODULE MIN 2"X4" TRUSS SUPPORT MOUNTING DETAIL02NTS PV MODULE FRAME IRONRIDGE RAIL IRONRIDGE STOPPER SLEEVEIRONRIDGE UFO DATE BY DESCRIPTION INITIAL DESIGN S.02 SCALE: NTS PAPER: ARCHB VER 01 A B C D E F 1 2 3 4 5 6 7 8 9 R.G.07.16.20 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS CALCS BASED ON MAX CONDITIONS. CIRCUIT LENGTH BASED ON 1% VOLTAGE DROP. SEE NOTE 1.6 FOR RACEWAYS IN DIRECT SUNLIGHT. *CCC: CURRENT CARRYING CONDUCTORS EXISTING 200A 120/240V MAIN PANEL W/ 150A MAIN BREAKER EGC BOND AT ROOF ARRAY RACKING SYSTEM, NOTE #3.2. B GENERAL NOTES01 INVERTER RATINGS04 SYSTEM02 CONDUCTOR SCHEDULE05 ELECTRICAL LINE DIAGRAM06 GENERAL 1.1. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH NEC 2014 AND FBC 2017 REQUIREMENTS AND EQUIPMENT INSTALLATION INSTRUCTIONS NOT SPECIFIED IN THIS PLAN. 1.2. CONDUCTOR TYPES SHALL MEET THE REQUIREMENTS SET FOURTH IN NEC 310.10 BASED ON INSTALLATION LOCATION. 1.3. DIRECT-CURRENT PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS INSIDE A BUILDING SHALL BE CONTAINED IN METAL RACEWAYS 690.31(G). 1.4. ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(D). 1.5. CONDUCTOR SIZING IS BASED ON RACEWAYS NOT EXPOSED TO DIRECT SUNLIGHT UNLESS STATED OTHERWISE. 10% OF CIRCUIT LENGTH CAN BE EXPOSED DIRECT SUNLIGHT UP TO 10FT, NEC 310.15(A)(2). 1.6. PV SOURCE AND OUTPUT CIRCUIT CONDUCTORS ARE SIZED BE EXPOSED TO DIRECT SUNLIGHT GREATER THAN 10% OF THEIR LENGTH WHEN INSTALLED IN RACEWAYS ½” OR GREATER ABOVE ROOF. ADJUSTMENTS ARE BASED ON MAX CURRENT OF 16A, 35C AMBIENT TEMPERATURE, NEC 310.15(B)(2)(A) AND 310.15(B)(3)(C). SYSTEM SPECIFIC 2.1. THE ENPHASE SYSTEM IS NON-ISOLATED AND UNGROUNDED. NEITHER THE NEGATIVE NOR POSITIVE CONDUCTOR IS GROUNDED AND HAS A COMMON AC AND DC EQUIPMENT GROUNDING TERMINAL THEREFORE NO DC GEC IS REQUIRED. 2.2. ENPHASE IQ SERIES MICROINVERTERS™ REQUIRE NO GROUND OR GROUNDED CONDUCTOR BECAUSE THE DC CIRCUIT IS ISOLATED AND INSULATED FROM GROUND. 2.3. UTILITY CONNECTION IS MADE ON LOAD SIDE OF SERVICE DISCONNECT IN ACCORDANCE WITH 705.12(D)(2)(1)(A). GROUNDING 3.1. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690. 3.2. PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS USING MODULE LUGS OR RACKING INTEGRATED GROUNDING CLAMPS AS ALLOWED BY LOCAL JURISDICTION. EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN ACCORDANCE WITH NEC 250.120(C). 3.3. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF #10 AWG WHEN NOT EXPOSED TO DAMAGE, AND #6 AWG SHALL BE USED WHEN EXPOSED TO DAMAGE. A BRANCH C: 15 - 16 MODS MICRO- INVERTER MODULE RATINGS03 MAKE ENPHASE MODEL IQ7 MAX INPUT VOLTAGE 48 V MPP VOLTAGE 27-37 V MAX ISC CURRENT 15 A NOM AC VOLTAGE 240 V MAX AC CURRENT 1 A MAKE MISSION MODEL MSE 320 RATED POWER 320 W VMPP 34.22 V IMPP 9.35 A VOC 40.8 V ISC 10 A # MODS 31 # BRANCH 2 # INVERTERS 31 MIN STRING SIZE 15 MOD MAX STRING SIZE 16 MOD STC DC RATING 9.92 KW AC OUTPUT RATING 7.44 KW DC/AC 133 % INTERCONNECT BREAKER ID RUN VOLTAGE (V) CURRENT (A) VD (%)LENGTH CONDUCTOR SIZE Ω/KFT CONDUIT SIZE #CCC EGC OCPD TERM (C)TEMP ADJ FILL ADJ BASE