November 4, 2019
RE: 10692 S US 1
Permit # 1906-0641
To Whom It My Concern
Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
*ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT
BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT
USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CHID)
Response: SEE REVISED OCCUPANT LOADS SHEET A-2
*PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY
SHALL NOT BE OCCUPIED AT THE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED.
LETTER IS REQUIRED AS A CONDITION OF USE. (1004.1)
Response: OWNER TO PROVIDE
*WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT
THE NEW OCCUPANCY IS SUBIECTTO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED
MECHANICAL VENTALATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL
PROVISIONS. (3009.1) **THIS IS A CHANGE OF USE FROM MASSAGE THERAPY TO WORSHIP CENTER. SEE CH 4
AND TABLE 403.3.1 MINIMUM VENTILATION RATES. **
Response: SEE VENTILATION CALCULATION ON SHEET A-2
Di 69a --
cini
gnlc Inc.
VvRED PAC
806 Delaware Avenue
Fort Pierce, Florida 34950
Tel: 772 460 7751
Fax: 772 460 4244
se'we
1 2019
Permitting Department
County,St. Lucie
www.architectonicinc.com
FL Reg #AA26003348 1 of 1
Architccton'ic Inc
St. Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
November 4, 2019
RE: 10692 S US 1
Permit # 1906-0641
To Whom it My Concern
Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
*ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT
BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT
USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CH10)
Response: SEE REVISED OCCUPANT LOADS SHEET A-2
*PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY
SHALL NOT BE OCCUPIED AT THE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED.
LETTER IS REQUIRED AS A CONDITION OF USE. (3004.1)
Response: OWNER TO PROVIDE
*WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING 15 CHANGED SUCH THAT
THE NEW OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED
MECHANICAL VENTALATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL
PROVISIONS. (1009.1) **THIS IS A CHANGE OF USE FROM MASSAGE THERAPY TO WORSHIP CENTER. SEE CH 4
AND TABLE 403.3.1 MINIMUM VENTILATION RATES. **
Response: SEE VENTILATION CALCULATION ON SHEETA-2
a tSeal Ps9669
A 't{onic Inc.
C�`rTFRED
806 Delaware e
Fort Pierce, Florida 34950
Tel: 772 460 7751
Fax: 772 460 4244
NOV -5 2019
Permitting Department
St. Lucie County, FL
www.architectonicinc.com
FL Reg #AA26003348 1 of 1
Architectonic Inc
St. Lucie County Building Department Planning & Development Services
Building & Code Regulatlon Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
September 25, 2019
RE: 10692 S US 1
Permit # 1906-0641
To Whom It My Concern:
Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans
corresponding (if required) to these comments are noted.
ELECTRIC
'PLEASE PROVIDE ELECTRICAL PLANS TO COMPLETE PLAN REVIEW. ((A)) 107.2.1)
Response., NOTREQUIRED PER MEETING
MECHANICAL
'WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL, THE NEW OCCUPANCY SHALL COMPLY
WITH THE RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS (1009.1)
Response., NOT REQUIRED FOR BUSINESS OCCUPANCY
*PLEASE PROVIDE A UL DETAIL FOR THE SEPARATION WALL. ADJACENT UNITS ARE IN PLAN REVIEW FOR GROUP B
OCCUPANCIES. (508.1)
Response: NOT REQUIRED FOR BUSINESS OCCUPANCY
*PLEASE PROVIDE DETAILS FOR THE PULPIT, INCLUDE HEIGHT. ((a})107.2.1
Response: SEESHEETA-2
*THE OCCUPANT LOAD FACTOR USED FOR THE SANCTUARY AND MEETING ROOM IS FOR TABLES AND CHAIRS, PLEASE USE THE
CORRECT FACTOR FOR THE FUNCTIONS OF EACH SPACE. (1004.1)
Response: SEESHEETA-2
*PLEASE SHOW THE FURNITURE CHAIRS AND AISLES ON THE LIFE SAFETY PLAN FOR THE MEETING ROOM AND SANCTUARY.
INCLUDE EXIT SIGNS, ALARMS, DETECTORSK FIRE EXTINGUISHERS. ((F}) 1001.4)
Response: SEESHEETA-2 NOT IF BUSINESS
"PROVIDE THE REQUIRED FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INTERIOR FINISHES.
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1
Architectonic Inc
St. Lucle County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
September 25, 2019
RE: 10692 S US 1
Permit # 1906-0641
To Whom It My Concern:
Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans
corresponding (if required) to these comments are noted.
