HomeMy WebLinkAboutProject Informationwrightsofto Project Summary Date: Mar02,2020 Entire House By: QUICK CALCS, INC. 17 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: OUICKCALCS@AOL.COM For. THOMPSON RESIDENCE, MEL-RYCONSTRUCTION, INC. 2151 NETTLES BLVD., JENSEN BEACH, FL Notes: Weather. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 16747 Btuh Structure 15428 Btuh Ducts 4463 Btuh Ducts 6290 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 21210 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 20632 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3438 Btuh Ducts 1695 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coolingg (none) Area (ffl 1635 1635 Equipment latent load 5132 Btuh Volume (ft� 13916 13916 Air changeslhour 0.38 0.20 Equipment Total Load (Sen+Lat) 25765 Btuh Equiv. AVF (cfm) 88 46 Req. total capacity at 0.70 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR4031L1 AHRI ref Coil TEM6AOC36H31++TDR AHRI ref 7567544 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 5.6 kW Sensible cooling 20580 Btuh Heating output 19029 Btuh Latent cooling 8820 Btuh Temperature rise 18 OF Total cooling 29400 Btuh Actual airflow 980 cfm Actual airflow 980 cfm Air flow factor 0.046 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fl&- hfC wr9gts ^ 2026Mar-0214:17:24 A— -• RlghtSuite® Unimmal 2019 19.0.08 RSUD8101 Page 1 ...VAC\THOMPSON RESIDENCE- MEL-RY NETR-ES BLVD.mp Calc - MJ8 Front Doorbcea: S wrightsoft' Right-J® Worksheet Job: Entire House pate: Mar02, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 77246"799 Fax 77246"706 Email: OUICKCALCS@AOL.COM 1 Room name Entine House SFAIRS UP 2 3 F)losed wall Room height 2226 It 8.5 It 20.0 It 8.0 It healfcod 4 Room dimensions 6.0 x 20.0 It 5 Room area 1634.5 ft- 100.o fP Ty COretactim number U-telue (BtulVWF) Or HTM (Btulvftl Area (ft) or perimeter (n) Load (Bluh) Area (ftj a perimeter (ft) Load (Btuh) Heal Cod Goss WP/S Heat Cod Gross WP/S Heat Cod 6 W LG 13A-4acs 2 glazing, dr lov-e 13A1acs 0.143 0.300 0.143 n n ns 4.00 8.40 4.00 2.19 8.69 219 132 32 281 100 0 236 399 269 943 218 278 515 0 0 0 0 0 0 0 0 0 - 0 0 0 11 2 glazing, clr louse 2 glazing, clr love 13A41 o 2 glazing, dr Iowa 2 glazing, clr Iowa 2 glazing, or Iowa 2 glazing, clr Iowa 0.300 0.300 0.143 0.300 0.300 0.300 0.300 ns ne a a a a a 8.40 8.40 4.00 8.40 8.40 8.40 8.40 18.20 18.20 2.19 2372 23.72 23.72 23.72 30 15 555 4 4 6 9 0 0 517 0 0 0 0 252 125 2071 34 34 50 76 548 273 1132 95 95 142 213 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ll11VV G 1{V 2 glazing, dr Iowa 1344ocs 2 glazing, dr lows 0.300 0.143 0.300 a S 5 8.40 4.00 8.40 23.72 2.19 9.52 15 102 8 D 72 0 126 289 50 358 158 57 0 0 0 0 0 0 0 0 0 0 0 0 t)-GC w 2 glazbpr, clr Iowa 13440cs 0.300 0.143 s sw 8.40 4.00 9.52 219 24 220 0 192 202 768 228 420 0 0 0 0 0 0 0 0 EI--u : G w �--G IL-----rG, 2 glazing, cb lax-e 2 glazing, clr Iowa 13A-00cs 2 glazing, cir lava 2 g1mig, dr to -e 2 glazing, dr b*e 0.300 0.300 0.143 0.300 0.300 0.300 sw sw w w w w 8.40 8.40 4.00 8.40 8.40 8.40 16.62 16.62 219 23.72 23.72 23.72 9 19 572 12 8 12 3 7 540 0 0 0 74 161 2164 101 67 101 145 319 1182 285 190 285 0 0 160 4 8 0 0 0 148 0 0 0 0 0 593 34 67 0 0 0 324 95 190 0 w C 1344ocs 16X19-0md 0.143 0.408 nry - 4.00 1.59 2.19 1.37 34 992 34 992 134 1573 73 1358 0 100 0 100 0 159 0 137 F 22A-tph 1.358 - 38.02 0.00 727 104 3971 0 0 0 0 0 6 c)AED ecwsion 0 109 Envelope loss/gain 14035 8564 952 854 12 a) Infiltration 2712 765 229 65 b) Room ventilation 1 0 01 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 6100 0 Subtotal (lines 6 to 13) 16747 15428 1081 919 Less e°lernal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 185 114 14 Subtotal 16747 15428 1266 1033 15 Duct loads 27% 41% 4463 6290 27% 41% 337 421 Total room load 21210 21718 1604 1455 Air required (chn) 980 a80 74 66 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrlgtiesoTi- 2020-Mar-02 14:17:24 A�A -" Right -Suite® Universal 2019 19.0.08 RBW8101 Page 1 ...VACWHOMPSON RESIDENCE- MEL-RV NETTLES BLVD.mp Celc - MJB Front Doorfaces: 8 wrightsoft' RighW@ Worksheet Job: Entire House Bate: Maroz,zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34046 Phone: 