Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
Wind zone, project info
NewSouth WINDOW SOLUTIONS W)A nt.e hnhee RI..rl West Palm Beach. FL 33409 • 561-712-9000 • CRC 1330822 Propeny Information Buildin Information Owner: Leslie Rosenwasser Wind Zone: 170 MPH. Address: 9005 One Putt PI Exposure Category: C Port St Lucie, FI 34986 Minimum Building Dimension: 25 ft. Mean Roof Height: 15 ft. Risk Category: II Design Pressure Calculations Opening Location Device Device Device Max Positive Max Negative Number Zone Width (in) Height (in) Elevation (ft) Pressure (psf) Pressure (psf) 1 Int 53.50 27 7 37.8 -41.0 2 Int 53.50 27 7 37.8 -41.0 3 Int 71.75 21 7 37.4 -40.6 4 Int 72 61.50 7 35.0 -38.2 5 Int 71.75 21 7 37.4 -40.6 6 Int 72 61.50 7 35.0 -38.2 7 Int 72 61.50 7 35.0 -38.2 8 Int 71.75 21 7 37.4 -40.6 9 Int 72 21.25 7 37.3 -40.6 10 Int 71.75 21 7 37.4 40.6 11 Int 72 70.75 7 34.7 -37.9 12 Int 35 61.50 7 36.8 40.0 13 Int 35 61.50 7 36.8 -40.0 14 Int 35 4.2 36.25 7 37.8 41.0 15 Int 24 12 7 37.8 -41.0 16 Int 24.25 37 7 37.8 41.0 17 Int 35 17.50 7 37.8 41.0 18 Int 35 61.50 7 36.8 -40.0 19 Int 35 17.50 7 37.8 41.0 20 Int 35 44.50 7 37.6 40.8 21 Int 24.75 37 7 37.8 41.0 22 Int 24.50 75.50 7 37.1 -40.3 23 Int 24.50 75.50 7 37.1 -40.3 Prepared in accordance with: ASCE 7-10. Chapter 30. Wind Loads - Compomnis and Cladding. 6th Edition (2017) Florida Building Code. Page 1 of 1