Model GE-200VL Pat. Pending
Main Breaker 200 amp single handle Vertical throw down (off), up (on) 2 ½ to 3 ½ inch spacing
between Main and first breaker
Generator Breaker Top left side 2 positions
WARNING
Only qualified personnel should be working on the panel box
An amateur should NEVER open the panel box
Please follow all rules and regulations of the National Electric Code
Step 1: Disassemble the interlock. Place the bottom plate (holes only) following contour of the main breaker above the left hand top
breaker, as in the picture. And mark holes.
Step 2: Turn off main breaker and remove panel cover.
Step 3: Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover.
Step 4: Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install tread lock to screws and install
retaining nuts. Ensure proper movement.
Step 5: Install 2 pole Generator breaker on top left side and place Generator Warning Sticker on Generator breaker.
Step 6: Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in picture below. Pull on
ends to make tight around breakers. Trim zip ties as needed and Install Warning label next to release tab on zip tie at
generator breaker.
Step 7: Re-Install panel cover, Verify proper operation of interlock. Main breaker ON, generator breaker OFF and generator breaker
CAN NOT be turned on. Generator breaker ON, main breaker OFF and main breaker CAN NOT be turned on.
Main On Generator On
Step 8: Place Generator start-up procedure label on panel box, Place CAUTION label on panel box and electric meter pan.
The MAIN and the GENERATOR breakers should NEVER be able to be turned on at the same time. If panel cover is removed the
Generator breaker is NEVER to be turned on. If for any reason the interlock does not function properly, DO NOT USE and contact us
immediately at sales@GenInterlock.com for support and instructions.
Thank You for your support,
GenInterlock Team
DISCLAIMER: GenInterlock.com is NOT responsible for misuse or improper installation.
All electrical equipment should be installed and maintained by qualified personnel. Any
consequences arising from improper use is the responsibility of the user.