HomeMy WebLinkAbout002 Energy Calcs - Manual J - Layout - Chambers 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: CHAMBERS RESIDENCE Builder Name: COLE CONSTRUCTION SERVICES,LLC.
Street: 4700 INDRIO ROAD Permit Office: ST LUCIE COUNTY
City,State,Zip: FORT PIERCE,FL,34951 Permit Number: Y
U
Owner: ROSS AND NORANN CHAMBERS Jurisdiction: ST LUCIE COUNTY w
Design Location: FL,Fort Pierce U
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA,
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with the The insulation in any dropped ceiling/soffit
Ceiling/attic insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be sealed. shall be insulated by completely filling the cavity with a
Knee walls shall be sealed. material having a thermal resistance of R-3 per inch
minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and continuous
alignment with the air barrier.
Windows,skylights The space between window/door jambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be installed to
(including maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation shall
and cantilevered floors) be permitted to be in contact with the top side of
sheathing,or continuous insulation installed on the
underside of floor framing and extends from the bottorr
to the top of all perimeter floor framing members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with a Where provided instead of floor insulation,insulation
Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls.
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to exterior
or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on installation
readily conforms to the available cavity spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall Recessed light fixtures installed in the building
be sealed to the drywall. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring an J
plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring.
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall be
on exterior wall tubs shall separate them from the showers and tubs. insulated.
Electrical/phone box on The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be sealed
sprinklers in a manner that is recommended by the manufacturer.Caulking or other
adhesive sealants shall not be used to fill voids between fire sprinkler
cover plates and walls or ceilings.
a.In addition,inspection of log walls shall be in accordance with the provisions of[CC-400.
7/30/2020 12:32 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 1
This document was created with Win2PDF available at http://www.win2pdf.com.
The unregistered version of Win2PDF is for evaluation or non-commercial use only.
This page will not be added after purchasing Win2PDF.
GENERAL SPECIFICATIONS: SHEET INDEX
WINDOW/ LINTEL SCHEDULE DOOR/ LINTEL SCHEDULE i° p
1. ROOF: 5V METAL OVER 30#FELT OVER 5/8"CDX PLY OVER PE WOOD ROOF TRUSS AS PER FRAMING PLAN. A-1 floor plan ,o,+ � U
= • D. 2.CEILING: 1/2"OR 5/8"GWB OVER WOOD PE TRUSS BOTTOM CHORD. un O �' o
LINTELTE • • • • 3. E:XTERIOR SOFFIT: STUCCO&LATH PER GEN NOTE 34 OVER FRAMING W/NO VENTS. A-2 foundation plan = p
• _. u T R PINE T&G PER GEN NOTE 34. o — U s?
4. PORCH CEILING: STUCCO& LATH OVER FRAMING O - m =
3fr , L7NTEG8RFZ2, S 1T„ .,, 6.,S1hffN ,.fiiLAZEG:,,_i.,
A 3 elevs N
;1' "_ ._ o
W�n1:. .,: z�`r�-7i,��$.���,F n.t2).`3� ,i5-'.1,.. �`�� ,1, GG"11f±111-„�..�.• .�i , . . . ... . t.
5. INSULATION: R20 SPRAYFOAM @ CONDITINED ROOF DECK, &ATTIC SEPARATING KNEE WALLS @PORCHES&GARAGES. � „ � � �
1B/1T D.SWING,GLAZED o E
•,,, R-13 BATT @GARAGE SEPARATING WALL, FLOOR TO CLG. PROVIDE ACCESS HATCH TO CONNECT ATTIC SPACES. A-4 elect/plumb plan "� ;' o � E .a
W2 35.7,-38.7 6-3 8 9 8-0 CC LINTEL 8F24-1B/1T TRIP FIXED W/ARCH OWNER SUPPLIED a D2 34.1 36 1 6 0 8-0 CC LINTEL SRF22 , V k „
..,. ,a,. .,,. , . � , ,a„L .. 61 N EL.BNtl:22.1 _ :, S.SWING � EI}� , . r .,_.... MITT P DUCT LAYOUT Q o
,.. ,.,.. ... .��p.,. ., ,.. .,i,.,,,.,,,.,, , ,,.;, ,..,. .:. D3 34'1 3 ...2.-$,:,, ,$•fl.. .CC,U...T ..,.�/, ,,, .r.,. . , „ ...,.. ^, .R ._, . .. ,... ., 6. DEFFERED SUBMITTALS: ROOF TRUSSES, SITE LAN, -
��P$�,k �,�,I de;.C{r�U��e�r$Pw .K%. ., fi�r.��4UN�v s.mw,2,d: v.l,., ,.1EE�S,.., ,,,,u F, I„kua r-..,, ,w ... . -,.
_ r _-; 4- „ �° GN 1 general notes + iE Co � m
W4 357 387 28 52 8-0 CC LINTEL8F2418/1T SHUNG EGRESS D4 341 361 9-0 8-0 CC LINTEL8F2418/2T SECTIONAL OVERHEAD ,^ C � M
��/ 3 3S 9-0,-;' E . CG�INTEL�3�2416/27.,,. � '}5EGIIONALO
i,v ,�,5�i, 3'a'7„�9;77/:.,1 42,, "4.r :, 3,- .Ir�r..1+ +F`�,'E.,17.^�'tr;tirnr24-.�. �'.. 4 �t , x l;5, „L< :,.�i , rv . ,. •, !. �.,, D `�. ..a..,,-. k>,...... .. < a., __�-... , _ —
W6 35.7,-38.7 4-4 6-3 8-0 CC LINTEL8F24-1B/1T FIXED OWNER SUPPLIED D6 31.3,-35.5 2-6 8-0 CC LINTEL8RF22-1B/1T S.SWING,GLAZED a lh ti n W
W,7,l,,r;a3IX",3$�3„',,,i ,,NlimGdi+lr" t,'.it 'r.vCCL;1NFEL-$ 7416fi,,, ,t FGXEDr- r,,, ),I, „'' OU/t�Eft.SUPPLIEd), ? SEE GEN NOTE 26. CC:CAST CRETE pg cl1 �
W8 35 7 38 7 4-4 6 3 8-0 CC LINTEL 8F24 1B/1T FIXED OWNER SUPPLIED O co co LL_
PROJECT DESCRIPTION J U z
78 �� DOUR AREA CALCULATIONS:
38 7 (2)4-0 5 2 8 0 CC LINTEL 8F24 1B/1T S HUNG NEW CONSTRUCTION OF A 1 STORY SF
W10 35 7
conditioned living area 3,436 sf RESIDENCE ON A VACANT LOT.