AMP DERATED AMP A JBOX - COMB 240 16 1 60 THHN/THWN-2 #10 1.24 PVC/EMT MIN 3/4"2 #10 20 75 0.96 1 35 35 B COMB - PCC 240 31 1 50 THHN/THWN-2 #8 0.778 PVC/EMT/FMC/NMLT MIN 3/4" 3 #10 40 75 0.96 1 50 50 RE: NOTE 2.3 150A === 20A/2 20A/2 10A/2 BRANCH B: 15 - 16 MODS INTEGRATED ENVOY CIRCUIT ENPHASE IQ COMBINER BOX ENPHASE Q CABLE JBOX Q-CABLE TO THHN/THWN-2 TRANSITION BIDIRECTIONAL METER EXISTING GROUNDING ELECTRODE 40A/2 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: DATE BY DESCRIPTION INITIAL DESIGN E.01 SCALE: NTS PAPER: ARCHB VER 01 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. A B C D E F 1 2 3 4 5 6 7 8 9 MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 R.G.07.16.20 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS LABELS01 ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LOCATION: AC/PV DISCONNECT, NEC 690.17 ! WARNING ! LOCATION: EACH DISCONNECT, NEC 690.13(B),NFPA 11.12 PHOTOVOLTAIC DISCONNECT LOC: MARKINGS SHALL COMPLY WITH NEC 690.31(E)(3), 690.31(E)(4) AND NFPA 11.12 AND SHALL BE PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE ASSEMBLIES AT LEAST EVERY 10 FEET; AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL JUNCTION BOXES. WARNING: PHOTOVOLTAIC POWER SOURCE LOCATION: RAPID SHUTDOWN SWITCH OR AC/PV DISC, NEC 690.56(C) SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LOCATION: MAIN SERVICE DISCONNECT, NFPA 11.12 WARNING: PHOTOVOLTAIC POWER SOURCE LOCATION: POINT OF INTERCONNECTION, NEC 705.12(D)(3) WARNING: DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM GENERAL 1.1. LABELING REQUIREMENTS BASED ON NEC 2014 & NFPA 2015. 1.2. MATERIALS USED ARE SUBJECT TO THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3. LABEL MATERIALS SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT. 1.4. LABELS SHALL BE A MINIMUM LETTER HEIGHT OF 3/8" AND PERMANENTLY AFFIXED. PHOTOVOLTAIC AC DISCONNECT AC OUTPUT VOLTAGE 240 V AC OUTPUT CURRENT 31 A LOCATION: AC DISCONNECT, NEC 690.54 SOLAR SYSTEM POWERED BY PLANET SOLAR SOLUTIONS PH:561 250-7652 PLANETSOLARSOLUTIONS.COM LOCATION: ADJACENT TO MAIN SERVICE DISC, NFPA 11.12 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: DATE BY DESCRIPTION INITIAL DESIGN L.01 SCALE: NTS PAPER: ARCHB VER 01 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. A B C D E F 1 2 3 4 5 6 7 8 9 MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 R.G.07.16.20 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS RAIL01 ATTACHMENT02 DATE BY DESCRIPTION INITIAL DESIGN D.01 SCALE: NTS PAPER: ARCHB VER 01 A B C D E F 1 2 3 4 5 6 7 8 9 R.G.07.16.20 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS INVERTER01 MODULE02 ENGINEER OF RECORDCONTRACTOR | PROJECT ID: DATE BY DESCRIPTION INITIAL DESIGN D.02 SCALE: NTS PAPER: ARCHB VER 01 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. A B C D E F 1 2 3 4 5 6 7 8 9 MICHAEL DERIBIN 209 RAMIE LN, PORT ST LUCIE, FL 34952 071620EN9.92-PSS CVC57054 SPENCER N. ROBINSON PE81250 R.G.07.16.20 4371 NORTHLAKE BLVD STE 185 PH:561 250-7652 PLANETSOLARSOLUTIONS.COM PLANET SOLAR SOLUTIONS