772466-6799 Fax 77240"796 Email: OUICKCALCS@AOL.COM 1 Roan narre LIVING ROOM IOfCHEN 2 Exposed wall 48.4 ft 10.0 ft 3 Room height 6.0 It heaUcod ao ft heatlood 4 5 Roan dimensions Rcom area 1.0 x 241.5 It 241.5 TV 1.0 x 162.0 it 162.0 f' Ty Construction nurnber U-Ww (Btuh/ft'-'F) Or HTM (Btuhfft') Area III a perimeter (ft) Load (Btuh) Area (111 or perimeter (ft) Load (Stuh) Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 1W i-G 13A4Ccs 2 glazing, cir to a 13A-4= 0.143 0.300 0.143 n n ne 4.00 8.40 4.00 219 8.69 219 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 w 11 2 glazing, cir lawe 2 glazing, cir Io" 0.300 0.300 ne ne 8.40 8.40 18.20 10.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A-4= 2 glazing, dr it w 2 glazing, Ur $ w 2 glazing, cir lowe 2 gluing, cir lave 0.143 0.300 0.300 0.300 0.300 e : a a a a 4.00 8.40 8.40 8.40 8.40 2.19 23.72 23.72 23.72 23.72 144 0 0 6 0 138 0 0 0 0 553 0 0 50 0 302 0 0 142 0 80 0 0 0 9 71 0 0 0 0 284 0 0 0 76 155 0 0 0 213 �1 2 glazing, cir h" 13A40Cs 0,300 0.143 a s 8.40 4.00 23.72 219 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I-G 2glazing dr to -e 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 �G 2 nlazina, cir bw-e 13A400S 0.300 0.143 S sw 8.40 4.00 9.52 2.19 0 22D 0 192 0 768 0 420 0 0 0 0 0 0 0 0 ElI--u El 2 glazing, dr lowe 0.300 sw 8.40 16.62 9 2 74 145 0 0 0 0 2 glazing, cir lave- 13A-0ocs 0.300 0.143 sw w 8.40 AD0 16.62 219 19 24 3 20 161 80 319 44 0 0 0 0 0 0 0 0 2 glazing, dr lowe 2 glazing, dr low-e 2 glazing, dr la a 0.300 0.300 0.3D0 w w w 8.40 8.40 8.40 23.72 23.72 23.72 4 0 0 0 0 0 34 0 0 95 0 0 0 0 0 0 0 0 0 0 0 0 0 0 w C 13AAOCS 16X19-0171d 0.143 0.408 nw - 4.DD 1.59 2,19 1.37 0 242 0 242 0 383 0 330 0 162 0 162 0 257 0 222 F 22A-tph 1.358 - 38.02 0.00 40 8 303 0 0 0 0 0 6 c)AED excursion 109 -02 Envelops loss/gain 2404 1906 617 548 12 a) Infiltration 555 156 114 32 b) Roan ventilation 0 0 0 0 13 Memel gains: Occupants Q 230 0 0 0 0 Appiianceslother 300 1600 Subtotal Pines 6 to 13) 2959 2362 731 2181 Less edema) lead 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 32 27 14 Subtotal 2959 2362 764 2208 15 Duct loads 27% 41% 789 963 27% 41% 203 900 Total room load 1 1 3748 3325 967 3108 Air required (Cfm) 173 150 45 140 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. f}J- wri hlsotPb� 2020-Mar-0214:17:24 . L`A PSONRESID Right-RY NETTLES CRSU08101 Paget ...VAC\THOMPSON RESIDENCE-MEL-RY NETTLES BLVD.iup Celc=M,A Front Door faces: S +j+wrightsofC Right-J®Worksheet Job: Entire House Date: Mar 02,2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772486-6796 Email: QUICKCALCS®AOL.COM 1 Roan name W/D A/C CHASE 2 Eglosed wall 0 ft 0 It 3 Room height 8.0 It heat/=[ 8.0 ft hwtfcod 4 Roan dimensions 3.0 x 3.0 H 3.0 x 2.0 ft 5 Roan area 9.0 It' 6.0 fN Ty Construction number U-value (BUIVfl'-°F) Or HTM (Btuh/fil Area Ill) or perimeter (H) Load (Btuh) Area (ft') or perimeter (fl) Load (Btuh) Heat I Cod Gross WP/S Heat Cod Gross NIP/S Heat Cod 8 kl I--G 13A4ocs 2 glazing, dr lave 0.143 0.300 n n 4.00 8.40 2.19 8.69 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 w 13A-0ocs 0.143 ns 4.00 2.19 0 0 0 0 0 0 0 0 11 El 2 glazing, dr lave 2 glazing, clr lame 0.300 0.300 he ne 8.40 8.40 18.20 18.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 lQ/ 0.300 a 4.40 3.79 0 0 0 0 0 0 0 0 2gluins 2 glazing, dr low-e 2 glazing, dr a 0.300 0.300 a a 8.40 8.40 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 to 2 glazing, dr low-e 0.300 a 8.40 23.72 0 0. 0 0 0 0 0 0 2 glazing, dr lave 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 l(V 2 glazing, cir lave 13A4om 0.300 0.143 a s 8.40 4.00 23.72 Z19 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ��Ci 2 glazing, dr lave 0.300 5 8.40 9.52 0 0 0 0 0 0 0 0 2 glazing, dr b*e 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 14V lak4ocs 0.143 sw 4.00 2.19 0 0 0 0 0 0 0 0 2 gluing, cir lave 0.30(1 sw 8.40 16.62 0 0 a 0 0 0 0 0 II---GG 2 glazing, clr lawe 13A-0ocs 0.300 0. sw w 8.40 4. 16.62 2. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, dr Iowa 0.300300 w 8.4040 23.7272 0 0 0 0 0 a 0 0 2 glazing, dr 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 low-e 2 glazing, dlave r 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 W C 1344acs 16X19-0md 0.143 0.408 av - 4.00 1.59 219 1.37 0 9 0 9 0 14 0 12 0 6 0 6 0 10 0 8 F 22A-lph 1.358 - 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED excursion 0 0 Emalope lesslgain 1 14 72 1 10 8 12 a) IMBration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal pines 8 to 13) 14 12 10 8 Less e#en al load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -14 -12 -10 -8 14 Subtotal 0 0 0 0 15 Duct Inds 27% 41% 0 0 271. 41% 0 0 Total room load 0 0 0 0 Air required (cfm) 0 0 0 0 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. -FId- 2020-Mar-0214:17:24 A`k RlghtSuite® Unbersal 2019 19.0.08 RSW8101 Page 3 ...VAC%THOMPSON RESIDENCE-MEL-RY NETTLES BLVD.rup Cale=MJi Front Doorfaces: S wrightsoft• Right-J® Worksheet Job: Entire House Date: Mar02, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-46"799 Fax 772-466-6796 Emil: OUICKCALCS@A.OL.COM 1 Room name PANTRY LINEN 2 l5posed wall 0 ft O ft 3 Room height 8.0 ft tgaV000l 8.0 ft heat/cod 4 5 Room dimensions Rcom area 3.0 x 3.0 ft 9.0 ft2 3.0 x 5.0 ft 15.0 ft2 Ty Construction number U-value (BtulVft22F) Or HTM (Btuh/ft') Area (ft2) a perimeter (ft) Load (Btuh) Area (ft2) a perimeter (ft) load (Stuh) Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 lS/ I-G 13A4ocs 2 glazing, cir Icwe 0.143 0.300 n n 4.00 8.40 219 8.69 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A4aa 0.143 no 4.00 218 0 0 0 0 0 0 0 0 11 2 glazing, dr lowe 2 glazing, dr low- 0.300 0.300 ne no 8.40 8.40 18.20 18.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 l(V 134-0as 2 glazing, dr low-e 2 glazing, dr lowe 2 glazing, dr lowe 2 glazing, dr low-e 0.300 0.300 0.300 0.300 0.300 a a a a a 4.40 8.40 8.40 8.40 8.40 219 23.72 23.72 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 IIIF------�rGGG2 ljJ I�-CG 2 gluing, clr lave 13A40cs 2 glmlrg, dr lave 0.3D0 0.143 0.300 a s s 8.40 4.00 8.40 23.72 219 9.62 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1N 2 plazin q dr low- 13A4= 0.300 0.143 s sw 8.40 4.00 9.52 2.19 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 it---GG 2glazing, dr ow-e 2 glazing, air lowers 13A-0acs 0.300 0.3D0 0. sw sw W 8,40 8.40 .40 16.62 16.62 219 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, dr lave 2 glazing, dr lowe 2 glazing, dr lower 0.300300 0.300 0.300 W w w 8 8.40 8.40 8.40 23.72 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W C 13A-0oos 16X19-0md 0.143 0.408 av - 4.00 1.59 219 1.37 0 9 0 9 0 14 0 12 0 15 0 15 0 24 0 21 F 27A-tph 1.358 - 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED emersion 0 -1 Envelope loss/gain 14 12 24 20 12 a) Infiltration 0 0 0 0 b) Roan ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (Ihnes 6 to 13) 14 12 24 20 Less e#emal load 0 0 0 0 Less lmnsfer 0 0 0 0 Redistribution -14 -12 -24 -20 14 Subtotal 0 0 0 0 15 Duct loads 27-/e 41% 0 0 27°/a 41% 0 0 Total room load 0 0 0 0 Air require? (cfm) D 0 D o Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrl9r+uoTt- 2020Mar-0214:17:24 A%k RlghtSuite® Universal 201919.0.08 RSUD8101 - Page 4 ...VACVTHOMPSON RESIDENCE-MEL-RY NETTLES BLVD.rup Calc=M.➢J Front Door faces: 8 wrightsoft° Right-J® Worksheet Job: Entire House pate: Mar02,2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: OUICKCALCS@AOL.COM 1 Roorn name M WIC POWDER RM 2 Eglosed wall 8.0 It 0 It 3 Room height 8.0 It teatkool 8.0 It heaVcool 4 Room dimensions 7.0 x 8.0 ft 4.0 x 8.0 ft 5 Roan area 66.0 ft' 32.0 It' Ty Construction U-%dw Or HTM Area (M load Area (ft� Load nanber (BLWVftMF) (Bb"" a perimeter (ft) (Btuh) a perimeter (ft) (Btuh) Heat Cad Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 VN 13A-4ocs 0.143 n 4.00 219 0 0 0 0 0 0 0 0 �G 2 glazing, Gr low-e 0.300 n 8.40 8.69 0 0 0 0 0 0 0 0 13A-flocs 0.143 ne 4.00 219 0 0 0 0 0 0 0 0 2 glazing, cir lave 0.300 ne 8.40 18.20 0 0 0 0 0 0 0 0 11 2 glazing, cir lowe 0,300 ne 8.40 18.20 0 0 0 0 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 64 64 256 140 0 0 0 0 2 glazing, clr lave 0.300 a a40 23.72 0 0 0 D 0 0 0 0 2 glazing, Ur lowe 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 gluing, cir Iowa 0.3D0 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, clr