EEL
:,2 2�;.P�,,rD,ti I,'I §? nh'� R,t , it �.� .;� 011!/NER,SI�PIIfA��
W12 35 7 8.7 5-4 5-4 8 0 CC LINTEL 8F24-1B/1T GLASS BLOCK garage 576 sf ZONING INFORMATION:
3, • . '.* S 2. ,'it�I_a" s`COUAITBs�_. ,. .E!U :� !�;k , ,•..,,-ELfE?S. ., ., .?! C• covered rear porch 738 sf
parcel id: 1418-133-0040-000-7
covered front porch 266 sf AR-1 (unincorporated St Lucie County)
W14 35.7,47.7 3-0 5-2 8-0 CC LINTEL8F24-1B/1T IS.HUNG ITEMP
total building area 5,076 sf flood zone:X
SEE GEN NOTE 26. CC:CAST CRETE
conditioned volume 34,360 cf
UTILITY INFORMATION:
gas: n/a
sewage: septic w
potable water public a
61
LL_
U
W
12'-51/2" • - �" 8'-11" 2'-9" r
o
3 o
w
O
SLOPE AS PER ELEVATIONS o
I ¢
0
�qCL I ROOF/UNDERLAYMENT/SHEATHING AS PER GENERAL SPECS W
o w
J
13'-8 1/ 6'-10" 8'4" '1 PE TRUSS AS PER FRAMING PLANS- w
\\ � i INSULATION AS PER GENERAL SPECSLo
, Q}
N^ LU
BR.3
SK i� SEE FRAMING PLANS OR CONNECTOR SCHEDULE W o
4 _ u —
BR.2 I SEE E ELEVS
7
' Y i [� \ CL N METAL DRIP OVER PT WOOD DRIP OVER ' r' W U a
w
n CLG AS PER GENERAL SPECS&FLOOR PLAN ® o
1l z
r7
®® n V
J 12 10" I Zx8 CEDAR FASC16d TRUSS ENDS W/(2) 2 � !; (�� m
13'-8 1/ -4" 6'-1 #16d NAIL,5"TRUSS HEEL
2 8x 24x8A ( REF AS PER GENERALI& �+
MASONRY BOND MASONRY BOND B
S2
di ,;.„ •7;,;.+�,,. , I EXTERIOR SOFFIT AS PER GENERAL SPECS SPECS 0 o
i N da
G- N ( SVERT REBTUCCO IAR @ 48DOC,CONTO BOND BEAM TOP 2VER 8x8x16 CMU /) I I � w
- - - - COURSES W/#5 REBAR EA COURSE-51 OR 1/2"GWB '� a
- - - - - - - - OVER R4.1 FOIL INSULATION OVER 314"FURRING STRIP. W
N a
LI_ w
x
WALL REINF AS PER GENERAL SPECS- O m
I m SPLICING AS PER GENERAL NOTES "L
SOG/FILUCOMPCTION AS PER w
FOUNDATON PLAN AND L
I I 8"x8"THICKNED EDGE W/(1)CONT#5 GENERAL NOTES
O
� N W W � f
z s
cIg.10'-0"typ LIVING � i
fV z
I o- STEM WALL:8x8x16 CMU W/#5 VERT z
I o REBAR @ 48"OC
w
REAR
PORCH
T-8" i GRADE AS PER SITE PLAN
0
I
3 r y
Z_ Fit
I I ;
FRONT _ I z
24" .. . c1
I PORCH —�
dg.12.-0., o
N TYP WALL SECTION o
(O � D2
J
z ? I SCALE:V2"=1'-0"
� I o
I
I I
3 2'-1 4' 10, '
c1g.11• n
I
SK O O 9 D3
2-8xe-0
I
I DINING o 0 4 I-
�rJ_ KI CHEN dg.11-o" x x o
CLST � tyb � �
ro O
izOL 1 - - - - - -I U
4-0x8-0 WALL LEGEND THICKNESS
m CLST ON FLOOR
� � Q ID DESORPTION SPECS PLAN
-"�.'� N 5'S" R. REINFORCED CMU WALL -
W/FINISHES SEE TYP WALL SETCTION 9
Pam ' ( j REINFORCED CMU WALL floor Ian
s'-11 yr � GA. GE GARAGE W/O INT FINISH SEE TYP WALL SETCTION S. p
6'-41/2" 3' i : Q RA
IE
REINFORCED CMU COLUMN SEE FLOOR PLAN VARIES
9i\J 7/26/20
1 i(�r��� � NON LOAD BEARING INT WALL SEE GENERAL SPECS ON A-1 4.5" SHEET
2-4x8-O
WEIR A MBA " LOAD BEARING 4 WALL BR WALL DETAIL 4.5"
r' - - - oEc il
O B G2x SEE G E A
DEN - - - - - - - - - - - a - - - - - - - - - - - a
� SK
24x8-0
C T C$ N BA.M
' F LST SWR
17'-4" 6'4 1!2" T T- 4" '�' 13'-9 112" 4'-71l2" 3' /11'-$3/4" \ / 111314"\
FLOOR PLAN NOTES:
D6 DS D4 1.INTERIOR DIMENSIONS ARE TO FINISH
W 4 W 3 W 2 W 1 W 0 m 2.EXTERIOR DIMENSIONS ARE TO STRUCTURE
�� F'F��R
4_3^ 10'-4" Ic; 20'-73/4' T-61/2" , r-�" 10'-111/4" ;� 13'-91l4" 3'-61/2" 9' 2' 9' 2'-4' FLOOR PLAN KEYNOTES: -' NClS P.ClFe '9
1.22"x30"RO MIN ATTICACCESS
•», ,, �. 931 " 2.DRIVEWAY PER SITE PLAN TO SERVE AS LANDING.
3.TYP PORCH COLUMN:12"x12"x8"CMU,4#5 VERT. o AR97108
4.TYP FRONT PORCH LINTEL:CASTCRETE 8F24-16/1T.12'TOB. �,FLOOR PLAN 5.TYP REAR PORCH LINTEL:CASTCRETE 8F16-1 B/2T.10'TOB.
'sTFRED,ARG��
SCALE: 114"=T-O"
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: CHAMBERS RESIDENCE Builder Name: COLE CONSTRUCTION SERVICES,LLC.
Street: 4700 INDRIO ROAD Permit Office: ST LUCIE COUNTY
City,State,Zip: FORT PIERCE,FL,34951 Permit Number:
Owner: ROSS AND NORANN CHAMBERS Jurisdiction: ST LUCIE COUNTY
Design Location: FL,Fort Pierce County: St.Lucie(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types (2574.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul,Exterior R=4.1 2358.00 ft2
b.Frame-Wood,Adjacent R=13.0 216.00 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 3 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (3436.0 sqft.) Insulation Area a.Roof Deck(Unvented) R=20.0 3436.00 ft2
6. Conditioned floor area above grade(ft2) 3436 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11.Ducts R ft2
7. Windows(469.3 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 6 150
a. U-Factor: Sgl,U=0.32 136.33 ft2 b.Sup: Attic,Ret:Attic,AH:Attic 6 130
SHGC: SHGC=0.22
b. U-Factor: Sgl,U=0.34 84.00 ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.22 a.Central Unit 35.2 SEER:16.00
b.Central Unit 24.0 SEER:16.00
c. U-Factor: Sgl,U=0.30 78.00 ft2
SHGC: SHGC=0.24 13.Heating systems kBtu/hr Efficiency
d. U-Factor: other(see details) 171.00 ft2 a.Electric Strip Heat 27.0 COP:1.00
SHGC: other(see details) b.Electric Strip Heat 17.0 COP:1.00
Area Weighted Average Overhang Depth: 8.452 ft.
Area Weighted Average SHGC: 0.230 14.Hot water systems
8. Floor Types (3436.0 sqft.) Insulation Area a.Electric Cap:50 gallons
EF:0.980
a.Slab-On-Grade Edge Insulation R=0.0 3436.00 ft2 b. Conservation features
b.N/A R= ft2 None
c.N/A R= ft2 15.Credits None
Glass/Floor Area: 0.137
Total Proposed Modified Loads: 97.23 PASS
Total Baseline Loads: 98.48
1 hereby certify that the plans and specifications covered by Review of the plans and COD ME
this calculation are in compliance with the Florida Energy specifications covered by this
Code. calculation indicates compliance • .Q
with the Florida Energy Code. " G
PREPARED BY: Before construction is completed
DATE: 7-31-20 this building will be inspected for 10
compliance with Section 553.908
I hereby certify that this building, as designed, is in compliance Florida Statutes. j+
with the Florida Energy Code. OE�NE2�'�y�
OWNER/AGENT: BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires
an envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2).
