INITIAL DESIGN T.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
VACINITY MAP
NTS01
SHEET INDEX
COVER PAGE
ROOF PLAN & PV LAYOUT
ATTACHMENT DETAILS
ELECTRICAL SLD
LABELS
DATASHEET (STRUCTURAL)
DATASHEET (ELECTRICAL)
T.01
S.01
S.02-S.03
E.01
L.01
D.01-D.02
D.03-D.04
PROJECT INFORMATION
AUTHORITY HAVING JURISDICTION
BUILDING:
DESIGN SPECS
WIND EXPOSURE:
WIND SPEED (MPH):
GOVERNING CODES
BUILDING:
ELECTRICAL:
FIRE:
SYSTEM
SIZE (KWDC):
# PANELS:
PANEL:
INVERTER:
VOLTAGE:
AERIAL VIEW
NTS02
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
ST. LUCIE COUNTY
B
160
FBC 2017
NEC 2014
2015 NFPA 1
9.92
31
MISSION 320
ENPHASE IQ7
120/240
R.G.07.16.20
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS
PLAN VIEW01
M
I
S SOLAR DISCONNECT
INVERTER
METER
BUILDING/ROOF DATA03
MEAN ROOF HEIGHT, h (FT)14
ROOF FACE LEAST HORIZONTAL DIM 22
ROOF PITCH, θ (DEG)<27
ROOF TYPE SHINGLE
SUPPORT SPACING 16" OR 24"
10% LEAST HORIZONTAL DIM (FT)2.2
0.4h (FT)5.6
4% LEAST HORIZONTAL DIM (FT)1.2
WIND PERIMETER, a (FT)3
a: 10 percent of least horizontal dimension or 0.4h, whichever is smaller,
but not less than either 4% of least horizontal dimension or 3 ft (0.9 m).
h: Mean roof height, in feet (meters), except that eave height shall be used
for θ ≤ 10°.
θ: Angle of plane of roof from horizontal, in degrees.
RAIL SYSTEM04
MAKE IRONRIDGE
MODEL XR100
# PER PANEL 2
PER SPAN TABLES (IN): Z1, Z2 94 70
MAX CANTILEVER (IN), Z1, Z2 38 28
ADJ SPAN: 24" SPACING (IN): Z1, Z2 48 48
ADJ SPAN: 16" SPACING (IN): Z1, Z2 48 48
ATTACHMENT SYSTEM02
MAKE SRH
MODEL QUICKBOLT
MIN # ATTACH POINTS (24" SPACING)56
MIN # ATTACH POINTS (16" SPACING)56
FINAL PLACEMENT OF PANELS TO BE
DETERMINED BY SUPPORT PLACEMENT AND
UNIDENTIFIED OBSTRUCTIONS
31 MISSION 320
KEY:
( )
P INTERCONNECTION PNL/MAIN DISC
ZONE 1
ZONE 2
26'
42.4'
15'
9.1'
16'
51.5'
4'
3'
3'
3'
3'
