HomeMy WebLinkAboutConstruction Plansd J Design Parameters 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk Category I. 2. Basic Wind Speed, Table 1609C, State of Florida Debris Region & Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed, VOLT=160 MPH 3. Exposure Category, Paragraph 1609.4.3 : C Applicable Codes. Regulation and Standards 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Stmcturel Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structure, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition 3. ASCE 7-10 General Notes 1. The contractor shall verify all dimensions prior to construction 2. All work shall comply with all local and regional ordinances. 3. Any deviation from this plan shall be reviewed by the engineer of record and is subject to approval. Specifications The following specifications are applicable to this projects: 1. Where concrete specification are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable. 1.1. Concrete shall conform to ASTM C94 for following components: 1.1.1. Portland Cement Type 1, -ASTM C 150 1.1.2. Aggregate - Large Aggregate 3/4" max- ASTM C 33 1.1.3. Air entraining +/-1 %-ASTM C 260 1.1.4. Water reducing agent-ASTM C494 1.1.5. Clean Potable water 1.1.6. Other admixture not permitted 1.2. Metal accessories shall oenform to: 1.2.1. Reinforcing Bars - ASTM A615, grade 60 1.2.2. Welded wire fabric-ASTMA185 1.3. Concrete slump at discharge per chute not less then 3" or more than 5". Water added after batching is not permitted. 1.4. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2 and 3 including hot weather recommendation: I.S. Moist cure or polyethylene curing required. 1.6. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. 1.7. All aluminum components embedded within concrete shall be coated with E bituminous paint or epoxy. 1.8. Fiber reinforced concrete per ASTSM C1116 is an acceptable alternative to 6X6 WIAANIA WWF. 2. Aluminum extrusions shall be 6005 T5 Alloy. 3. Fasteners are required to be comosion resistant, minimum SAE Grade 2 or better zinc plate to ASTM B633, or stainless steel series "300". 4. All Sell Mating Beam Sections and PFB are to be stitched with either#14 screws 6" from end 24" on center or #12 screws 6" from end 12" on center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 and FBC 454.1.3.1.9. 6. Door location shall be determined by contractor in the field. 7. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the anchors must extend past the pavers and reach proper embedment into the underlying foundation. B. All flashing and waterproofing shall be provided by the contractor. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. 10. Vinyl and acrylic panels shall be removed when wind speeds exceed 75mph Foundation Design: Existing 8"x8" Thickened Edge 4" Slab on Grade Existing concrete. No additional concrete footing is required to resist the leads imposed by the proposed construction if the existing footing is in sound condition, free from structural cracking, spelling, or other deterioration. Roof Type Screen Size Full Mansard 18114 ALUMINUM MEMBER DIMENSIONS HOLLOWSECTIONs SELF MATING BEAM (SMB) THE PORCH F40TORY BEAM IPFB 2xz rxrX0.w]• zx4sMB: rx4•x B.ow•xo.loo- 3.2s PFB: rx3.Tr%0.0W 2x3: rxYx0.05r 2x55MB: TXSX0.0Vx(L107 5.75PFB: rx5.]Sx0.05S 2x4: rxrxsO P 2zfi 5MB: rx rx0.O5rx R12r CO UMNS 2xS rx4x LLO5P 2x7SMB: rx]•x O.OSTx4121Y ""] "1•"0125• rxrxB.Brexalz4• 1 x3: 1•xrx0.015• MWIMUM FASTENER W09 DISTPNCE: Ill rx3'x0.05P CONCRETE SCREWANCHOR: SHEET MAWL SCREWS (SMB): rx4•xO.MS BIMPSONTRENHOOREpNVAIEM M UMEXCREQUNALEW SCALE. USE DIMENSIONS GNEN. CABLE BRACING MAY TERMINATE AT SLAB IN DIFFERENT LOCATION. MAINTAIN ANGLE PER DETAIL 3'-0'--1 --6- i 3'-0-4 W-6• =- _HOS j- lxz cryp) RN4 V �A 2X] 2x3 2x3 2x3 2X3 9(3 N } C y RC3 a 9(3 ix3 2x3 2X3 .3 2x3 04 z V RCS ] BR4 2 r-z• ! r-z' ! T-2• ! 2•-z•- 1 43' 0• PLAN VIEW 2X8 SMS CARRY BEAM ! 211-6"--1 FRONT ELEVATION to jh O 00.�v-1 = Y UUZ �w 1` Z Q' p: Z • �(` n �� +. COPY EVIEWED R %J0 COMPLIANCE ST. L CIE CO T 'Rccc7`lp1� d u C d 9 lY a- x 0oO1 m J e9 >a Eo `o = C LL C N m 'a N to � m LL 9 N 9 U tb �O a` SHEET 1 VB"BRACKETCUr FROM 1-x 5•ANGLE W CONNECTTH (S) 914 X WV SMS ra UPRIGHT DOUBLE COMPRESSION SLEEVES 1-1/4' x BS/e• x 1/8' ALUM. FLAT BAR. 6063T6 ALUM. EVE RAIL EYE BOLT FOR CABLETENSION (2) W8- DIA x 3^ EMBED - CONCRIFTESCREW ALTERNATE CONNECTION ANCHOR VB-S.S. CABLE 1-1/4• x 558"x 1/S=ALUM. FLAT BAR. WITH (2) M- DIA. CONCRETE ANCHORS. MIN. 2d1 EMBEDMENT p Note - Orientation may be different. 3116' GUSSET PURUNS ATTACHED TO BEAM - WITH (4) 010 x 1-IM" SMS WNH WASHE INTO SCREW BOSSES. B14 X314°SMS 01-114"O.C.� BRICK PAVERS MAY NOT BE PRESENT. ENSURE z o MIN. REQUIRED ANCHOR i NOTES: EMBEDMENT INTO 1. SEE THE NOTE BELOW FOR SCREWS SPACING. THE NUMBER OF SCREWS SHOWN ARE CONCRETE - D� FOR ILLUSTRATIVE PURPOSES. DO NOT COUNT SCREWS ON DRAWING. ...n9 iWo 2. GUSSET DIMENSIONS AREA MINIMUM (2) RE(TD - (1) EA SIDE OF BEAM -MAY BE INTERNAL FOUNDATION PER PLAN .' A OR EXTERNAL - 3. AS BEAM SIZE CHANGES. ADD OR SUBTRACT SCREWS TO MAINTAIN 11I4• C/C SPACING. 4. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE 1BR'1 CABLE BRACING G-1 TYPICAL INTERNAUEXTERAL GUSSET CONNECTION Z SCALE: NTS SCALE:NTS 29¢klle"ANGLE FE SIDE O SIDE VIEW ;r (1) AC DIACONCRETE SCREWEN AORSIMO YY.. EACH LEG — (1) +/2" DIA THRU BOLT WITH IS-x 2-x rANGM WITH NYLOCK JAM NUT(JAM NUT WITH (4) 914x 314" SMS INTO THREADLOCKER MAY BE USED, IN 00 POST LIEU). DO NOT OVER TIGHTEN. O O TIGHTEN ONLY UNDL CONTACT. RICK PAVERF NOT FOR 2x2 AND 2X3 UPRIGHTS, USE BE PRESENT. FOLLOW (4) 914 x W4-SMS INTO POST ANCHOR MINIMUM — BRICK PAVERS. MAY NOT CONCRETE EMBEDMENT BE PRESENIT. ENSURE MINIMUM CONCRETE EMBEDMENT. 2 Ow K ° 0 �w, ° TOP VIEW AT INTERMEDIATE UPRIGHT SIDE VIEW FOUNDATION PER PLAN PER PLAN UPRIGHT PER PLAN O0 8 ANCHORED TO CONCRME NTH 114' ow. 1X20.B. ANCHORED TO CONCRETE ANCHOR ANCHOR(MIN.1-C. NTH 1/4• DIA. CONCRETE SCREW EMBED) (� 24° O.C. ANCHOR 024 O.C. MAX (4) 914x 314° SMS INTO POST NN FOR CORNER COECTION 4);14x W4 SMSINTO FASTSr EN In 512x 3/4' n�O1 X POST BMSMS ®24' O.C. OIX2 (D UPRIGHT (4) R14x r SMS THRU In INTOPOST TOPVIEW AT CORNER UPRIGHT TO FOUNDATION CONNECTION SCALE: NTS 1)M. DIA CONC. .m • ANCHOR EMBED MIN. 4 DOTING. SEE PLAN FOR FRONT VIEW DETAILS iDJ-1 DOORJAMB CONNECTION 2 SCALE:NTS (4) 910. I-lM SMS INTO SCREW BOSSES (TYP) ONLY WOOD, A10 x 3' WOOD SCREWS ® VFROMFROM ENDS & 12.O.C. CONC. lie DIA. x 3=CONCRETE SCREW ANCHOR ® 6"FROM ENDS & 24° O.C. 2• X V x 110°ANGLE WITH (2) S10 x 3M" SMS IN EACH FLANGE, EACH SIDE (TYP) rPURLN/GIRT/CHAIRRAIL M-1 PURLIN I GIRT I O.B TO HOST CONNECTION 2 SCALE:NTS GUSSETPLATE PER PLAN / DETAILS PURUN I 0 I PURLIN —(2)C14 X2�THRUE Jlylllll��llll1l'1 BEAM THRU GUSIET PIATE BRACE i RMEDIATE JOINT r-Vir-WED FOR BODE COMPLIANT -,,�T. LUCIE COUNT ROCC l/4• DIA THRU BOLT WITH NYLON BRACE AT SAVE RAIL WASHER S STAINLESS STEEL NUT tBR-3 ROOF BRACING 2 SCALE:NTS SHEET 2 0.12 THICK4 BRACKET@ EACH BEAWPURUN, ATTACHED BRACKET TO FASCIA W/31Wx T LAGS (3 PER BRACKET). ATTACH GUTTER TO FASCIA WITH VW X 3" LAG ® 24. O.C. ELSEWHERE 1-X 2' OPEN BACK 18 NOT NEEDED IF GUTTER HAS SPLINE GROOVE. OTHERWISE CONNECT 1XZT0 SEAMIPURLIN WITH (2) $10 x 2-W SMS THRU BEAMIPURLIN INTO SCREW BOSSES. CONNECT 1X2 TO GUTTER WITH (1) 014 x 1-le-SMS ® 6' FROM ENDSAND24.O.C. O O Bey_ 1 a�R4iNR 2-x 2'x 11W x 2' ANGLE WITH (4)� O14 x 3/4' EMS INTO BEAM/PURUN AND (4) [(2) IF 1X2 IS SCREWED TO BEAM USING SCREW BOSSES]#14 X XV SMS INTO 1X2 (OR GUTTER). REPEAT ON OTHER SIOE OF BEAMIPURUM WHEN BEAM IS LARGER THAN GUTTER, 21I8' x 110 x 0.062" (MIN.) ALUM RECEIVING CHANNEL W/ MIN. (2) O12 x WSMS NOTE: (2) TW DIA. x P LAG SCREWS FOR SPANS GREATER THAN 30'41' O.Wr BACKING PLATE ON INSIDE OF GUTTER NOTE BEAM ORIENTATION MAY BE CONTRACTOR TO VERIFY FASCIA IS MINIMUM OF 2' x P. IF LESS, 2' X 4- PT SUB FASCIA SHALL BE PLACED BEHIND EXISTING AND LAG IAG SCREWS SHALL