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 7
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: CHAMBERS RESIDENCE Bedrooms: 3 Address Type: Street Address
Building Type: User Conditioned Area: 3436 Lot#
Owner Name: ROSS AND NORANN CHAM Total Stories: 1 Block/Subdivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: COLE CONSTRUCTION SER Rotate Angle: 0 Street: 4700 INDRIO ROAD
Permit Office: ST LUCIE COUNTY Cross Ventilation: No County: St.Lucie
Jurisdiction: ST LUCIE COUNTY Whole House Fan: No City,State,Zip: FORT PIERCE,
Family Type: Single-family FL, 34951
New/Existing: New(From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
v Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL VERO BEACH MUNI 39 90 70 75 299 62 Low
BLOCKS
Number Name Area Volume
1 AHU 1 2061 18549
2 AHU 2 1375 12375
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 BEDROOM 3 210 1890 No 0 1 1 Yes Yes Yes
2 WIC 3 49 441 No 0 1 Yes Yes Yes
3 BATH 3 56 504 No 0 1 No Yes Yes
4 BATH 2 56 504 No 0 1 Yes Yes Yes
5 BEDROOM 2 247 2223 No 0 1 1 Yes Yes Yes
6 HALL 57 513 No 0 1 Yes Yes Yes
7 FOYER 80 720 No 0 1 Yes Yes Yes
8 PANTRY 96 864 No 0 1 Yes Yes Yes
9 LIVING 448 4032 No 0 1 Yes Yes Yes
10 WIC 56 504 No 0 1 Yes Yes Yes
11 WIC 2 49 441 No 0 1 No Yes Yes
12 KITCHEN 304 2736 Yes 0 1 No Yes Yes
13 DINING 353 3177 No 0 1 Yes Yes Yes
14 MASTER BEDROO 410 3690 No 0 1 1 Yes Yes Yes
15 M WIC 1 105 945 No 0 1 Yes Yes Yes
16 M WIC 2 42 378 No 0 1 Yes Yes Yes
17 M BATH 229 2061 No 0 1 Yes Yes Yes
18 M TOILET 28 252 No 0 1 No Yes Yes
19 HALLWAY 60 540 No 0 1 No Yes Yes
20 DEN 258 2322 No 0 1 Yes Yes Yes
21 DEN CLST 27 243 No 0 1 No Yes Yes
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 7
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
22 BATH 4 50 450 No 0 1 Yes Yes Yes
23 UTILITY 166 1494 No 0 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulation BEDROOM 3 37 ft 0 210 ft2 ---- 1 0 0
2 Slab-On-Grade Edge Insulation WIC 3 7 ft 0 49 ft2 ---- 1 0 0
3 Slab-On-Grade Edge Insulation BATH 3 1 ft 0 56 ft2 --_- 1 0 0
4 Slab-On-Grade Edge Insulation BATH 2 8 ft 0 56 ft2 ---- 1 0 0
5 Slab-On-Grade Edge Insulation BEDROOM 2 31 ft 0 247 ft2 ---- 1 0 0
6 Slab-On-Grade Edge Insulation HALL 3 ft 0 57 ft2 ---- 1 0 0
7 Slab-On-Grade Edge Insulation FOYER loft 0 80 ft2 --_- 1 0 0
8 Slab-On-Grade Edge Insulation PANTRY 12 ft 0 96 ft2 ---- 1 0 0
9 Slab-On-Grade Edge Insulation LIVING 22 ft 0 448 ft2 ---- 1 0 0
10SIab-On-Grade Edge Insulation WIC 7 ft 0 56 ft2 ---- 1 0 0
11SIab-On-Grade Edge Insulation WIC 2 1 ft 0 49 ft2 ---- 1 0 0
12SIab-On-Grade Edge Insulation KITCHEN 1 ft 0 304 ft2 ---- 1 0 0
13Slab-On-Grade Edge Insulation DINING 19 ft 0 353 ft2 ---- 1 0 0
14SIab-On-Grade Edge Insulation MASTER BEDRO 45 ft 0 410 ft2 ---- 1 0 0
15SIab-On-Grade Edge Insulation M W IC 1 7 ft 0 105 ft2 ---- 1 0 0
16SIab-On-Grade Edge Insulation M W IC 2 6 ft 0 42 ft2 ---- 1 0 0
17Slab-On-Grade Edge Insulation M BATH 15 ft 0 229 ft2 ---- 1 0 0
18SIab-On-Grade Edge Insulation M TOILET 1 ft 0 28 ft2 ---- 1 0 0
19SIab-On-Grade Edge Insulation HALLWAY 1 ft 0 60 ft2 ---- 1 0 0
20SIab-On-Grade Edge Insulation DEN 15 ft 0 258 ft2 ---- 1 0 0
21SIab-On-Grade Edge Insulation DEN CLST 1 ft 0 27 ft2 ---- 1 0 0
22SIab-On-Grade Edge Insulation BATH 4 5 ft 0 50 ft2 ---- 1 0 0
23SIab-On-Grade Edge Insulation UTILITY 13 ft 0 166 ft2 --_- 1 0 0
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 3 of 7
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
ROOF
Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Hip Metal 3843 ft2 0 ft2 Light N 0.2 No 0.9 No 20 26.6
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Unvented 0 3436 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Unvented) BEDROOM 3 0 Blown 210 ft2 0.1 Wood
2 Under Attic(Unvented) WIC 3 0 Blown 49 ft2 0.1 Wood
3 Under Attic(Unvented) BATH 3 0 Blown 56 ft2 0.1 Wood
4 Under Attic(Unvented) BATH 2 0 Blown 56 ft2 0.1 Wood
5 Under Attic(Unvented) BEDROOM 2 0 Blown 247 ft2 0.1 Wood
6 Under Attic(Unvented) HALL 0 Blown 57 ft2 0.1 Wood
7 Under Attic(Unvented) FOYER 0 Blown 80 ft2 0.1 Wood
8 Under Attic(Unvented) PANTRY 0 Blown 96 ft2 0.1 Wood
9 Under Attic(Unvented) LIVING 0 Blown 448 ft2 0.1 Wood
10 Under Attic(Unvented) WIC 0 Blown 56 ft2 0.1 Wood
11 Under Attic(Unvented) WIC 2 0 Blown 49 ft2 0.1 Wood
12 Under Attic(Unvented) KITCHEN 0 Blown 304 ft2 0.1 Wood
13 Under Attic(Unvented) DINING 0 Blown 353 ft2 0.1 Wood
14 Under Attic(Unvented) MASTER BEDRO 0 Blown 410 ft2 0.1 Wood
15 Under Attic(Unvented) M W IC 1 0 Blown 105 ft2 0.1 Wood
16 Under Attic(Unvented) M W IC 2 0 Blown 42 ft2 0.1 Wood
17 Under Attic(Unvented) M BATH 0 Blown 229 ft2 0.1 Wood
18 Under Attic(Unvented) M TOILET 0 Blown 28 ft2 0.1 Wood
19 Under Attic(Unvented) HALLWAY 0 Blown 60 ft2 0.1 Wood
20 Under Attic(Unvented) DEN 0 Blown 258 ft2 0.1 Wood
21 Under Attic(Unvented) DEN CLST 0 Blown 27 ft2 0.1 Wood
22 Under Attic(Unvented) BATH 4 0 Blown 50 ft2 0.1 Wood
23 Under Attic(Unvented) UTILITY 0 Blown 166 ft2 0.1 Wood
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
o
1 N Exterior Concrete Block-Int InsuBEDROOM 3 4.1 15 0 9 0 135.0 ft2 0 0 0.2 0
2 S Exterior Concrete Block-Int InsuBEDROOM 3 4.1 8 0 9 0 72.0 ft2 0 0 0.2 0
3 W Exterior Concrete Block-Int InsuBEDROOM 3 4.1 14 0 9 0 126.0 ft2 0 0 0.2 0
4 N Exterior Concrete Block-Int Insul WIC 3 4.1 7 0 9 0 63.0 ft2 0 0 0.2 0
5 N Exterior Concrete Block-Int Insul BATH 2 4.1 8 0 9 0 72.0 ft2 0 0 0.2 0
6 N Exterior Concrete Block-Int InsuBEDROOM 2 4.1 14 0 9 0 126.0 ft2 0 0 0.2 0
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 4 of 7
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Belowo
To Wall Type
7 E Exterior Concrete Block-Int InsuBEDROOM 2 4.1 17 0 9 0 153.0 ft2 0 0 0.2 0
8 W Exterior Concrete Block-Int Insul HALL 4.1 3 0 9 0 27.0 ft2 0 0 0.2 0