DATE BY DESCRIPTION
INITIAL DESIGN S.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
R.G.07.16.20
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS
PV MODULE FRAME
IRONRIDGE RAIL
IRONRIDGE UFOEND CLAMP
END CLAMP PLAN END CLAMP FRONT
PV MODULE FRAMEIRONRIDGE UNIVERSALFASTENING OBJECT PV MODULE FRAME
IRONRIDGE RAIL
MID CLAMP PLAN MID CLAMP FRONTSS L FOOT SIDE VIEW HANGAR BOLT SIDE VIEW
GENERAL
1.1. DESIGN CONFORMS WITH 2017 FLORIDA BUILDING CODE 6TH
EDITION CRITERIA FOR WIND FORCES PER ASCE/SEI 7-10
MINIMUM DESIGN LOADS FOR BUILDINGS & OTHER
STRUCTURES
1.2. RAILS SHALL BE MOUNTED PERPENDICULAR AND NOT
CANTILEVER BEYOND OUTSIDE END OF ROOF ATTACHMENT
1.3. MODULES SHALL BE FASTENED USING MID-CLAMPS & END
CLAMPS
1.4. CONTRACTOR SHALL CHANGE/ADJUST THIS PLAN TO SATISFY
FBC, AHJ, JOBSITE CONSTRAINTS & OEM DOCUMENTATION
1.5. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONDITION
CHANGES
MOUNTING
2.1. EACH MODULE SHALL HAVE A MIN. OF (4) CLAMPS EACH
2.2. RAILS SHALL MOUNT TO L-FOOT/FLASH-FOOT
2.3. MODULES SHALL NOT OVERHANG ANY RIDGE LINE.
2.4. SYSTEM DEAD LOAD IS LESS THAN 4LBs PER SQ. FT.
ATTACHMENT/L-FOOT/FLASHING DETAILS04NTS
.66"
.46"
1.99"2.44"
2.34"
.58"
1.25"
RAIL DETAILS05NTS
QUICKBOLT XR-100
NOTES03
CLAMP DETAILS06NTS
IRONRIDGE UNIVERSALFASTENING OBJECT
IN
IN
MISSION 320
65.51
39.33
PANEL DETAILS01NTS
RUBBERIZED
CAULK
5/16-18 X 5.25"
304 SS
REMOVABLE HANGAR
BOLT
4.15"
0.75"
SS L FOOT TOP VIEW
40MM
40MM ø9MM
85MM
40MM
4MM
ø3'
MICROFLASHING TOP VIEW
5/16-18 X 5.25" SS
HANGAR BOLT
3" MIN
EMBEDMENT
5/16" SERRATED HEX
FLANGE NUT
BOLT, 3/8-16" X 1" HEX SS
NUT, 3/8-16" FLANGE SS 3" MICROFLASHING
SS L-FOOT
XR-100 RAIL
PV MODULE
MIN 2"X4"
TRUSS SUPPORT
MOUNTING DETAIL02NTS
PV MODULE FRAME
IRONRIDGE RAIL
IRONRIDGE STOPPER SLEEVEIRONRIDGE UFO
DATE BY DESCRIPTION
INITIAL DESIGN S.02
SCALE:
NTS
PAPER:
ARCHB
VER
01
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
R.G.07.16.20
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS
CALCS BASED ON MAX CONDITIONS. CIRCUIT LENGTH BASED ON 1% VOLTAGE DROP. SEE NOTE 1.6 FOR RACEWAYS IN DIRECT SUNLIGHT. *CCC: CURRENT CARRYING CONDUCTORS
EXISTING 200A
120/240V MAIN
PANEL W/ 150A
MAIN BREAKER
EGC BOND AT ROOF
ARRAY RACKING SYSTEM,
NOTE #3.2.
B
GENERAL NOTES01 INVERTER RATINGS04
SYSTEM02
CONDUCTOR SCHEDULE05
ELECTRICAL LINE DIAGRAM06
GENERAL
1.1. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH NEC 2014 AND FBC 2017 REQUIREMENTS AND EQUIPMENT INSTALLATION INSTRUCTIONS
NOT SPECIFIED IN THIS PLAN.
1.2. CONDUCTOR TYPES SHALL MEET THE REQUIREMENTS SET FOURTH IN NEC 310.10 BASED ON INSTALLATION LOCATION.
1.3. DIRECT-CURRENT PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS INSIDE A BUILDING SHALL BE CONTAINED IN METAL RACEWAYS 690.31(G).
1.4. ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(D).
1.5. CONDUCTOR SIZING IS BASED ON RACEWAYS NOT EXPOSED TO DIRECT SUNLIGHT UNLESS STATED OTHERWISE. 10% OF CIRCUIT LENGTH CAN
BE EXPOSED DIRECT SUNLIGHT UP TO 10FT, NEC 310.15(A)(2).
1.6. PV SOURCE AND OUTPUT CIRCUIT CONDUCTORS ARE SIZED BE EXPOSED TO DIRECT SUNLIGHT GREATER THAN 10% OF THEIR LENGTH WHEN
INSTALLED IN RACEWAYS ½” OR GREATER ABOVE ROOF. ADJUSTMENTS ARE BASED ON MAX CURRENT OF 16A, 35C AMBIENT TEMPERATURE, NEC
310.15(B)(2)(A) AND 310.15(B)(3)(C).
SYSTEM SPECIFIC
2.1. THE ENPHASE SYSTEM IS NON-ISOLATED AND UNGROUNDED. NEITHER THE NEGATIVE NOR POSITIVE CONDUCTOR IS GROUNDED AND HAS A
COMMON AC AND DC EQUIPMENT GROUNDING TERMINAL THEREFORE NO DC GEC IS REQUIRED.
2.2. ENPHASE IQ SERIES MICROINVERTERS™ REQUIRE NO GROUND OR GROUNDED CONDUCTOR BECAUSE THE DC CIRCUIT IS ISOLATED AND
INSULATED FROM GROUND.
2.3. UTILITY CONNECTION IS MADE ON LOAD SIDE OF SERVICE DISCONNECT IN ACCORDANCE WITH 705.12(D)(2)(1)(A).
GROUNDING
3.1. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690.
3.2. PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS USING MODULE LUGS OR RACKING INTEGRATED GROUNDING CLAMPS AS ALLOWED BY
LOCAL JURISDICTION. EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN ACCORDANCE WITH NEC 250.120(C).
3.3. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF #10 AWG WHEN NOT
EXPOSED TO DAMAGE, AND #6 AWG SHALL BE USED WHEN EXPOSED TO DAMAGE.