ELECTRIC
*PLEASE PROVIDE ELECTRICAL PLANS TO COMPLETE PLAN REVIEW. ((A)) 107.2.1)
Response: NOT REQUIRED PER MEETING
MECHANICAL
*WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL, THE NEW OCCUPANCY SHALL COMPLY
WITH THE RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS (1009.1)
Response: NOT REQUIRED FOR BUSINESS OCCUPANCY
*PLEASE PROVIDE A UL DETAIL FOR THE SEPARATION WALL. ADJACENT UNITS ARE IN PLAN REVIEW FOR GROUP B
OCCUPANCIES. (508.1)
Response: NOT REQUIRED FOR BUSINESS OCCUPANCY
*PLEASE PROVIDE DETAILS FOR THE PULPIT, INCLUDE HEIGHT. ((a))107.2.1
Response: SEESHEETA-1
*THE OCCUPANT LOAD FACTOR USED FOR THE SANCTUARY AND MEETING ROOM IS FOR TABLES AND CHAIRS, PLEASE USE THE
CORRECT FACTOR FOR THE FUNCTIONS OF EACH SPACE. (1004.1)
Response: SEESHEETA-2
*PLEASE SHOW THE FURNITURE CHAIRS AND AISLES ON THE LIFE SAFETY PLAN FOR THE MEETING ROOM AND SANCTUARY.
INCLUDE EXIT SIGNS, ALARMS, DETECTORSK FIRE EXTINGUISHERS. ((F)) 3001.4)
Response: SEE SHEETA-2 NOTIF BUSINESS
*PROVIDE THE REQUIRED FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INTERIOR FINISHES.
Response: NOT REQUIRED PER MEETING
MBLY STANDARDS AND ATTACHMENT. (2506.1)
MEETING
Seal
806 De Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1
Architectonic Inc
St. Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
November 19, 2019
RE: 10692 S US 1
Permit # 1906-0641
To Whom It My Concern
Please accept the following responses to the comments dated 11/4/2019 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
*ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT
BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT
USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CH10)
Response: SEE REVISED BUILDING INFORMATION
*PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY
SHALL NOT BE OCCUPIED AT THE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED.
LETTER IS REQUIRED AS A CONDITION OF USE. (1004.1)
Response: OWNER TO PROVIDE
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1
Architectonic Inc
9)e:_r7)i a- jqojp-0Uq I
St, Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL34982
November 4, 2019
RE: 10692 S US 1
Permit It 1906-0641
To Whom It My Concern
Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
*ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT
BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT
USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CHID)
Response: SEE REVISED OCCUPANT LOADS SHEETA-2
*PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY
SHALL NOT BE OCCUPIED ATTHE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED.
LETTER IS REQUIRED AS A CONDITION OF USE. (1004.1)
Response: OWNER TO PROVIDE
*WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT
THE NEW OCCUPANCY IS SUBJECTTO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED
MECHANICAL VENTALATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL
PROVISIONS. (1009.1) **THIS IS A CHANGE OF USE FROM MASSAGE THERAPY TO WORSHIP CENTER. SEE CH 4
AND TABLE 403.3.1 MINIMUM VENTILATION RATES. **
Response: SEE VENTILATION CALCULATION ON SHEET A-2
!RECEIVED
NOV 2019
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1
Architectonic Inc
St. Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
September 25, 2019
RE: 10592 S US 1
Permit # 1906-0641
To Whom It My Concern:
Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans
corresponding (if required) to these comments are noted.
ELECTRIC
*PLEASE PROVIDE ELECTRICAL PLANS TO COMPLETE PLAN REVIEW. (IQ 107.2.1)
Response: NOT REQUIRED PER MEETING
Adre.3
MECHANICAL
*WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL, THE NEW OCCUPANCY SHALL COMPLY
WITH THE RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS (1009.1)
Response: NOTREQUIRED FOR BUSINESS OCCUPANCY
*PLEASE PROVIDE A UL DETAIL FOR THE SEPARATION WALL. ADJACENT UNITS ARE IN PLAN REVIEW FOR GROUP B
OCCUPANCIES. (508.1)
Response: NOT REQUIRED FOR BUSINESS OCCUPANCY
*PLEASE PROVIDE DETAILS FOR THE PULPIT, INCLUDE HEIGHT. ({a}) 107.2.1
Response: SEESHEETA-2
*THE OCCUPANT LOAD FACTOR USED FOR THE SANCTUARY AND MEETING ROOM IS FOR TABLES AND CHAIRS, PLEASE USE THE
CORRECT FACTOR FOR THE FUNCTIONS OF EACH SPACE. (1004.1)
Response: SEESHEETA-2
*PLEASE SHOW THE FURNITURE CHAIRS AND AISLES ON THE LIFE SAFETY PLAN FOR THE MEETING ROOM AND SANCTUARY.
INCLUDE EXIT SIGNS, ALARMS, DETECTORSK FIRE EXTINGUISHERS. ({F}) 1001.4)
Response: SEE SHEETA-2 NOTIF BUSINESS
*PROVIDE THE REQUIRED FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INTERIOR FINISHES.
Response: NOT REQUIRED PER MEETING
ASSEMBLY STANDARDS AND ATTACHMENT. (2506.1)
PER MEETING