9 W Exterior Concrete Block-Int Insul FOYER 4.1 10 0 9 0 90.0 ft2 0 0 0.2 0
10 W Exterior Concrete Block-Int Insul PANTRY 4.1 12 0 9 0 108.0 ft2 0 0 0.2 0
11 N Exterior Concrete Block-Int Insul LIVING 4.1 6 0 9 0 54.0 ft2 0 0 0.2 0
12 E Exterior Concrete Block-Int Insul LIVING 4.1 16 0 9 0 144.0 ft2 0 0 0.2 0
13 W Exterior Concrete Block-Int Insul WIC 4.1 7 0 9 0 63.0 ft2 0 0 0.2 0
14 N Exterior Concrete Block-Int Insul DINING 4.1 11 0 9 0 99.0 ft2 0 0 0.2 0
15 E Exterior Concrete Block-Int Insul DINING 4.1 8 0 9 0 72.0 ft2 0 0 0.2 0
16 N Exterior Concrete Block-Int InsuMASTER BE 4.1 8 0 9 0 72.0 ft2 0 0 0.2 0
17 S Exterior Concrete Block-Int InsuMASTER BE 4.1 18 0 9 0 162.0 ft2 0 0 0.2 0
18 W Exterior Concrete Block-Int InsuMASTER BE 4.1 19 0 9 0 171.0 ft2 0 0 0.2 0
19 S Exterior Concrete Block-Int Insul M W IC 1 4.1 7 0 9 0 63.0 ft2 0 0 0.2 0
20 S Exterior Concrete Block-Int Insul M W IC 2 4.1 6 0 9 0 54.0 ft2 0 0 0.2 0
21 S Exterior Concrete Block-Int Insul M BATH 4.1 15 0 9 0 135.0 ft2 0 0 0.2 0
22 S Exterior Concrete Block-Int Insul DEN 4.1 15 0 9 0 135.0 ft2 0 0 0.2 0
23 S Exterior Concrete Block-Int Insul BATH 4 4.1 5 0 9 0 45.0 ft2 0 0 0.2 0
24 N Exterior Concrete Block-Int Insul UTILITY 4.1 9 0 9 0 81.0 ft2 0 0 0.2 0
25 S Exterior Concrete Block-Int Insul UTILITY 4.1 4 0 9 0 36.0 ft2 0 0 0.2 0
26 E Garage Frame-Wood UTILITY 13 24 0 9 0 216.0 ft2 0 0.1 0.2 0
WINDOWS
Orientation shown is the entered,Proposed orientation.
Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 N 1 Vinyl Low-E Single Yes 0.32 0.22 Y 15.0 ft2 2 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
2 W 3 Vinyl Low-E Single Yes 0.3 0.24 Y 54.0 ft2 2 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
3 N 6 Vinyl Low-E Single Yes 0.32 0.22 Y 30.0 ft2 2 ft 0 in 1 ft 4 in None None
4 W 9 Vinyl Low-E Single Yes 0.65 0.22 Y 48.0 ft2 10 ft 0 in 1 ft 4 in None None
5 E 12 Vinyl Low-E Single Yes 0.31 0.24 Y 18.0 ft2 20 ft 0 in 1 ft 4 in None None
6 E 12 Vinyl Low-E Single Yes 0.34 0.22 Y 48.0 ft2 20 ft 0 in 1 ft 4 in None None
7 N 14 Vinyl Low-E Single Yes 0.65 0.25 Y 48.0 ft2 20 ft 0 in 1 ft 4 in None None
8 E 15 Vinyl Low-E Single Yes 0.3 0.24 Y 24.0 ft2 20 ft 0 in 1 ft 4 in None None
9 S 17 Vinyl Low-E Single Yes 0.32 0.22 Y 30.0 ft2 2 ft 0 in 1 ft 4 in None None
10 W 18 Vinyl Low-E Single Yes 0.34 0.22 Y 36.0 ft2 2 ft 0 in 1 ft 4 in None None
11 S 21 Vinyl Low-E Single Yes 0.31 0.24 Y 12.0 ft2 2 ft 0 in 1 ft 4 in None None
12 S 21 Vinyl Low-E Single Yes 0.31 0.24 Y 25.0 ft2 2 ft 0 in 1 ft 4 in None None
13 S 22 Vinyl Low-E Single Yes 0.32 0.22 Y 40.0 ft2 2 ft 0 in 1 ft 4 in None None
14 N 24 Vinyl Low-E Single Yes 0.32 0.22 Y 21.3 ft2 2 ft 0 in 1 ft 4 in None None
15 S 25 Vinyl Low-E Single Yes 0.65 0.25 Y 20.0 ft2 10 ft 0 in 1 ft 4 in None None
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 5 of 7
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 576 ft2 576 ft2 24 ft 9 ft 13
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 W holehouse Proposed ACH(50) .0004 3607.8 198.06 372.49 .1454 7
HEATING SYSTEM
# System Type Subtype Speed Efficiency Capacity Block Ducts
1 Electric Strip Heat/ None COP:1 27 kBtu/hr 1 sys#1
2 Electric Strip Heat/ None COP:1 17 kBtu/hr 2 sys#2
COOLING SYSTEM
# System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split Single SEER: 16 35.2 kBtu/hr 1056 cfm 0.8 1 sys#1
2 Central Unit/ Split Single SEER: 16 24 kBtu/hr 720 cfm 0.8 2 sys#2
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None UTILITY 0.98 50 gal 62.3 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
----Supply---- ----Return---- Air CFM 25 CFM25 HVAC#
v # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool
1 Attic 6 150 ft2 Attic 15 ft2 Default Leakage Attic (Default)c(Default)c 1 1
2 Attic 6 130 ft2 Attic 13 ft2 Default Leakage Attic (Default)c(Default)c 2 2
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 6 of 7
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
TEMPERATURES
Programable Thermostat: N Ceiling Fans: rjCooling Jan Feb Mar Apr I May
Jun
Nov Dec
VentinHeating H Jan H Feb X Mar A Jan Feb Mar pr May Jun rj
Jul rj
Aug �Xj
Sep �A Oct Nov Dec
Oct Oct xJ Nov Dec
Jun Jul Aug Sep
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 80 80 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 80 80 78 78 78 78 78 78 78 78
Heating(WD) AM 65 65 65 65 65 65 65 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 68 68
Heating(WEH) AM 65 65 65 65 65 65 65 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 68 68
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 Ibs/sq.ft. 0 ft2 Oft 0.3 BEDROOM 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 WIC 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 BATH 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 BATH 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 BEDROOM 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 HALL
Default(8 Ibs/sq.ft. ft2 ft 0.3 FOYER
Default(8 Ibs/sq.ft. ft2 ft 0.3 PANTRY
Default(8 Ibs/sq.ft. ft2 ft 0.3 LIVING
Default(8 Ibs/sq.ft. ft2 ft 0.3 WIC
Default(8 Ibs/sq.ft. ft2 ft 0.3 WIC 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 KITCHEN
Default(8 Ibs/sq.ft. ft2 ft 0.3 DINING
Default(8 Ibs/sq.ft. ft2 ft 0.3 MASTER BEDROO
Default(8 Ibs/sq.ft. ft2 ft 0.3 M W IC 1
Default(8 Ibs/sq.ft. ft2 ft 0.3 M W IC 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 M BATH
Default(8 Ibs/sq.ft. ft2 ft 0.3 M TOILET
Default(8 Ibs/sq.ft. ft2 ft 0.3 HALLWAY
Default(8 Ibs/sq.ft. ft2 ft 0.3 DEN
Default(8 Ibs/sq.ft. ft2 ft 0.3 DEN CLST
Default(8 Ibs/sq.ft. ft2 ft 0.3 BATH 4
Default(8 Ibs/sq.ft. ft2 ft 0.3 UTILITY
7/30/2020 12:31 PM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 7 of 7
This document was created with Win2PDF available at http://www.win2pdf.com.
