HomeMy WebLinkAboutEngineering; Installation Guidelines for GeneratorSite Selection and Preparation
Potential CO Entry Points
See Figure 3-1. Generator exhaust can enter a structure
through large openings, such as windows and doors.
However, exhaust and CO can also seep into the
structure through smaller, less obvious openings.
Protect the Structure
x�.
Verify structure itself is correctly caulked and sealed to
prevent air from leaking in or out. Voids, cracks, br
openings around windows, doors, soffits, pipes, and
vents can allow exhaust gas to be drawn into the
structure.
Some examples of potential entry points are described
and included in, but not limited to, the accompanying
table.
Figure 3-1. Carbon Monoxide —Potential Entry Points
ID
Entry on
Description /Comments
A
Windows and doors
Architectural details which can be (or are) opened to admit fresh air into the structure.
B
Garage door
CO can leak into garage if door is open, or does not seal correctly when closed.
C
Attic vent
Attic vents, ridge vents, crawl space vents, and soffit vents can all admit generator exhaust.
D
Basement windows
Windows or hatches allowing ventilation to or from lower level of a structure.
E
Furnace intake!
Air intake and exhaust pipes for furnace.
exhaustvent
Includes (but not limited to) cracks in wall, foundation, mortar, or air gaps around doors,
F
Wall cracks
windows -,and pipes. See Protect the Structure.
G
Dryer vent
Exhaust duct or clothes dryer.
H
Airflow restrictions
Structural corners and locations with heavy vegetation restrict airflow. Exhaust gases can collect
in such areas.
IMPORTANT NOTE: Mechanical and gravity outdoor air intake openings for HVAC supply
i
Make up air system
air systems shall be located not less than 10 feet (3048mm) horizontally from the
generator enclosure. See Section 401 in the ICC Mechanical Code for any additional
requirements.
14 Installation Guidelines for 60 Hz Air -Cooled Generators
Site Selection and Preparation
Fire Prevention
The generator must be installed at a safe distance away
from combustible matarials. Engine, alternator, and
exhaust system components become very hot during
operation. Fire risk increases if unit is not correctly
ventilated, is not correctly maintained, operates too close
to combustible materials, or if fuel leaks exist. Also,
accumulations of flammab!e debris within or outside the
generator enclosure may ignite.
Distance Requirements
See Figure 3-2. Minimum clearances must be
maintained around the generator enclosure. These
clearances are primarily for fire prevention, but also to
ensure sufficient room for removing front and end panels
for maintenance purposes.
Figure 3-2. Generator Distance nequiremems
ID
Description
I Definition
Front and end
I Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes
A
clearance
shrubs, bushes, and trees.
Fuel and electrical connections are made here. 18 in (457 mm) minimum clearance per NFPA
B
Rear clearance
testing, labeling, and listing, unless state or local codes dictate otherwise.
Windows, vents,
No operable windows, doors, vents, window wells, or openings in the wall are permitted near any
O
and openings
point of the generator. See Potential CO Entry Points for more information.
D
Existing wall
The generator should not be placed closer than 18 in (457 mm) from existing walls.
A removable barrier (non -permanent; without footings) installed as a visual surround.
E
Removable fence
Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the
generator.
5 ft (1.52 m) minimum distance from any structure, overhang, or projections from wall.
F
Overhead clearance
DO NOT install under wooden decks or structures.
Maneuvering space around generator for performing routine maintenance tasks such as battery
G
Maintenance and
replacement and engine service. Do not attempt to conceal generator with shrubs, bushes, or
servicing
plants.
fnr r h H> Air -Cooled Generators
iti
Site Selection and Preparation
Fire Codes, Standards, and Guidelines
Generator installation must comply strictly with ICC
IFGC, NFPA 37, NFPA 54, NFPA 58, and NFPA 70
standards. These standards prescribe the minimum safe
clearances around and above the generator enclosure.
NFPA 37
NFPA 37 is the The National Fire Protection
Association's standard for the installation and use of
stationary combustion engines. Its requirements limit the
spacing of an enclosed generator set from a structure or
wall, and require generator to be located where it is
readily accessible for maintenance, repair, and first
responders.
NFPA 37, Section 4.1.4, Engines Located Outdoors:
Engines, and their weatherproof housings if provided,
installed outdoors shall be located at least 5 ft (1.52 m)
from openings in walls and at least 5 ft (1.52 m) from
structures having combustible walls. A minimum
separation shall not be required where the following
conditions exist:
1. The adjacent wall of the structure has a fire resis-
tance rating of at least one hour.
2. The weatherproof enclosure is constructed of non-
combustible materials and it has been demon- .
strated that a fire within the enclosure will not ignite
combustible materials outside the enclosure:
Annex A —Explanatory Material
A4.1.4 (2) Means of demonstrating compliance are by
means of full scale fire test or by calculation procedures.
Because of the limited spaces frequently available for
installation, it has become apparent that exception (2)
would be beneficial for many residential and commercial
installations. The manufacturer contracted with an
independent testing laboratory to run full scale fire tests.