lowe 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 l(V I�-CG 2 glazing, Gr lowe 134-0ocs 0.300 0.143 a s 8.40 4.00 23.72 219 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, clr lone 0.300 5 8.40 9.52 0 0 0 0 0 0 0 0 2 glazing. clr lave 0.3D0 s 8.40 9.52 0 0 0 0 0 0 0 0 W , 13A-0ocs 0.143 sw 4.00 219 0 0 0 0 0 0 0 0 2 gluing, cir low-e 0.3W sw 8.40 16.62 0 0 0 0 0 0 0 0 L�---.GG W 2 glazing, clr lave 13440cs 0.300 0.143 sw w 8.40 4.00 16.62 219 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I--G 2 glazing, cir lave 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, cir bxe 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 II--GG 2 glazing, cir Icwe 0,300 w 8.40 23.72 0 0 0 0 0 0 0 0 W 13A40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 C 16X19-Dnnd 0.4D8 - 1.69 1.37 56 56 89 77 32 32 51 44 F 22A-tph 1.358 - 38.02 0.00 0 0 0 0 0 0. 0 0 6 c)AED excursion 1 -12 -9 Envelope loss/gain 345 2D5 51 35 12 a) Infiltration 92 28 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 160 250 Subtotal pines 6 to 13) 437 380 51 285 Less e#emal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 31 26 14 Subtotal 437 380 82 311 15 Dud loads 270/o 41% 116 155 27°/ 41 % 22 127 Total roan load 1 1 553 538 104 438 Air required (don) 26 24 5 20 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. p -PI+- wrl9rrrtsoit- 2020-Mar-0214:17:24 A9 k Ri MEL-RY Un I-LES 2019 BLVD.nu 0.06 RSU08101 Page 5 ...VACITHOMPSON RESIDENCE-MEL-RY NETTLES BLVD.rup CaIc=MJB Front Dow faces: 6 wrightsoit° RighW@ Worksheet Job: Entire House Date: Mar02, 2020 QUICK CALCS, INC. By. 317 STLUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-068A796 Email: OUICKCALCS@AOL.COM 1 Roan name HALLWAY MASTER BEDROOM 2 Flposed wall 0 ft 26.8 It 3 Roan height 8.0 ft heallood 8.0 ft heat/cool 4 Roan orrenslors 1.0 x 67.6 It 1.0 x 189.5 It 5 Room area 67.5 fi 189.5 ft' Ty Construction U-value Or HTM Area (ftj Load Arm Load number (Btuh/ft'°F) (Btuh/ft°) orpedneter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross WPIS Heat Cod Gross WP/S Heat Cod 6 15/ �C 13A-4ocs 0.143 n 4.00 219 0 0 0 0 0 0 0 0 2 glazing, clr lowe 0.300 n 8.40 8.69 0 0 0 0 0 0 0 0 W 13A4ocs 0.143 ne 4.00 219 0 0 0 0 143 113 453 247 2 glazing, clr lowe 0.300 ne 8.40 18.20 0 0 0 0 30 0 252 546 11 2 glazing, clr love 0.3M ne 8.40 18.20 0 0 0 0 0 0 0 0 VN 1a4-4ocs 0.143 a 4.00 219 0 0 0 0 72 68 272 149 2 glazing, otr lo++e 0.300 a 8.40 23.72 0 0 0 0 4 0 34 95 -� 2 glazing, clr love 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, dr love 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, clr bw-e 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 14/ 1344acs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 l�-CG 2 glazing, cir 10 0.300 a 8.40 9.52 0 0 0 0 0 0 0 0 2 glazing, dr love 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 W 13A4ocs 0.143 sw 4.00 219 0 0 0 0 0 0 0 0 2 glazing, clr lowe 0,300 sw 8.40 16.62 0 0 0 0 0 0 0 0 2 glazing, clr lows 0.300 sw 8.40 16.62 0 0 0 0 0 0 0 0 w 13A-4ocs Dw w 4.00 2.19 0 0 0 0 0 0 0 0 I--G 2glazing, dr Iowa 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, dr o" 0.3D0 w 8.40 23.72 0 0 0 0 0 0 0 0 II----GG 2 glazing, dr lowe 0.3D0 w 8.40 23.72 0 0 0 0 0 0 0 0 W 1344ocs 0.143 nwe 4.00 219 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 - 1.59 1.37 68 68 107 92 190 190 300 259 F 22A4ph 1.358 - 38,02 0.00 0 0 0 0 7 1 37 0 6 c)AED excursion -3 -58 Envelope loss/gain 107 90 1348 1239 12 a) infiltration 0 0 308 87 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 500 Subtotal (frees 8 to 13) 107 g0 1656 1826 Less ekenvl load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -107 .90 40 34 14 Subtotal 0 0 1698 1859 15 Dud loads 279/ 41% 0 0 27% 41% 452 758 Total room low 0 0 2148 2817 A r rellul ed (dm) 0 0 99 116 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -FW wrr9L+>rsoR- 2020-Mar-0214:17:24 Ag--A Right -Suite® Uniwmal2019 19.0.08 RSt108101 Page 6 ...VACITHOMPSON RESIDENCE-MEL-RY NETMES BLVD.rup Calc -MB Front Door faces: S wrightsoft' Right-M Worksheet Job: Entire House Date: Mar02,2020 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-46"799 Fax 772466-6796 Emall: OUICKCALCS@AOL.COM 1 Room name ELEV. 2ND FUR M TOILET 2 EVmed wall 5.0 ft 3.0 ft 3 Room height 8.0 It heat/cool 8.0 ft heat/cool 4 5 Room dimensions Roan area 5.0 x 5.0 ft 25.0 ft- 7.0 x 3.0 ft 21.0 ft- ry construction number u-value (BtuMftk'F) Or HTM (Bwft5 Area (ft') or perimeter (ft) Load (Btuh) Area (ft5 a perimeter (ft) Load (Stuh) Heat Cool Gross WP/S Heat Cad Gross WP/S Heat CaA 6 W 1344ocs 0.143 It4.00 219 0 0 0 0 0 0 0 0 L-G 2 glazing, cir bxe 0.300 n 8.40 8.69 0 0 0 0 0 0 0 0 W 13A ocs 2 glazing, clr lower 0.143 0.300 ne ne 4.00 8.40 219 18.