The unregistered version of Win2PDF is for evaluation or non-commercial use only.
This page will not be added after purchasing Win2PDF.
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 99
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition 1. New(From Plans) 12. Ducts, location & insulation level
a) Supply ducts R 6.0
2. Single-family or multiple-family 2. Single-family b) Return ducts R 6.0
c)AHU location Attic
3. No. of units (if multiple-family) 3. 1
4. Number of bedrooms 4. 3 13. Cooling system: Capacity 59.2
a) Split system SEER 16.0
5. Is this a worst case? (yes/no) 5. No b)Single package SEER
c)Ground/water source SEER/COP
6. Conditioned floor area (sq. ft.) 6. 3436 d) Room unit/PTAC EER
e)Other
7. Windows, type and area
a) U-factor:(weighted average) 7a. 0.401
b)Solar Heat Gain Coefficient(SHGC) 7b. 0.230 14. Heating system: Capacity 44.0
c)Area 7c. 469.3 a) Split system heat pump HSPF
b) Single package heat pump HSPF
8. Skylights c) Electric resistance COP 1.0
a) U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE
b) Solar Heat Gain Coefficient(SHGC) 8b. NA e) Gas furnace, LPG AFUE
f)Other
9. Floor type, insulation level:
a) Slab-on-grade(R-value) 9a. 0.0
b)Wood, raised (R-value) 9b. 15. Water heating system
c)Concrete, raised (R-value) 9c. a) Electric resistance EF 0.98
b) Gas fired, natural gas EF
10. Wall type and insulation: c) Gas fired, LPG EF
A. Exterior: d) Solar system with tank EF
1. Wood frame(Insulation R-value) 10A1. e) Dedicated heat pump with tank EF
2. Masonry(Insulation R-value) 10A2. 4.1 f) Heat recovery unit HeatRec%
B. Adjacent: g) Other
1. Wood frame(Insulation R-value) 10B1. 13.0
2. Masonry(Insulation R-value) 10132.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level a) Ceiling fans
a) Under attic 1 la. 0.0 b) Cross ventilation No
b) Single assembly 11 b. c)Whole house fan No
c) Knee walls/skylight walls 11 c. d) Multizone cooling credit
d) Radiant barrier installed 11 d. No e) Multizone heating credit
f) Programmable thermostat No
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature: Date:
Address of New Home: 4700 INDRIO ROAD City/FL Zip: FORT PIERCE, FL 34951
7/30/2020 12:32:24 PM EnergyGauge®USA 6.0.04(Rev. 1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
This document was created with Win2PDF available at http://www.win2pdf.com.
The unregistered version of Win2PDF is for evaluation or non-commercial use only.
This page will not be added after purchasing Win2PDF.
MIJ�.� N� t*,a alo1 rr Project SummaryJob:
Date: Jul 30,2020
AHU 1 By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
Project • •
For: CHAMBERS RESIDENCE, COLE CONSTRUCTION SERVICES, LLC.
4700 INDRIO ROAD, FORT PIERCE, FL 34951
Notes:
Design Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 28 °F Design TD 15 °F
Daily range M
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 18878 Btuh Structure 17899 Btuh
Ducts 6031 Btuh Ducts 8635 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 24909 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipmenf sensible load 25207 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 3423 Btuh
Ducts 2381 Btuh
Central vent (0 cfm) 0 Btuh
Heating Cooling (none)
Area (ft2) 2061 2061 Equipment latent load 5804 Btuh
Volume (ft3) 18549 18549
Air changes/hour 0.28 0.15 Equipment Total Load (Sen+Lat) 31011 Btuh
Equiv.AVF (cfm) 86 46 Req. total capacity at 0.70 SHR 3.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Trane
Trade Trade TRANE
Model Cond 4TTR6036J 1
AHRI ref Coil TEM4AOC37S31++TDR
AHRI ref 201763705
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input 6.5 kW Sensible cooling 24640 Btuh
Heating output 22349 Btuh Latent cooling 10560 Btuh
Temperature rise 17 °F Total cooling 35200 Btuh
Actual air flow 1173 cfm Actual air flow 1173 cfm
Air flow factor 0.047 cfm/Btuh Air flow factor 0.044 cfm/Btuh
Static pressure 1.00 in H2O Static pressure 1.00 in H2O
Space thermostat Load sensible heat ratio 0.82
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
nn��lN�zoM® 2020-Jul-30 11:52:19
,qcCd � Right-SuiteO Universal 2019 19.0.08 RSU08101 Page 1
`� ...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S g
MIJ�.� N� t*,a alo1 rr Project SummaryJob:
Date: Jul 30,2020
AHU 2 By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
Project • •
For: CHAMBERS RESIDENCE, COLE CONSTRUCTION SERVICES, LLC.