BE LENGTHENED TO FULLY PENETRATE SUB FASCIA. IF NO FASCIA IS EXISTING, ADD 2' x e PT FASCIA WITH 10 DLA. LAG BOLTS. EMBEDDING 1-11T INTO TRUSSTAILS. PRE-0RILL M`H&B- DIABITTO PRIV NTSPLITNNG. SHIM AS NECESSARY IF OTHER THAN A PLUMS CUT FASCIA RH-1 BEAM/PURLIN TO GUTTER CONNECTION 3 SCALE: NTS ATTACH INSIDE FACE OF BEAM WITH COLUMN USING 2 - x 2'x US'x BEAM DEPTH LONG ANGLE WITH (8) O14x 314" EMS EACH LEG. COLUMN PER PLAN. NOTCH COLUMN TO ACCEPT CARRIER BEAM 1-12 x 16-x 0.12Y ALUM STRAP ON OUTSIDE WITH (5) O14 x W4' IN BOTH CARRIER BEAM AND POST EACH S1DE (10 TOTAL) O O O O 1' x 2" O.B. ATTACHED EACH SIDE OF POST WITH $12 x 1-U2' SMS ® 6' FROM BOTTOM AND24'O.C. O O O O DETAIL AT CORNER V x 2.O.D. ATTACH TO UPRIGHT WITH (2) 610 x 2la' EMS THRU UPRIGHT INTO SCREW BOSSES PLUS O10x1 VT SMS W FROM EACH SIDE OF UPRIGHTAND TYPICAL AT 24' O.C. MAX NOTE IGNORE 1' X 2. O.B. AND CONNECTION IF SCREEN ISNT BEING INSTALLED RC-4 CARRIER BEAM TO COLUMN CONNECTION 3 SCALE:NTS Tx 2' W x 2 LONG ANGLE WITH (2)012x 141 SMS INTO POST &(1) 3.R" CIA X 2AM' CONCRETE SCREW ANCHOR INTO UNCRACKED J 3B' DIATHRU BOLTS IN COLUMN CONCRETE (HOLE DEPTH=3-112� ® / qND INTERNAL ANGLES. 1'X2'D,B. 2'x 2" z 114' (LENGTH = INTERIOR OF WIDTH OF COLUMN) ANGLE WITH M- TADLE•n .ermwn DIA CONCRETE SCREW ANCHORS (SEE 'A' commas sm TABLEFOR QUANTITY) MIN 2-12 INTO UNCRACKED CONCRETE (HOLE U3 1 xxx 2 DEPTH =3-12'). (2) T8' DIA BOLTS 66 3 THRU COLUMN x2'O.B. AT CORNER POST NOTE: OMIT 1X2 IF NO PROPOSED SCREEN. AT CENTER POST B-3 POST TO FOUNDATION INTERNAL CONNECTION 3 SCALE:NTS PURUN TO OVERLAP UPRIGH SCREW THRU EAVE RAIL INTO PURLIN SCREW BOSSES WITH (2) O1D x 0 SMS ATTACH 1X2 TO SAVE RAIL WITH O10 x 1-lW SMS ®6' FROM ENDS & 24.O.C. 0 xT x 118' PLATE WITH (4) ib xW SMS EACH SIOE OF BEAT UPRIGHT PER PLAI '"11111 FILE CO RC-2 UPRIGHT TO PURLIN CONNECTION 3 SCALE: NTS PLAN VIEW ATTACH 1X2 TO ROOF BEAM WITH (2)410 x 2-SMS INTERNAL INTO SCREW BOSSES (NOT SHOWN FOR CLARITY). ATTACH 1X2 TO CARRIER BEAM WITH O14 x 1-112' SMS @ 6' FROM ENDS &24. O.C. REVIEWED F( CODE COMPLIP ST. LUC�fIIE COU T' occ ANCHOR SEAM PURUN OOFSCREWS SIZE IN EACH LEG OFANGLE 2X2-2X3 4 2X4-2XS 6 2XB-2XT B vs-m 10 Mo 12 ROOFBEAM/ PURUN PER PLAN II' `ATTACH ROOF PURLIN TO CARRIER REAM CARRIER BEAM PER ZxlWx[D WITH 2" x VS' x IDEPTH p ROOF OF ROOFITH #14LONG ANGLE WITH OR x SMS. AN SEE TABLE FOR QUANTITY OF SCREWS. (TYP EACH SECTION VIEW SIDE) RC-5 NOTE BEAM ORIENTATION MAY BE DIFFERENT THAN ILLUSTRATED CARRIER BEAM TO ROOF BEAM / PURLIN CONNECTION 3 SCALE:NTS m L. O a, W t I— LL 6t W 0 0 C 0 :O N r 4) N H m J M A m C Eo 0 = C LL 0- u c2 OIL IB N O OmO LL a PC "' Q 0 0 �O IL SHEET 3