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 2 glazing, dr lave 0.300 ne 8.40 18.20 0 0 0 0 0 0 0 0 1344acs 0.300 a 21g 0 0 0 0 0 0 0 0 2 glazing, cir lowe 2 glazing, cir lavc 0.300 0.3m a a 8.40 8,40 &40 23.72 23.72 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1N 2 glazing, cir lave 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, dr lave 0.300 a 8.40 23.72 0 0 00 0 0 0 0 2 glazing, cir Iowa 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 ,W 13A4ocs 2 glazing, cir lave 0.143 0.300 s s 4.00 8.40 219 9.52 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Il----GG 2 plazirm, cir lave 0.300 s 8.40 9.62 0 0 0 0 0 0 0 0 ltU 13A4ocs 0.143 sw 4.00 219 0 0 0 0 0 0 0 0 II--GG 2 glazing, cir low- 2 glazing, cir Iowa 0.300 0.300 sw sw 8.40 8.40 16.62 16.62 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 13A4ocs 0.143 w 4.00 219 40 40 160 88 24 20 80 44 2 glazing, dr Iowa 0.300 w 8.40 23.72 0 0 0 0 4 0 34 95 2 glazing, dr lave 2 glazing, cir lava 0.300 0.300 w w 8.40 8.40 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W lak4ocs 0.143 nrr 4.00 2.19 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 - 1.69 1.37 25 25 40 34 21 21 33 29 F 22P tph 1.358 - 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED e=asion -0 32 Envelope loss/gain 200 118 147 199 12 a) IMihratim 57 16 34 10 b) Roan 1entllation 0 0 0 0 13 4temal gains: Occupants (off 230 0 0 0 0 Appilanceslafcer 0 250 Subtotal (lines 6 to 13) 257 134 181 459 Less a#errel load 0 0 0 0 Less transfer 0 0 0 0 Reoi t hUhm .257 -134 136 73 14 Subtotal 0 0 318 532 15 Dud loads 27-1. 41% 0 0 27% 41% 85 217 Total roan load 0 0 402 749 Air required (elm) 0 0 19 34 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -FW wrlghiso_Yt- 20201v1ar-0214:17:24 A K RlghtSuite® Universal 2019 19.0.08 RSL*8101 Page 7 ...VACITHOMPSON RESIDENCE-MEL-RY NETTLES BLVD.mp Calc=MJS Front Door Feces: 8 e wrightsoftRight-J® Worksheet Job: Entire House Date: Mar 02, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-066.5799 Fax 772-468-6796 Email: QUICKCALCS@AOL.COM 1 1 Roan name M BATH SITTING ROOM 2 Fiposed wall 15.1 ft 24.4 ft 3 Roan height 110 ft heat/cod 9.3 It heat/cod 4 5 Room dimensions Roan area 1.0 x 54.5 ft 54.5 ft' 1.0 x 233.5 It 233.5 ft' Ty Construction number U-%slue (Btuh/ftuF) Or HTM (BtuhtM Area (ft� err Padneter (ft) Load (Btuh) Area a perimeter (ft) two (Btuh) Heal Cool Gross WP/S Had Coil Grow N/P/S Heat Cod 6 W, LG 13A-4= 2 glazing, dr lawe 13A-0ocs 0.143 0.300 0.143 In n ne 4.00 8.40 4.00 2.19 8.69 219 67 0 0 57 0 0 229 0 0 125 0 0 74 32 64 42 0 39 170 259 157 93 278 86 11 2 glazing, clr lore 2 glazing, clr to ere 0.300 0.300 ne ne 8.40 8.40 18.20 18.20 0 0 0 0 0 0 0 0 0 15 0 0 0 125 0 273 a 13A-0ocs 2 glazing, dr love 2 glazing. clr love 2 glazing, olr love 2 glazing, clr love 2 glazing, cir lo✓✓e lak4ocs 2 glazing, clr lore 0.143 0.300 0.300 0.300 0.300 0,300 0.143 0.300 a a a a a a s s 4.00 8.40 8.40 8.40 8.40 8.40 4.00 8.40 2.19 23.72 23.72 23.72 23.72 23.72 2.19 9.52 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0- 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 l(J tF----(Gi IN 2 glazing, clr bwe 13A-0oos 0.300 0.143 s sw 8.40 4.00 9.52 219 0 0 l 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Eu -G IN 2 glazl g, clr low-e 2 glazing, dr low- 13A4ocs 0.300 0.300 0.143 sw sw w 8.40 8.40 4.00 16.62 16.62 2.19 0 0 64 0 0 64 0 0 256 0 0 140 0 0 65 0 0 59 0 0 237 0 0 129 2 glazing, dr love 2 glazing, dr love 2 glazing, clr loxe 0.300 0.300 0.300 w w w 8.40 8.40 8.40 23.72 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 0 60 0 0 142 IN C 13A flocs 16X19-0md 0.143 