4700 INDRIO ROAD, FORT PIERCE, FL 34951
Notes:
Design Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 28 °F Design TD 15 °F
Daily range M
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 12741 Btuh Structure 12770 Btuh
Ducts 3132 Btuh Ducts 4543 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 15873 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipmenf sensible load 16447 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 3307 Btuh
Ducts 1211 Btuh
Central vent (0 cfm) 0 Btuh
Heating Coolingg (none)
Area (ft2) 1375 1375 Equipment latent load 4518 Btuh
Volume (ft3) 12375 12375
Air changes/hour 0.28 0.15 Equipment Total Load (Sen+Lat) 20965 Btuh
Equiv.AVF (cfm) 58 31 Req. total capacity at 0.70 SHR 2.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Trane
Trade Trade TRANE
Model Cond 4TTR40251-1
AHRI ref Coil TEM6AOB24H21++TDR
AHRI ref 7567540
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input 4.2 kW Sensible cooling 16800 Btuh
Heating output 14376 Btuh Latent cooling 7200 Btuh
Temperature rise 16 °F Total cooling 24000 Btuh
Actual air flow 800 cfm Actual air flow 800 cfm
Air flow factor 0.050 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 1.00 in H2O Static pressure 1.00 in H2O
Space thermostat Load sensible heat ratio 0.79
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
nn��lN�zoM® 2020-Jul-30 11:52:19
,qcCd � Right-SuiteO Universal 2019 19.0.08 RSU08101 Page 2
`� ...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S g
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name AHU 1 BEDROOM 3
2 Exposed wall 156.0 ft 37.0 ft
3 Room height 9.0 ft 9.0 ft heat/cool
4 Room dimensions 15.0 x 14.0 ft
5 Room area 2061.0 ft2 210.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 549 456 1826 998 135 120 480 263
2 glazing,clr low-e 0.320 n 8.96 9.41 30 0 269 282 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 48 0 430 452 0 0 0 0
11 2 glazing,clr low-e 0.320 n 8.96 6.00 15 0 134 90 15 0 134 90
V�/ 13A-40cs 0.143 e 4.00 2.19 369 279 1117 610 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 18 1 161 449 0 0 0 0
2 glazing,clr low-e 0.320 a 8.96 24.95 72 4 645 1796 0 0 0 0
13A40cs 0,143 s 4.00 2.19 72 72 288 158 72 72 288 158
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 13A-40cs 0,143 w 4.00 2.19 414 312 1249 683 126 72 288 158
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 48 2 430 1209 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 14.69 54 2 484 793 54 2 484 793
C 16X19-0md 0.408 1.59 1.37 2061 2061 3268 2820 210 210 333 287
F 22A-tph 1,358 38.02 0.00 2061 156 5932 0 210 37 1407 0
6 c)AED excursion 0 374
Envelope loss/gain 16234 10340 3415 2123
12 a) Infiltration 2644 759 627 180
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 6800 0
Subtotal(lines 6 to 13) 18878 17899 4042 2303
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 62 24
14 Subtotal 18878 17899 4104 2327
15 Duct loads 32% 48% 6031 8635 32% 48% 1311 1122
FFTotal room load 24909 26534 5416 3449
Air required(cfm) 1173 1173 255 152
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 1
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name WIC 3 BATH 3
2 Exposed wall 7.0 ft 0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 7.0 x 7.0 ft 8.0 x 7.0 ft
5 Room area 49.0 ft2 56.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 63 63 252 138 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 8.96 6.00 0 0 0 0 0 0 0 0
V�/ 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 2 glazing,
0.320 w 4.00 2.00 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 14.69 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 49 49 78 67 56 56 89 77
F 22A-tph 1,358 38.02 0.00 49 7 266 0 56 0 0 0
6 c)AED excursion -17 -26
Envelope loss/gain 596 188 89 51
12 a) Infiltration 119 34 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 300
Subtotal(lines 6 to 13) 715 222 89 351
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 71 28
14 Subtotal 715 222 160 378
15 Duct loads 32% 48% 228 107 32% 48% 51 182
Total room load 943 330 211 560
Air required(cfm) 44 15 10 25
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 2
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name BATH 2 BEDROOM 2
2 Exposed wall 8.0 ft 31.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 8.0 x 7.0 ft 1.0 x 247.0 ft
5 Room area 56.0 ft2 247.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-40cs 0.143 n 4.00 2.19 72 72 288 158 126 96 384 210
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 30 0 269 282
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
1 1 2 glazing,clr low-e 0.320 n 8.96 6.00 0 0 0 0 0 0 0 0
V)/ 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 153 153 613 335
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 2 glazing,
0.320 w 4.00 2.00 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 14.69 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 56 56 89 77 247 247 392 338
F 22A-tph 1,358 38.02 0.00 56 8 304 0 247 31 1179 0
6 c)AED excursion 40 -112
Envelope loss/gain 681 194 2836 1053
12 a) Infiltration 136 39 525 151
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 300 300
Subtotal(lines 6 to 13) 817 533 3362 1504
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 27 10
14 Subtotal 817 533 3388 1514
15 Duct loads 32% 48% 261 257 32% 48% 1082 730
Total room load 1078 791 4471 2245
Air required(cfm) 51 35 211 99
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 3
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name HALL FOYER
2 Exposed wall 3.0 ft 10.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 19.0 x 3.0 ft 8.0 x 10.0 ft
5 Room area 57.0 ft2 80.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 8.96 6.00 0 0 0 0 0 0 0 0
V�/ 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 13A-40cs 0,143 w 4.00 2.19 27 27 108 59 90 42 168 92
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 0 0 0 0 48 2 430 1209
2 glazing,clr low-e 0.320 w 8.96 14.69 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 57 57 90 78 80 80 127 109
F 22A-tph 1,358 38.02 0.00 57 3 114 0 80 10 380 0
6 c)AED excursion -11 466
Envelope loss/gain 313 127 1105 1876
12 a) Infiltration 51 15 169 49
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 300
Subtotal(lines 6 to 13) 363 141 1275 2225
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution -363 -141 71 28
14 Subtotal 0 0 1346 2253
15 Duct loads 32% 48% 0 0 32% 48% 430 1087
FFTotal room load 0 0 1776 3339
Air required(cfm) 0 0 84 148
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 4
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name PANTRY LIVING
2 Exposed wall 12.0 ft 22.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 8.0 x 12.0 ft 1.0 x 448.0 ft
5 Room area 96.0 ft2 448.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 54 54 216 118
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 8.96 6.00 0 0 0 0 0 0 0 0
V�/ 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 144 78 312 171
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 18 1 161 449
2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 48 3 430 1198
13A40cs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 13A-flocs 0,143 w 4.00 2.19 108 108 432 236 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 14.69 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 96 96 152 131 448 448 710 613
F 22A-tph 1,358 38.02 0.00 96 12 456 0 448 22 837 0
6 c)AED excursion -30 -164
Envelope loss/gain 1041 338 2667 2384
12 a) Infiltration 203 58 373 107
b) Room ventilation 0 0 1 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 1800
Subtotal(lines 6 to 13) 1244 396 3040 4291
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 97 38
14 Subtotal 1244 396 3137 4329
15 Duct loads 32% 48% 398 191 32% 48% 1002 2088
Total room load 1642 588 4139 6418
Air required(cfm) 77 26 195 284
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 5
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name WIC WIC 2
2 Exposed wall 7.0 ft 0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 8.0 x 7.0 ft 7.0 x 7.0 ft
5 Room area 56.0 ft2 49.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 8.96 6.00 0 0 0 0 0 0 0 0
V�/ 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 13A-40cs 0,143 w 4.00 2.19 63 63 252 138 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 14.69 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 56 56 89 77 49 49 78 67
F 22A-tph 1,358 38.02 0.00 56 7 266 0 49 0 0 0
6 c)AED excursion -38 -5
Envelope loss/gain 607 176 78 62
12 a) Infiltration 119 34 0 0
b) Room ventilation 0 0 1 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 300 0
Subtotal(lines 6 to 13) 726 511 78 62
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 35 14
14 Subtotal 726 511 113 76
15 Duct loads 32% 48% 232 246 32% 48% 36 37
FFTotal room load 958 757 149 113
Air required(cfm) 45 33 7 5
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 6
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 1 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name KITCHEN DINING
2 Exposed wall 0 ft 19.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 16.0 x 19.0 ft 1.0 x 353.0 ft
5 Room area 304.0 ft2 353.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 99 51 204 112
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 48 0 430 452
11 2 glazing,clr low-e 0.320 n 8.96 6.00 0 0 0 0 0 0 0 0