NOTE: The Southwest Research Institute (SWRI) is a
nationally recognized third party testing and listing
agency. SwRI testing approves 18 in (457 mm) installa-
tion minimum from the rear panel of the generator to an
adjacent structure for fire protection.
The criteria was to determine the worst case fire scenario
within the generator and to determine the ignitability of
items outside the engine enclosure at various distances.
The enclosure is constructed of non-combustible
materials, and the results and conclusions from the
independent testing lab indicated that any fire within the
generator enclosure would not pose any ignition risk to
nearby combustibles or structures, with or without fire
service personnel response.
® sofa D NV 1320"W1
UV O U C ""'�^ t nhh Clause 121
V1/ 4.14 of NFPA 37
nSTEO BY. Souftest Research
fnstiNtb SM-Antoeu, Tom
-®®•— NOTE f 130 CHAA
KW —NOTE 2 130 CHAR MAXI-
-®® NOTE 3 13D CHAR MA*—
�®®•NOTE 4 130 CHAR MA* --®®
NDTE U 130 CHAR. M4x—®
NOTE a 130 CHAR IRM
.—.®® NOTE 7 f30 CHAR MAX —®
Sam= POVIM SYSMW, INC
\ WAUKESHA, YA USA 83189 WSW
002158
Figure 3-3. Southwest Research Institute Marking
hitp✓/www2.swri.org/www2(listarod/
DocumentSelection.asp7ProduatlD=973bindustrylD=2
Based on this testing and the requirements of NFPA 37,
Sec 4.1.4, the guidelines for installation of the generators
listed above are changed to 18 in (457 mm) from the
back side of the generator to a stationary wall or building
For adequate maintenance and airflow clearance, the
area above the generator should be at least 5 ft (1.52 m)
with a minimum of-3 ft (0.91 m) at the front and ends of
the enclosure. This includes trees, shrubs, and bushes.
Vegetation not in compliance with these clearance
parameters could obstruct air flow. In addition, exhaust
fumes from the generator could inhibit plant growth. See
Figure 3-2 and the accompanying, descriptions.
Generator Maintenance
Regular maintenance is crucial for minimizing exhaust
emissions and reducing the risk of fire or equipment
failure. For example:
o A dirty air filter or low engine oil level may cause
engine to overheat.
o Incorrect spark plug gaps may cause engine back-
firing and incomplete combustion.
IMPORTANT NOTE: See Maintenance section of
generator owner's manual to view a table of
scheduled maintenance tasks and procedures.
Perform all maintenance tasks as directed.
Wp
Installation Guidelines for 60 Hz Air -Cooled Generators
Fresh Alr for Ventilation and Cooling
Install unit where air inlet and outlet openings will not
become obstructed by leaves, grass, snow, etc. If
prevailing winds will cause blowing or drifting, consider
using'a windbreak at a safe distance to protect the unit.
Water ingress Avoidance
o Select a location on high ground where water lev-
els will not rise and,flood the generator. This unit
should not operate in, or be subjected to, standing
water.
a Install unit where rain gutter downspouts, roof run-
off, landscape irrigation, water sprinklers, or sump
pump discharge does not flood unit or spray enclo-
sure, including any air inlet or outlet openings.
o Excess moisture can cause excess corrosion and
decrease life expectancy of the unit.
Proximity to Utilities
o Contact local utility providers and verify proposed
site selection meets all required utility placement
requirements before installation. This could affect
warranty coverage.
o Remember, laws and or codes may regulate dis-
tance and location.of unit to specific utilities.
It is recommendeq to pick a location where the
generator is as close as possible to the transfer
switch andthe fue) supply, while verifying the site
location conforms to the rest of the Site Selection
section.
Verify WI-Fi Range
See Wi-Fi manual shipped with the unit if planning to use
the WI-Fi feature.
Transportation Recommendations
Use a suitable cart or equipment to carry generator,
including wooden pallet, to installation site. Place
cardboard between cart and generator to prevent any
damage or scratches to generator.
Do not lift, carry, or move generator by grasping the
louvers. Doing so may bend, or damage. the sheet
metal.
Site Selection and Preparation
Suitable Mounting Surface
See Figure 3-4. Prepare a rectangular area
approximately 5 in (127 mm) deep (A) and approximately
3 in (76.2 mm) longer and wider (B) than the generator
on all sides.
N
Figure 34. Compacted Gravel or Concrete Pad
Select base type as desired or as required by local laws
or codes. The generator is typically placed on pea gravel,
crushed stone, or a concrete pad. Follow all applicable
codes if a concrete pad is required.
Verify surface where + generator will be mounted is
compacted, leveled, and will not erode over time.
Generator must be level within 0.5 in (13 mm) all around.
Placement on Roofs, Platforms,. and
Other Supporting Structures
Where required to place generator on a roof, platform,
deck, or other supporting structure, generator must be
placed in accordance with the requirements in NFPA 37,
Section 4.1.3. Generator can be located 18 in (457 mm)
from structures having combustible walls and 5 ft (1.52
m) from any operable opening in the structure. Surface
beneath the generator and beyond must be
noncombustible to a minimum distance of 12 in (30.5
cm). Contact local Building Inspection Department or fire
department to determine which noncombustible materials
are approved for installation.