0.408 my - 4.00 1.59 219 1.37 0 55 0 55 0 Be 0 75 34 1 34 1 134 2 73 2 F 22A4ph 1.358 - 38.02 0.00 34 9 353 0: 234 24 928 0 61 c)AED em:umion 1 -18 1 -06 Envelope loss/gain 925 323 ( 2073 1010 12 a) Infiltration 174 49 326 92 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appiances/other 160 1D00 Subtotal Qines 6 to 13) 1098 522 2399 2102 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 1240 327 14 Subtotal 1098 522 3639 2429 15 Duct loads 2N/o 41% 293 213 27% 41% 970 990 Total room lard Air requhed (Cfm) 1391 64 735 33 4608 213 3419 154 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. -Pp- wrighCsoft- 2020-Mar-0214:17:24 �'rn Right-Sulte® Universal 2019 19.0.08 RSLI08101 Page 8 ...VACITHOMPSON RESIDENCE-MEL-RY NETTLES BLVD.rup Calc=MJB Front Doorfaces: S wrightsoft• Right-J® Worksheet Job: Entire House pate: Mar 02,2o20 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772386-6799 Fax 772-468-0796 Email: OUICKCALCS@AOL.COM 1 Room name aATH 2 BEDROOM 2 2 FVosed wall 16.9 ft 129 It 3 Room height 9.3 It heat/cool 9.3 It heaVcod 4 5 Room dimensions Room area 1.0 x 80.0 ft 80.0 ft' 1.0 x 125.5 ft 125.5 fP Ty Conshucti number on U-vdlue F) (BluNft;° Or HTM (Btdvftl ar�paimeter (ft) Load (Btuh) Atea meter (ft) or peri Load (Btuh) Halt Cod Gross NIP/S Heat Cod Gross WP/S Heat Cod 6 13AAOCS 2 gluing. or love 0.143 0.300 n n 4.00 8.40 219 8.69 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 w 13A-4ecs 0.143 ne 4.00 219 63 83 333 182 0 0 0 0 11 2 gluing, dr lowe 2 glaring, or Ioxe 0.300 0.300 ne ne 8.40 8.40 18.20 18.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.300 a 219 74 70 280 150 120 100 424 232 2 glui g, dr lox-e 2 gluing, 0.300 a 8.40 8,40 23.72 0 0 0 0 0 0 0 0 2 glazing, drlow-e 0.300 a S40 23.72 4 0 34 95 0 0 0 0 2 glazing, dr lave 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, or lc a 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, clr lava 0.300 a 8.40 23.72 0 0 0 0 15 0 125 356 13A4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 T� 2 glazing, clr love 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 2 glazing, dr lowe 0.300 s 8.40 9.62 0 0 0 0 0 0 0 0 1N- 13440cs 0.143 sw 4.00 219 0 a 0 0 0 0 0 0 �,-GG 2 glazing, clr Iox-e 0.300 sw 8.40 16.62 0 0 0 0 0 0 0 0 2 glazing, clr lave 0,300 sw 8.40 16.62 0 a 0 0 0 0 0 0 w 13A4= 0.143 w 4.00 219 0 0 0 0 0 0 0 0 2 glazing, clr bwe 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, dr love 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 2 glazhg, ar bve 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 w 134-0oes 0,143 rev 4.00 2.19 0 0 0 0 0 0 0 0 C 16X194md 0.408 - 1.59 1.37 0 0 0 0 0 0 0 0 F 22A-tpl 1.358 38.02 0.00 80 17 e43 0 126 13 491 0 6 c)AED exursion -11 -0 Envelope loss/gain 1292 420 1041 584 12 a) Infiltration 225 64 173 49 b) Room %entllafion 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 250 900 Subtotal (lines 6 to 13) 1617 733 1214 1532 Less edemal load 0 0 0 0 Less trdmfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1517 733 1214 1532 15 Duct loads 27% 41% 404 299 27% 41% 324 625 Total room load 1922 1032 1538 2167 Air required (cfm) 89 47 71 i1i Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -Fw wrlghisoic- 2020-Mar-0214:17:24 lebA -'-' Right -Suite® Universal 2019 19.0.08 RSUuB101 Page 0 ...VACkTHOMPSON RESIDENCE- MEL-RY NETTLES BLVD.rup Calc = MJB Front Doorfaces: S +� wrightsoft' Right-M Worksheet Job: Entire House Date: Mar 02, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL3494S Phone: 7724666799 Fax 7724666796 Email: QUICKCALCSCAOL.COM 1 Room name CLST 2 AHU CLST 2 Exposed wall 0 it 0 It 3 Roan height 9.3 it heallcod 9.3 ft heaticod 4 Rcon dimenslons 1.0 x 16.5 ft 3.0 x 3.0 ft 5 Room area 18.5 ft' 9.0 ft' Ty Construction U-value Or HTM Area (11) load Area (ft� load number (BtutVftk'F) (Btuwftl a perimeter (ft) (Btuh) a perimeter (ft) (8tuh) Heat Cool Gross WP/S Heat Cod Gross NIP/S Heat Cod 6 lqJ L--l' 134-4= 2 glazing, dr lav-e 0.143 0.300 n n 4.00 8.40 219 8.69 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A40cs 0.143 ne 4.00 219 0 0 0 0 0 0 0 0 11 2 glazing, dr lows 2 glazing, cir lave 0.300 (13D0 ne ne 8.40 8.40 18.20 18.