V�/ 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 72 48 192 105
I; GCI 2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 8.96 24.95 0 0 0 0 24 1 215 599
13A40cs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 0.00 0.00 0 0 0 0 0 0 0 0
W 2 glazing,
0.320 w 4.00 2.00 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 25.20 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 14.69 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 304 304 482 416 353 353 560 483
F 22A-tph 1,358 38.02 0.00 304 0 0 0 353 19 722 0
6 c)AED excursion -167 -232
Envelope loss/gain 482 249 2324 1519
12 a) Infiltration 0 0 322 92
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 2000 1500
Subtotal(lines 6 to 13) 482 2249 2646 3111
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 482 2249 2646 3111
15 Duct loads 32% 48% 154 1085 32% 48% 845 1501
FFTotal room load 636 3333 3491 4612
Air required(cfm) 30 147 164 204
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 7
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 2 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name AHU 2 MASTER BEDROOM
2 Exposed wall 106.0 ft 45.0 ft
3 Room height 9.0 ft 9.0 ft heat/cool
4 Room dimensions 1.0 x 410.0 ft
5 Room area 1375.0 ft2 410.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 153 132 527 288 72 72 288 158
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 21 0 191 201 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
V)/ 13A-40cs 0.143 e 0.00 0.00 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 630 503 2014 1101 162 132 529 289
2 glazing,clr low-e 0.320 s 8.96 9.41 12 12 108 113 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 30 30 269 282 30 30 269 282
2 glazing,clr low-e 0.320 s 8.96 9.41 40 40 358 376 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 25 25 224 235 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 20 20 179 188 0 0 0 0
W 13A-flocs 0.143 w 4.00 2.19 171 135 541 295 171 135 541 295
I;; GCCII 2 glazing,clr low-e 0.320 w 8.96 24.95 36 2 323 898 36 2 323 898
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 1375 1375 2180 1881 410 410 650 561
F 22A-tph 1,358 38.02 0.00 1375 106 4031 0 410 45 1711 0
6 c)AED excursion 195 342
Envelope loss/gain 10944 6054 4310 2825
12 a) Infiltration 1797 516 763 219
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 6200 1500
Subtotal(lines 6 to 13) 12741 12770 5073 4544
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 17 14
14 Subtotal 12741 12770 5089 4558
15 Duct loads 25% 36% 3132 4543 25% 36% 1251 1621
FFTotal room load 15873 17313 6340 6179
Air required(cfm) 800 800 320 286
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 8
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 2 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name M WIC 1 M WIC 2
2 Exposed wall 7.0 ft 6.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 7.0 x 15.0 ft 6.0 x 7.0 ft
5 Room area 105.0 ft2 42.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
V)/ 13A-40cs 0.143 e 0.00 0.00 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 63 63 252 138 54 54 216 118
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
W 2 glazing,
0.320 w 4.96 2.19 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 105 105 166 144 42 42 67 57
F 22A-tph 1,358 38.02 0.00 105 7 266 0 42 6 228 0
6 c)AED excursion -14 -12
Envelope loss/gain 685 267 511 163
12 a) Infiltration 119 34 102 29
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 500 500
Subtotal(lines 6 to 13) 804 801 613 692
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 804 801 613 692
15 Duct loads 25% 36% 198 285 25% 36% 151 246
FFTotal room load 1001 1086 763 939
Air required(cfm) 501 50 38 43
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 9
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 2 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name M BATH M TOILET
2 Exposed wall 15.0 ft 0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 1.0 x 229.0 ft 7.0 x 4.0 ft
5 Room area 229.0 ft2 28.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
V)/ 13A-40cs 0.143 e 0.00 0.00 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 135 98 392 214 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 12 12 108 113 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 25 25 224 235 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
W 2 glazing,
0.320 w 4.96 2.19 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 229 229 363 313 28 28 44 38
F 22A-tph 1,358 38.02 0.00 229 15 570 0 28 0 0 0
6 c)AED excursion -34 -4
Envelope loss/gain 1657 842 44 34
12 a) Infiltration 254 73 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 1000 200
Subtotal(lines 6 to 13) 1912 1915 44 234
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 41 35 21 18
14 Subtotal 1953 1950 65 252
15 Duct loads 25% 36% 480 694 25% 36% 16 90
FFTotal room load 2433 2643 81 341
Air required(cfm) 1231 122 4 16
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 10
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 2 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name HALLWAY DEN
2 Exposed wall 0 ft 15.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 15.0 x 4.0 ft 1.0 x 258.0 ft
5 Room area 60.0 ft2 258.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
V)/ 13A-40cs 0.143 e 0.00 0.00 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 0 0 0 0 135 95 380 208
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 40 40 358 376
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
W 13A�4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 60 60 95 82 258 258 409 353
F 22A-tph 1,358 38.02 0.00 60 0 0 0 258 15 570 0
6 c)AED excursion -1 -35
Envelope loss/gain 95 81 1718 902
12 a) Infiltration 0 0 254 73
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 1000
Subtotal(lines 6 to 13) 95 81 1972 1975
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution -95 -81 51 43
14 Subtotal 0 0 2023 2018
15 Duct loads 25% 36% 0 0 25% 36% 497 718
FFTotal room load 0 0 2521 2736
Air required(cfm) 0 0 127 126
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 11
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 2 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name DEN CLST BATH 4
2 Exposed wall 0 ft 5.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 9.0 x 3.0 ft 5.0 x 10.0 ft
5 Room area 27.0 ft2 50.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0 0 0 0 0
V)/ 13A-40cs 0.143 e 0.00 0.00 0 0 0 0 0 0 0 0
I; GCI 2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 a 0.00 0.00 0 0 0 0 0 0 0 0
13A40cs 0,143 s 4.00 2.19 0 0 0 0 45 45 180 98
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0 0 0 0 0
W 2 glazing,
0.320 w 4.96 2.19 0 0 0 0 0 0 0 0
I;; GCCII 2 glazing,clr low-e 0.320 w 8.96 24.95 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0 0 0 0 0
C 16X19-0md 0.408 1.59 1.37 27 27 43 37 50 50 79 68
F 22A-tph 1,358 38.02 0.00 27 0 0 0 50 5 190 0
6 c)AED excursion -1 -12
Envelope loss/gain 43 36 450 155
12 a) Infiltration 0 0 85 24
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 500
Subtotal(lines 6 to 13) 43 36 534 679
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution -43 -36 0 0
14 Subtotal 0 0 534 679
15 Duct loads 25% 36% 0 0 25% 36% 131 242
FFTotal room load 0 0177, 666 921
Air required(cfm) 0 0 34 43
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 12
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
nn�.iaN�eo Right-J®Worksheet Job:
AHU 2 Date: Jul 30,2020
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name UTILITY
2 Exposed wall 13.0 ft
3 Room height 9.0 ft heat/cool
4 Room dimensions 1.0 x 166.0 ft
5 Room area 166.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-4ocs 0.143 n 4.00 2.19 81 60 239 131
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0
2 glazing,clr low-e 0.320 n 8.96 9.41 21 0 191 201
2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0
11 2 glazing,clr low-e 0.320 n 0.00 0.00 0 0 0 0
13A-4ocs 0.143 e 0.00 0.00 0 0 0 0
2 glazing,clr low-e 0.320 e 0.00 0.00 0 0 0 0
2 glazing,clr low-e 0.320 e 0.00 0.00 0 0 0 0
13A-4ocs 0.143 s 4.00 2.19 36 16 64 35
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0
2 glazing,clr low-e 0,320 s 8.96 9.41 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 0 0 0 0
2 glazing,clr low-e 0.320 s 8.96 9.41 20 20 179 188
W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0
2 glazing,clr low-e 0.320 w 8.96 24.95 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 0 0 0 0
2 glazing,clr low-e 0.320 w 0.00 0.00 01 0 0 0
C 16X19-0md 0.408 1.59 1.37 166 166 263 227
F 22A-tph 1.358 38.02 0.00 166 13 494 0
6 c)AED excursion -32
Envelope loss/gain 1431 749
12 a) Infiltration 220 63
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 1000
Subtotal(lines 6 to 13) 1651 1813
Less external load 0 0
Less transfer 0 0
Redistribution 9 7
14 Subtotal 1660 1820
15 Duct loads 25% 36% 408 647
FFTotal room load 2068 2467
Air required(cfm) 104 114
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
--4cCb, -I- �aN�ao ,.. 2020-Jul-30 11:52:19
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 13
...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
Art Liapfaotr, Duct System Summary Job:
Date: Jul 30,2020
AHU 1 By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
Project • •
For: CHAMBERS RESIDENCE, COLE CONSTRUCTION SERVICES, LLC.
