HomeMy WebLinkAbout2019-07-31_Building Dept. Comments_REV4RAG Reinaldo A. Gomez Architect A R #0013736 16047 SW 68 ST Miami, Florida 33193 Phone: 786-261-9551 7-31-2020 Response to comments: Permit Number: 2002-0505 Buildli Q1. PLEASE SHOW HOW THE RESTROOMS COMPLY WITH THE ADA SECTION (202.1) —ACCESSIBLE RESTROOMS ARE NOT PROVIDED."' R1. SEE SHEET A-1 FOR ADDED NOTES. Q2. THE "MEZZANINE" ON THE PLANS DOES NOT MEET THE OPENNESS REQUIREMENTS OF SECTION (505.2.3). THIS IS A FULLY ENCLOSED SECOND FLOOR. THERE IS A BOARDED UP DOOR TO AN ADJACENT SPACE, IT IS NOT CLEAR IF IT GOES TO A DIFFERENT TENANT SPACE OR IS A MEANS OF EGRESS. NO LIGHT, LIMITED VISIBILITY. —PROVIDE OPENNESS EXCEPTION ON THE PLANS"' R2. SEE NOTE ADDED ON SHEET A-2. Q3. ASSIGN A FUNCTION TO THE SECOND FLOOR SPACE. SHOW ACCESSIBILITY REQUIREMENTS. ([A] 107.2.1) R3. SEE SHEET A-2 FOR ROOM NAME "STORAGE". Q4. SEE DEAD END CORRIDOR ON SECOND FLOOR -•501N OCCUPANCIES IN GROUPS B, E, F, 1-1, M, R-1, R-2, R-4, S AND U, WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1, THE LENGTH OF THE DEAD-END CORRIDORS SHALL NOT EXCEED 50 FEET (15 240 MM). (1020.4 DEAD ENDS) R4. SEE SHEET A-2 FOR ADDED EXTERIOR STAIRS. NO DEAD END CONDITION EXISTS. PLUMBING Q1. NEED TO SHOW LOCATION OF DRINKING FOUNTAIN 107.2.1 FLORIDA BUILDING CODE 2017 6TH EDITION R1. PLEASE SEE SHEET A-2 FOR ADDED DF. Q2. NEED TO SHOW LOCATION OF WATER HEATER. 107.2.1 FLORIDA BUILDING CODE 2017 6TH EDITION R2. SEE SHEET A-1 FOR WH LOCATION. Q3. EXISTING FLOOR DRAIN- GREASE SEPARATOR REQUIRED. R3. SEE SHEET A-1 FOR EXISTING GREASE TRAP LOCATION.