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A4as Q143 a 4.00 219 0 0 0 0 0 0 0 0 2 glazing, dr lave 0.300 a 6.40 23.72 0 0 0 0 0 0 0 0 2 glazing, cir lcw a 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, cir love 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, cir Iowa 0.300 a 8.40 23.72 0 I a 0 0 0 0 0 0 2 glazing, cir love 0.300 a 8.40 23.72 0 0 01 0 0 0 0 0 Nil 1344005 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 UGC 2 glazing, cir Im" 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 2 glazinq, cir love 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 uV 1344ow 0.143 sw 4.00 Z19 0 0 0 0 0 0 0 0 {L-GG 2 glazing, cir low-e 0.300 sw 8.40 18.62 0 0 0 0 0 0 0 0 2 glazing, cir lave 0.300 sw 8.40 le62 0 0 0 0 0 0 0 0 13A4ocs 0.3w w 2.72 0 0 0 0 0 0 0 0 2 glazing, dr bwe 0.300 w 8,40 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, dr bwe 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, Gr Iowa 0.300 w 8.40 23.72 0 0 0 0 0 0 0 0 w 13A4ocs 0.143 nw 4.00 2,19 0 0 0 0 0 0 0 0 C 16X190md 0.4D6 - 1.59 1.37 0 0 0 0 0 0 0 0 F 22A-lph 1.358 - 38.02 0.00 17 0 0 0 9 0 0 0 6 c)AED excursion 0 0 Envelope loss/gain 0 0 0 0 12 a) Infiltration 0 0 0 0 b) Roan ventilatim 0 0 0 0 13 Internal gains: Occupants ® 230 0 0 0 0 Appiiancesfother 0 0 Subtotal (lines 6 to 13) 0 0 0 0 Less e#m eal load 0 0 0 0 Less transfer 0 0 0 0 Re6stribldlm 0 0 0 0 14 Subtotal 0 0 0 0 15 Dud loads 27% 41% 0 0 27% 41% 0 0 Trial roan load 0 0 0 0 Air requlred (cfm) 0 o D D Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A-rk- w��9tibo�f'!- 2020-Mar-0214:17:24 & Right -Suite® Uniwrsal 2019 19.0.08 RSU08101 Page 10 ...VACITHOMPSON RESIDENCE-MEL-RY NETTLES BLVD.rop Calc=MJ8 Front Doorfaces: S I wrightsoft Right-M Worksheet Job: Entire House Date: Mar 02,2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-465-8798 Enafl: QUICKCALCS@AOL.COM 1 Roan name ELEW3OR 1ST FLR STAIR STORAGE 2 E)posed wall 5.0 It 9.0 it 3 Roan height 9.3 It heatlood 9.3 ft hwVcod 4 Room dimersiona 4.0 x 6.0 it 6.0 x 9.0 it 5 Roan am 20.0 ft° 45.0 ft° Ty Construction U-value Or HTM Area (ft5 load Am (ftzj load number (BtutVfl;`F) (Btuh/ftj or perimeter (it) (Btuh) a perimeter (it) (Btuh) Heal Carl Gross NIP/S Heat Cool Grass WP/S Hit Cad 6 W L-C 134-0acs 2 glazing, cir lo*e 0,143 0.300 n n 4.00 8.40 219 8.69 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 13AAOCS 0.143 ne 4.00 219 0 0 0 0 0 0 0 0 11 2 glazing, clr Iowe 2 glazing, dr lave 0.300 0.300 ne ne 8.40 8.40 18.20 18.20 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 lql 1344acs 0.143 a 4. 219 0 0 0 0 0 0 0 0 G 2 glazing, dr lave 2 glazing, Or have 0.300 0.300 a a 8.4040 8.40 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, dr lows 0.300 a 8.40 23.72 0 0 0 0 0 0 0 0 2 glazing, clr lave 0.300 a B-40 23.72 0 0 0 0 0 0 0 0 'lltlL---�;rG 2 glazing, clr low-e 0.300 a 8.40 23.72 0 0 0 0 '0 0 0 0 l(V lak4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 l�-CG 2 glazing, dr lave 0.300 s 8.40 9.52 0 0 0 0 0 0 0 0 2 glaiinq, clr love 0.3D0 s 8.40 9.62 0 0 0 0 0 0 0 0 lSV 13A-4= 0.143 sw 4.00 2.19 0 0 0 0 0 0 0 0 IL-GG 2 glazing, dr lowe 0.3D0 sw 8.40 16.62 0 0 0 0 0 0 0 0 W 2 glazing, clr lowe 13A4= 2 gluing, dr lowe 0.3D0 0.143 0.3D0 sw w w 8.40 4.00 6.40 16.62 219 23.72 0 47 0 0 47 0 0 186 0 0 102 0 0 84 0 0 84 0 0 335 0 0 183 0 2 glazing, or low-e 2 glazing, clr lows 0.300 0.3D0 w w 8.40 8.40 23.72 23.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W C 13A-4ocs 16X19Oex1 0.143 0.4D8 my - 4.00 1.59 2-19 1.37 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 F 22A-(ph 1.358 - 38.02 0.00 20 5 190 0 45 9 342 0 6 c)AED excursion -0 -7 Envelope loss/gain 376 98 677 177 12 a) Infiltration 67 19 12D 34 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliarces/other 0 0 Subtotal (lines 6 to 13) 443 117 797 210 Less e#ernal load 0 0 0 0 Less lmnsfer 0 0 0 0 Redistribution 443 -117 -797 -210 14 subtotal 0 0 0 0 15 Duct loads 27% 41% 0 0 VIA 41°/ 0 0 Total room load 0 0 0 0 AIr required (dm) 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mer-0214:17:24 Right-MEL.RY Universal ILESB0191up CRSW8101 Page 1l ...VAC\THOMPSON RESIDENCE-MEL-RY NETTLES BLVD.rup CeIc=MJB Front Door feces: 8 I