1 L rEC0 i,c.
TILLIT TESTING & ENGINEERING COMPANY
NVALTER A. TILLIT. JR., P.E.
September 18, 2019
Mr. Tim Robinson
Managing Partner
Global Protection Products, LLC.
4800 SW 51 Street
Davie, Florida 33314
fifteco@aol.com
FL RE 1.icrose No. 44167
FL C.A. Lkm No. (MM719
19-070
Re.: State of Florida Approval Drawing #17-142. Additional limitations for use of
Component "9A" (sleeve=spacer) for 24 gage Galvanized Steel Storrs panel
installation into wood frame structures.
Dear Mr. Robinson:
As per your request, following are additional limitations for the use of spacer component
# "9A" for panel installation at existing wood frame structures.
These limitations are an addendum to limitations already indicated in approved Drawing
# 17-142 and shall be strictly enforced.
Spacer "9A" may be 1 '/" Long if the following additional limitations are complied with:
(1) Installation is.limited to a one story Buildings with 16-0 Max mean roof height (this is
a restriction from any building height currently indicated on sheet 11 of approved Drawing
#17-142)
(2) Anchors going thru component "9A" (panel mate female ID or panel mate plus) shall
be spaced maximum at 6 %" O.C_ (this is a restriction from 12 '/" O.C. Spacing allowed
on sheet 6 of approved Drawing # 17-142)
(3) Max 24 gage panel length is limited to 66" at any opening (this is a restriction from
larger panel lengths allowed on schedule, sheet 11 of approved Drawing # 17-142)
(a) 1 %" Long Spacer component # "9A" shall be as indicated on sheet 2 of approved
Drawing #17-142_ Installation of 1 'Y long spacer "9A" shall be similar to dekai) 2W', sheet
COPY
6355 N.W. 36th Street, Suite 305, Miami, Florida 33166 - Phone: (305) 871-1530 - Fax: (305) 871-1531
6 of approved Drawing #17-142, and its valid only to wind zones 1, 2 and 3 as deferred
by ASTNI E-1996 standard and the 2017 (6Edition) of the Florida Building Code.
Sincerely,
Walter A. Tillit Jr P.E.
President
Tilteco, Inc.