HomeMy WebLinkAboutFire department PermitSAINT LUCIE COUNTY FIRE DISTRICT
CVPLAN
REVIEW FARM
5160 N.W. Milner Drive
Telephone
Port Saint Lucie, FL 34983
x
DIS
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC FMO Permit # B-20-248
i
Project Name Island Village of Hutchinson Island-�� i BLDG Permit # 1905-0366
ddress 9431 South Ocean Drive City Jensen Beach
Contractor [The
W`Group ^�
ddressy140a 9 5W Albatross Way City !Palm City
State eIrFL Zip 134940 r �' 'telephone (772) 220-1930
�
Architect/Engineer Gary Kedy
Telephone
Occupancy Type ;Assembly
i
Construction Type !HIB
Square Feet 810
r
Occupant Load
Number of Stories 11
� -� Access Box �
Access Key Switch
j�
1140 per plans
i
FS Permit
�
FA Permit
FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper lIL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fen shutdown is required for HVAC system!s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration. of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
!.Assembly occupancies with an occupant load greater than 100 persons require panic hardware or fire exit hardware on the
required means of egress doors.
2. Portable fire extinguishers frorn a licensed contractor are required.
Page 11 of 11 Reviewed by iTorly jerger v Date 108-10-2020