4700 INDRIO ROAD, FORT PIERCE, FL 34951
Heating Cooling
External static pressure 1.00 in H2O 1.00 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 1.00 in H2O 1.00 in H2O
Supply/ return available pressure 0.500/ 0.500 in H2O 0.500/0.500 in H2O
Lowest friction rate 1.000 in/100ft 1.000 in/100ft
Actual air flow 1173 cfm 1173 cfm
Total effective length (TEL) 190 ft
Supply Branch DetailTable
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln (ft) Ln (ft) Trunk
BATH 2 h 1078 51 35 1.000 5.0 Ox 0 VIFx 14.3 115.0 st 1
BATH 3 c 560 10 25 1.000 5.0 Ox 0 VIFx 7.3 115.0 st3
BEDROOM 2 h 4471 211 99 1.000 7.0 Ox0 VIFx 10.1 115.0 st1
BEDROOM 3 h 5416 255 152 1.000 8.0 Ox0 VIFx 10.1 115.0 st3
DINING c 2306 82 102 1.000 7.0 Ox0 VIFx 53.7 135.0 st6
DINING-A c 2306 82 102 1.000 7.0 Ox0 VIFx 54.7 135.0 st6
FOYER c 3339 84 148 1.000 8.0 Ox 0 VIFx 13.6 115.0 st3
KITCHEN c 3333 30 147 1.000 8.0 Ox0 VIFx 31.1 115.0 st2
LIVING c 3209 97 142 1.000 8.0 Ox0 VIFx 13.7 115.0 st1
LIVING-A c 3209 97 142 1.000 8.0 Ox0 VIFx 18.3 115.0 st1
PANTRY h 1642 77 26 1.000 5.0 Ox0 VIFx 34.0 115.0 st2
WIC h 958 45 33 1.000 5.0 Ox0 VIFx 34.5 115.0 st2
WIC 2 h 149 7 5 1.000 4.0 Ox0 VIFx 11.7 115.0 st1
WIC 3 h 943 44 15 1.000 4.0 Ox0 VIFx 11.4 115.0 st3
SupplyDetail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st6 Peak AVF 164 204 1.000 374 10.0 0 x 0 VinlFlx st2
st2 Peak AVF 317 411 1.000 523 12.0 0 x 0 VinlFlx
st3 Peak AVF 393 339 1.000 721 10.0 0 x 0 VinlFlx
st1 Peak AVF 463 423 1.000 590 12.0 0 x 0 VinlFlx
�C� MI.IaFlZO � 2020-Jul-30 11:52:29
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 1
r ...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
TableReturn Branch Detail
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb2 Ox0 1173 1173 0 0 0 0 Ox 0 VIFx
�C� MI.IaFlZO � 2020-Jul-30 11:52:29
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 2
r ...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
Art Liapfaotr, Duct System Summary Job:
Date: Jul 30,2020
AHU 2 By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
Project • •
For: CHAMBERS RESIDENCE, COLE CONSTRUCTION SERVICES, LLC.
4700 INDRIO ROAD, FORT PIERCE, FL 34951
Heating Cooling
External static pressure 1.00 in H2O 1.00 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 1.00 in H2O 1.00 in H2O
Supply/ return available pressure 0.500/ 0.500 in H2O 0.500/0.500 in H2O
Lowest friction rate 1.000 in/100ft 1.000 in/100ft
Actual air flow 800 cfm 800 cfm
Total effective length (TEL) 176 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln (ft) Ln (ft) Trunk
BATH 4 c 921 34 43 1.000 6.0 Ox 0 VIFx 38.0 135.0 st7
DEN h 2521 127 126 1.000 7.0 Ox0 VIFx 40.6 135.0 st7
M BATH h 2433 123 122 1.000 7.0 Ox0 VIFx 7.9 115.0 st4
M TOILET c 341 4 16 1.000 4.0 Ox0 VIFx 9.1 115.0 st4
M WIC 1 h 1001 50 50 1.000 4.0 Ox0 VIFx 9.1 115.0 st5
MWIC2 c 939 38 43 1.000 6.0 Ox0 VIFx 10.9 115.0 st4
MASTER BEDROOM h 3170 160 143 1.000 8.0 Ox0 VIFx 13.8 115.0 st5
MASTER BEDROOM-A h 3170 160 143 1.000 8.0 Ox0 VIFx 12.1 115.0 st5
UTILITY c 2467 104 114 1.000 7.0 Ox0 VIFx 36.7 135.0 st7
SupplyTrunk Detail Table
Trunk Htg CIg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk
st7 Peak AVF 265 283 1.000 519 10.0 0 x 0 VinlFlx st4
st4 Peak AVF 430 464 1.000 591 12.0 0 x 0 VinlFlx
st5 Peak AVF 370 336 1.000 678 10.0 0 x 0 VinlFlx
�C� MI.IaFlZO � 2020-Jul-30 11:52:29
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 3
r ...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
TableReturn Branch Detail
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb1 Ox0 800 800 0 0 0 0 Ox 0 VIFx
�C� MI.IaFlZO � 2020-Jul-30 11:52:29
Right-Suite®Universal 2019 19.0.08 RSU08101 Page 4
r ...ocumnets\Wrightsoft HVAC\CHAMBERS RESIDENCE.rup Calc=MJ8 Front Door faces: S
This document was created with Win2PDF available at http://www.win2pdf.com.
The unregistered version of Win2PDF is for evaluation or non-commercial use only.
This page will not be added after purchasing Win2PDF.