A
BRANCH C: 15 - 16 MODS
MICRO-
INVERTER
MODULE RATINGS03
MAKE ENPHASE
MODEL IQ7
MAX INPUT VOLTAGE 48 V
MPP VOLTAGE 27-37 V
MAX ISC CURRENT 15 A
NOM AC VOLTAGE 240 V
MAX AC CURRENT 1
A
MAKE MISSION
MODEL MSE 320
RATED POWER 320 W
VMPP 34.22 V
IMPP 9.35 A
VOC 40.8 V
ISC 10 A
# MODS 31
# BRANCH 2
# INVERTERS 31
MIN STRING SIZE 15 MOD
MAX STRING SIZE 16 MOD
STC DC RATING 9.92 KW
AC OUTPUT RATING 7.44 KW
DC/AC 133 %
INTERCONNECT BREAKER
ID RUN VOLTAGE (V) CURRENT (A) VD (%)LENGTH CONDUCTOR SIZE Ω/KFT CONDUIT SIZE #CCC EGC OCPD
TERM (C)TEMP ADJ FILL ADJ BASE AMP DERATED AMP
A JBOX - COMB 240 16 1 60 THHN/THWN-2 #10 1.24 PVC/EMT MIN 3/4"2 #10 20 75 0.96 1 35 35
B COMB - PCC 240 31 1 50 THHN/THWN-2 #8 0.778 PVC/EMT/FMC/NMLT MIN 3/4" 3 #10 40 75 0.96 1 50 50
RE: NOTE 2.3
150A
===
20A/2
20A/2
10A/2
BRANCH B: 15 - 16 MODS
INTEGRATED
ENVOY CIRCUIT
ENPHASE IQ
COMBINER BOX
ENPHASE
Q CABLE
JBOX
Q-CABLE TO
THHN/THWN-2
TRANSITION
BIDIRECTIONAL
METER
EXISTING
GROUNDING
ELECTRODE
40A/2
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
DATE BY DESCRIPTION
INITIAL DESIGN E.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
R.G.07.16.20
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS
LABELS01
ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN POSITION
LOCATION: AC/PV DISCONNECT, NEC 690.17
! WARNING !
LOCATION: EACH DISCONNECT, NEC 690.13(B),NFPA 11.12
PHOTOVOLTAIC
DISCONNECT
LOC: MARKINGS SHALL COMPLY WITH NEC 690.31(E)(3), 690.31(E)(4)
AND NFPA 11.12 AND SHALL BE PLACED ON ALL INTERIOR AND
EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE
ASSEMBLIES AT LEAST EVERY 10 FEET; AT TURNS AND
ABOVE/BELOW PENETRATIONS AND ALL JUNCTION BOXES.
WARNING: PHOTOVOLTAIC
POWER SOURCE
LOCATION: RAPID SHUTDOWN SWITCH OR AC/PV DISC, NEC 690.56(C)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LOCATION: MAIN SERVICE DISCONNECT, NFPA 11.12
WARNING: PHOTOVOLTAIC
POWER SOURCE
LOCATION: POINT OF INTERCONNECTION, NEC 705.12(D)(3)
WARNING: DUAL POWER
SOURCES. SECOND SOURCE
IS PV SYSTEM
GENERAL
1.1. LABELING REQUIREMENTS BASED ON NEC 2014 & NFPA 2015.
1.2. MATERIALS USED ARE SUBJECT TO THE REQUIREMENTS OF THE AUTHORITY
HAVING JURISDICTION.
1.3. LABEL MATERIALS SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT.
1.4. LABELS SHALL BE A MINIMUM LETTER HEIGHT OF 3/8" AND PERMANENTLY AFFIXED.
PHOTOVOLTAIC AC DISCONNECT
AC OUTPUT VOLTAGE 240 V
AC OUTPUT CURRENT 31 A
LOCATION: AC DISCONNECT, NEC 690.54
SOLAR SYSTEM POWERED BY
PLANET SOLAR SOLUTIONS
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
LOCATION: ADJACENT TO MAIN SERVICE DISC, NFPA 11.12
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
DATE BY DESCRIPTION
INITIAL DESIGN L.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
R.G.07.16.20
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS
RAIL01 ATTACHMENT02
DATE BY DESCRIPTION
INITIAL DESIGN D.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
R.G.07.16.20
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS
INVERTER01 MODULE02
ENGINEER OF RECORDCONTRACTOR |
PROJECT ID:
DATE BY DESCRIPTION
INITIAL DESIGN D.02
SCALE:
NTS
PAPER:
ARCHB
VER
01
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
MICHAEL DERIBIN
209 RAMIE LN, PORT ST LUCIE, FL 34952
071620EN9.92-PSS
CVC57054
SPENCER N. ROBINSON
PE81250
R.G.07.16.20
4371 NORTHLAKE BLVD STE 185
PH:561 250-7652
PLANETSOLARSOLUTIONS.COM
PLANET SOLAR SOLUTIONS