wrightsoftRight-M Worksheet Job: Entire House Date: Mar 02, zozo QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34D46 Phone: 772466-6799 Fax 7724666796 Email: OUICKCALCS@AOL,COM 1 Roam name FOYER 2 Egwsed wag 18.0 ft 3 Roan height 9.3 ft heauc0ol 4 Room dimensions 1.0 x 117.0 ft 5 Room am 117.0 fP Ty Construction number U-value (BtWfti'F) Or HIM (sh"Il) Area (ftz or perimeter (ft) Load (Stuh) Area a perimeter Load Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cool 6 UN L--G 13A-4= 2 glazing, clr lov-e 0.143 0.300 n n 4.00 8.40 2-19 8.69 0 0 0 0 0 0 0 0 134-4acs 0.143 re 4.00 219 0 0 0 0 2 glazing, cif bwe 0.300 ne 8.40 18.20 0 0 0 0 11 2 glaring, cir lore-e 0.300 ne 8.40 16.20 0 0 0 0 13A40es 0.143 a 4.00 719 0 0 0 0 G 2 gluing, dr bwe 0.300 a 8.40 23.72 0 0 0 0 2 gluing, dr love 0.300 a 8.40 23.72 0 0 0 0 2 glazing, cir lore 0.300 a 6.40 23.72 0 0 0 0 2 glazing, dr to a 0.300 a 8.40 23.72 0 0 0 0 2 glazing, dr low-e 0.300 a 8.40 23.72 0 0 0 0 lW 13A40cs 0.143 s 4.00 2.19 102 72 289 158 2 glazing, cir laws 0.300 s 8.40 9.62 6 0 50 57 2 glazing. cir Iowa 0.300 s 8.40 9.52 24 0 202 228 w 13A4ocs 2 glazing, clr low-e 0.143 0.300 sw sw 4.00 8.40 219 16.62 0 0 0 0 0 0 0 0 ' 2 g1wig, cir low-e 0.30D sw 8.40 16.62 0 '0 0 0 R143 w 4.00 2.19 65 59 237 129 N13Abocs 2 glazing, cir lox-e 0.3D0 w 8.40 23.72 0 0 0 0 2 glazing, dr loxe 0.300 w 8.40 23.72 0 0 0 0 2 gluing, dr Ime 0.3D0 w 8.40 23.72 6 0 50 142 w 13AAccs 0.143 nw 4.Oo 219 0 0 0 0 C 1SX19-0md 0.408 - 1.59 1.37 3 3 5 4 F 27A-tph 1.358 - 38.02 0.00 117 18 684 0 6 c)AED excursion -12 Envelope loss/gain 1518 707 12 a) Infiltration 240 68 b) Room vemilatim 0 0 13 internal gains: Occupants @ 230 0 0 Applianceslother 750 Subtotal (lines 6 to 13) 1757 1525 Less eldemal load 0 0 Less transfer 0 0 Redistdbution 0 0 14 Subtotal 1757 1525 15 Duct loads 27-/e 41% 468 622 Total room load 2228 2146 Air required (cfm) 103 97 Calculations approved by ACCA to meet all requirements of Manual J Bth Ed. wrlgh-Eaalm- 2020-Mar-02 14:17:24 "'-" Right -Suite® UnlwmI 201919.0.08 RSU08101 Page 12 ...VAC\THOMPSON RESIDENCE-.MEL-RY NETTLES BLVD.rup Cale =MJB Front Door faces: S Duct System Summary Job: vvrightsoft Y � Date: ma.oz,zozo Entire House By: QUICK CALCS, INC. • 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-066-6796 Emil: QUICKCALCS@AOL.COM For. THOMPSON RESIDENCE, MEL-RYCONSTRUCTION, INC. 2151 NETTLES BLVD., JENSEN BEACH, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 10.600 in H2O 1.000 in/100ft 980 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.600 in H2O 1.000 in1100ft 980 cfm 199 ft Name Design (Btuh) Htg (cfm) Clg (Cfm) Design FR Diam (n) H x W (n) Duct Mall Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 1922 89 47 1.000 6.0 Ox 0 VIFx 17.3 115.0 st2 BEDROOM 2 c 2157 71 97 1.000 7.0 Ox 0 VIFx 12.2 115.0 st2 FOYER h 2226 103 97 1.000 7.0 Ox0 VIFx 5.0 95.0 KITCHEN c 3108 45 140 1.000 8.0 Ox 0 VIFx 24.6 150.0 st5 LIVING ROOM h 3748 173 150 1.000 8.0 Ox0 VIFx 23.6 150.0 st5 M BATH h 1391 64 33 1.000 5.0 Ox 0 VIFx 27.8 170.0 st4 M TOILET c 749 19 34 1.000 5.0 Ox 0 VIFx 28.7 170.0 st4 M WIC h 553 26 24 1.000 5.0 Ox0 VIFx 24.5 150.0 st3 MASTER BEDROOM C 2617 99 118 1.000 7.0 OxO VIFx 20.7 150.0 st3 POWDER RM c 438 5 20 1.000 5.0 Ox O VIFx 18.4 150.0 st3 SITTING ROOM h 4608 213 154 1.000 8.0 Ox O VIFx 15.3 116.0 st2 SwIRSUP h 1604 74 66 1.000 6.0 Ox0 VIFx 20.7 150.0 st3 Trunk Htg CIg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (In) (1n) Material Trunk st4 Peak AVF 83 67 1.000 422 6.0 0 x 0 VinlFlx st3 st3 Peak AVF 287 295 1.000 667 9.0 0 x 0 VinlFlx SH st5 Peak AVF 218 290 1.000 657 9.0 0 x 0 VinIFIx st1 st2. Peak AVF 373 298 1.000 844 9.0 0 x 0 VinIFIX st1 Peak AVF 504 585 1.000 745 12.0 0 x 0 VinlFlx wrighttsaft- 2D20-Mar-02 14:17:34 I\ ....�, •..w..,.••.•o Right -Suite® Unhersal 201919.0.08 RSL108101 Page 1 ...VAC1hi0MPSON RESIDENCE-MEL-RY NETTLES BLVD.rup Calc=MJ3 Front Door faces: S Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rbl Ox0 1 980 980 0 1 0 0 0 Ox 0 1 VIFx .� wrightsoft' 2020-Mar-0214:17:34 �t .��•—.-. Right -Suite® Universe] 2019 19.0.08 RSU08101 Page 2 ...VACIIHOMPSON RESIDENCE-MEL-RY NETRES BLVD.rup Calc=M.t From Daor faces: S