HomeMy WebLinkAboutLetterArchitectonic Inc St. Lucie County Building Department Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL 34982 November 4, 2019 RE: 10692 S US 1 Permit # 1906-0641 To Whom It My Concern Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. *ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CHID) Response: SEE REVISED OCCUPANT LOADS SHEET A-2 *PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY SHALL NOT BE OCCUPIED AT THE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED. LETTER IS REQUIRED AS A CONDITION OF USE. (1004.1) Response: OWNER TO PROVIDE *WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBIECTTO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTALATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS. (3009.1) **THIS IS A CHANGE OF USE FROM MASSAGE THERAPY TO WORSHIP CENTER. SEE CH 4 AND TABLE 403.3.1 MINIMUM VENTILATION RATES. ** Response: SEE VENTILATION CALCULATION ON SHEET A-2 Di 69a -- cini gnlc Inc. VvRED PAC 806 Delaware Avenue Fort Pierce, Florida 34950 Tel: 772 460 7751 Fax: 772 460 4244 se'we 1 2019 Permitting Department County,St. Lucie www.architectonicinc.com FL Reg #AA26003348 1 of 1 Architccton'ic Inc St. Lucie County Building Department Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL 34982 November 4, 2019 RE: 10692 S US 1 Permit # 1906-0641 To Whom it My Concern Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. *ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CH10) Response: SEE REVISED OCCUPANT LOADS SHEET A-2 *PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY SHALL NOT BE OCCUPIED AT THE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED. LETTER IS REQUIRED AS A CONDITION OF USE. (3004.1) Response: OWNER TO PROVIDE *WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING 15 CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTALATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS. (1009.1) **THIS IS A CHANGE OF USE FROM MASSAGE THERAPY TO WORSHIP CENTER. SEE CH 4 AND TABLE 403.3.1 MINIMUM VENTILATION RATES. ** Response: SEE VENTILATION CALCULATION ON SHEETA-2 a tSeal Ps9669 A 't{onic Inc. C�`rTFRED 806 Delaware e Fort Pierce, Florida 34950 Tel: 772 460 7751 Fax: 772 460 4244 NOV -5 2019 Permitting Department St. Lucie County, FL www.architectonicinc.com FL Reg #AA26003348 1 of 1 Architectonic Inc St. Lucie County Building Department Planning & Development Services Building & Code Regulatlon Division 2300 Virginia Avenue Ft. Pierce, FL 34982 September 25, 2019 RE: 10692 S US 1 Permit # 1906-0641 To Whom It My Concern: Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. ELECTRIC 'PLEASE PROVIDE ELECTRICAL PLANS TO COMPLETE PLAN REVIEW. ((A)) 107.2.1) Response., NOTREQUIRED PER MEETING MECHANICAL 'WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL, THE NEW OCCUPANCY SHALL COMPLY WITH THE RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS (1009.1) Response., NOT REQUIRED FOR BUSINESS OCCUPANCY *PLEASE PROVIDE A UL DETAIL FOR THE SEPARATION WALL. ADJACENT UNITS ARE IN PLAN REVIEW FOR GROUP B OCCUPANCIES. (508.1) Response: NOT REQUIRED FOR BUSINESS OCCUPANCY *PLEASE PROVIDE DETAILS FOR THE PULPIT, INCLUDE HEIGHT. ((a})107.2.1 Response: SEESHEETA-2 *THE OCCUPANT LOAD FACTOR USED FOR THE SANCTUARY AND MEETING ROOM IS FOR TABLES AND CHAIRS, PLEASE USE THE CORRECT FACTOR FOR THE FUNCTIONS OF EACH SPACE. (1004.1) Response: SEESHEETA-2 *PLEASE SHOW THE FURNITURE CHAIRS AND AISLES ON THE LIFE SAFETY PLAN FOR THE MEETING ROOM AND SANCTUARY. INCLUDE EXIT SIGNS, ALARMS, DETECTORSK FIRE EXTINGUISHERS. ((F}) 1001.4) Response: SEESHEETA-2 NOT IF BUSINESS "PROVIDE THE REQUIRED FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INTERIOR FINISHES. 806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1 Architectonic Inc St. Lucle County Building Department Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL 34982 September 25, 2019 RE: 10692 S US 1 Permit # 1906-0641 To Whom It My Concern: Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. ELECTRIC *PLEASE PROVIDE ELECTRICAL PLANS TO COMPLETE PLAN REVIEW. ((A)) 107.2.1) Response: NOT REQUIRED PER MEETING MECHANICAL *WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL, THE NEW OCCUPANCY SHALL COMPLY WITH THE RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS (1009.1) Response: NOT REQUIRED FOR BUSINESS OCCUPANCY *PLEASE PROVIDE A UL DETAIL FOR THE SEPARATION WALL. ADJACENT UNITS ARE IN PLAN REVIEW FOR GROUP B OCCUPANCIES. (508.1) Response: NOT REQUIRED FOR BUSINESS OCCUPANCY *PLEASE PROVIDE DETAILS FOR THE PULPIT, INCLUDE HEIGHT. ((a))107.2.1 Response: SEESHEETA-1 *THE OCCUPANT LOAD FACTOR USED FOR THE SANCTUARY AND MEETING ROOM IS FOR TABLES AND CHAIRS, PLEASE USE THE CORRECT FACTOR FOR THE FUNCTIONS OF EACH SPACE. (1004.1) Response: SEESHEETA-2 *PLEASE SHOW THE FURNITURE CHAIRS AND AISLES ON THE LIFE SAFETY PLAN FOR THE MEETING ROOM AND SANCTUARY. INCLUDE EXIT SIGNS, ALARMS, DETECTORSK FIRE EXTINGUISHERS. ((F)) 3001.4) Response: SEE SHEETA-2 NOTIF BUSINESS *PROVIDE THE REQUIRED FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INTERIOR FINISHES. Response: NOT REQUIRED PER MEETING MBLY STANDARDS AND ATTACHMENT. (2506.1) MEETING Seal 806 De Tel: 772 460 7751 www.architectonicinc.com Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1 Architectonic Inc St. Lucie County Building Department Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL 34982 November 19, 2019 RE: 10692 S US 1 Permit # 1906-0641 To Whom It My Concern Please accept the following responses to the comments dated 11/4/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. *ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CH10) Response: SEE REVISED BUILDING INFORMATION *PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY SHALL NOT BE OCCUPIED AT THE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED. LETTER IS REQUIRED AS A CONDITION OF USE. (1004.1) Response: OWNER TO PROVIDE 806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1 Architectonic Inc 9)e:_r7)i a- jqojp-0Uq I St, Lucie County Building Department Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL34982 November 4, 2019 RE: 10692 S US 1 Permit It 1906-0641 To Whom It My Concern Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. *ADDITIONAL PLAN REVIEW REQUIRED WHEN OCCUPANT COUNT IS REVISED. **THE OCCUPANT COUNT HAS NOT BEEN PROVIDED FOR EACH SPACE -ENTRY AND PULPIT ARE NOT ACCOUNTED FOR. MEETING ROOM DOES NOT USE THE CORRECT TABLE AND CHAIR LOAD FACTOR. **(CHID) Response: SEE REVISED OCCUPANT LOADS SHEETA-2 *PROVIDE A "LETTER OF NONCONCURRENCY" BOTH BUILDING OWNER AND TENANT SHALL STATE THE SACTUARY SHALL NOT BE OCCUPIED ATTHE SAME TIME AS THE MEETING ROOM. LETTER SHALL BE SIGNED AND NOTORIZED. LETTER IS REQUIRED AS A CONDITION OF USE. (1004.1) Response: OWNER TO PROVIDE *WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECTTO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTALATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS. (1009.1) **THIS IS A CHANGE OF USE FROM MASSAGE THERAPY TO WORSHIP CENTER. SEE CH 4 AND TABLE 403.3.1 MINIMUM VENTILATION RATES. ** Response: SEE VENTILATION CALCULATION ON SHEET A-2 !RECEIVED NOV 2019 806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1 Architectonic Inc St. Lucie County Building Department Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL 34982 September 25, 2019 RE: 10592 S US 1 Permit # 1906-0641 To Whom It My Concern: Please accept the following responses to the comments dated 7/2/2019 from your agency. Response shown on plans corresponding (if required) to these comments are noted. ELECTRIC *PLEASE PROVIDE ELECTRICAL PLANS TO COMPLETE PLAN REVIEW. (IQ 107.2.1) Response: NOT REQUIRED PER MEETING Adre.3 MECHANICAL *WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL, THE NEW OCCUPANCY SHALL COMPLY WITH THE RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS (1009.1) Response: NOTREQUIRED FOR BUSINESS OCCUPANCY *PLEASE PROVIDE A UL DETAIL FOR THE SEPARATION WALL. ADJACENT UNITS ARE IN PLAN REVIEW FOR GROUP B OCCUPANCIES. (508.1) Response: NOT REQUIRED FOR BUSINESS OCCUPANCY *PLEASE PROVIDE DETAILS FOR THE PULPIT, INCLUDE HEIGHT. ({a}) 107.2.1 Response: SEESHEETA-2 *THE OCCUPANT LOAD FACTOR USED FOR THE SANCTUARY AND MEETING ROOM IS FOR TABLES AND CHAIRS, PLEASE USE THE CORRECT FACTOR FOR THE FUNCTIONS OF EACH SPACE. (1004.1) Response: SEESHEETA-2 *PLEASE SHOW THE FURNITURE CHAIRS AND AISLES ON THE LIFE SAFETY PLAN FOR THE MEETING ROOM AND SANCTUARY. INCLUDE EXIT SIGNS, ALARMS, DETECTORSK FIRE EXTINGUISHERS. ({F}) 1001.4) Response: SEE SHEETA-2 NOTIF BUSINESS *PROVIDE THE REQUIRED FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INTERIOR FINISHES. Response: NOT REQUIRED PER MEETING ASSEMBLY STANDARDS AND ATTACHMENT. (2506.1) PER MEETING FIZpaycui �ry s�I tieo, �: _fit '52- n 1 Inc. 806 [Mn64"016-nue Tel: 772 460 7751 www.architectonicinc.com Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1