HomeMy WebLinkAboutConstruction PlansPHUTOVOLTAk, RuOF MOUNT SYSTEM
34 MODULES -ROOF MOUNTED-11.560 kW DC, 8.160 kW AC, 6801 COQUINA AVE, PIERCE, FL 34951
PHOTOVOLTAIC SYSTEM SPECIFICATIONS:
SYSTEM SIZE:
11.560 kW DC
8.160 kW AC
MODULE TYPE & AMOUNT:
(34) HANWHA Q.PEAK DUO BLK-G6+340W
MODULE DIMENSIONS:
(LIW/H) 68.5-140.6'/1.26-
INVERTER:
(34) ENPHASE ENERGY 1Q7-60-2-US [240V]
INTERCONNECTION METHOD: LOAD BREAKER
GOVERNING CODES
ALL WORK SHALL CONFORM TO THE FOLLOWING CODES
a. 2014 NATIONAL ELECTRICAL CODE
b. 2017 FL BUILDING CODE - 6TH EDITION
C. 2017 FL RESIDENTIAL CODE - 6TH EDITION
d. 2017 FL PLUMBING CODE-6TH EDITION
e. ANY OTHER LOCAL AMENDMENTS
PROOF ACCESS POINT
ROOF ACCESS POINT SHALL NOT BE LOCATED
IN AREAS THAT DO NOT REQUIRE THE
PLACEMENT OF GROUND LADDERS OVER
OPENINGS SUCH AS WINDOWS OR DOORS,
AND LOCATED AT STRONG POINTS OF
BUILDING CONSTRUCTION IN LOCATIONS
WHERE THE ACCESS POINT DOES NOT
ROOF #'
(05) HANWHA Q.PEAK DUO BLK-G6+
340VN
SLOPE:17'
AZIM.: 360'
EXISTING INTERIOR MAIN
SERVICE PANEL TIED TO
EXTERIOR UTILITY METER# --
CONFLICT WITH OVERHEAD OBSTRUCTIONS ROOF#3
SUCH AS TREE LIMBS, WIRES OR SIGNS. (04) HANWHA Q.PEAK DUO BLK-G6+
34OW
GENERAL NOTES: SLOPE:17°
1. APPLICABLE CODE: 2017 FLORIDA BUILDING CODE AZIM.:270°
(6TH EDITION) & ASCE 7-10 MINIMUM DESIGN LOADS
FOR BUILDING AND OTHER STRUCTURES.
2. LAG SCREW DIAMETER AND EMBEDMENT LENGTHS
ARE DESIGNED PER 2017 FLORIDA BUILDING CODE
(6TH EDITION) REQUIREMENTS. ALL BOLT
CAPACITIES ARE BASED ON A SOUTHER YELLOW PINE
(SYP) RESIDENTIAL WOOD ROOF RAFTERS AS
EMBEDMENT MATERIAL.
3. ALL WIND DESIGN CRITERIA AND PARAMETERS ARE
FOR HIP AND GABLE RESIDENTIAL ROOFS,
CONSIDERING FROM A 7° TO A MAXIMUM 23° (5112 TO
A MAXIMUM 7112 PITCH) ROOF IN SCHEDULE.
CONTRACTOR TO FIELD VERIFY THAT MEAN ROOF
HEIGHT DOES NOT EXCEED 15'-0°.
4. ROOF SEALANTS SHALL CONFORM TO ASTM C920
AND ASTM 6511, AND IS THE RESPONSIBILITY OF THE
CONTRACTOR TO PILOT DRILL AND FILL ALL HOLES.
5. ALL DISSIMILAR MATERIALS SHALL BE SEPARATED
WITH NEOPRENE WASHERS, PADS, ETC OR SIMILAR.
6. ALL ALUMINIUM COMPONENTS SHALL BE ANODIZED
ALUMINIUM 6105-T5 UNLESS OTHERWISE NOTED.
7. ALL LAG SCREW SHALL BE ASTM A276 STAINLESS
STEEL UNLESS OTHERWISE NOTED.
B. ALL SOLAR RAILING AND MODULES SHALL BE
INSTALLED PER MANUFACTURER INSTRUCTIONS.
9. CONTRACTOR SHALL ENSURE ALL R00� OPERTYLINE
PENETRATIONS TO BE INSTALLED AND SEALED PE
2017 FLORIDA BUILDING CODE (6TH EDITION) OR
LOCAL GOVERNING CODE,
1 PLOT PLAN
A oo SCALE: 1/16'=17
T
6801 COQUINA AVE
FRONT OF HOUSE
75-On
.S
ILE COPY
ROOF ACCESS POINT
I'41N. SETE
FRONT
81DE8 .���
CNq DIDtfII
SHEET INDEX:
PV0.0:
COVERSHEET
PV 1.0:
SITE PLAN
E S 1.1:
MOUNT DETAILS
E 1.1:
3-LINE DIAGRAM
E 1.2:
ELECTRICAL NOTES
E 1.3:
WARNING LABELS
DS-01+ DATA SHEET
CLIMATIC SOLAR
,em.°ema,°rer.wwn.
650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 772-567-3104
FAX: V72) 567-4553
wwwAimaticsolamom
11 oEsauPnDN I DATE I REV 11
W
W
Q
m
Z
w
CyLLZ
0
LaO
Z
U_
w _
W
w
co
a
SATELLITE VIEW
2 A-00 SCALE: NTS
SHEET NAME
Vero Beach
IOOF#1 )4) HANWHA Q.PEAK DUO BLK-G6+ COVER , ,,._ .,!� I,I � � \+, ,
40w SHEET
;LOPE: 17o
I -Oslo - }
4- i ^ - 'R.0daRldge`-
•1. y+ ^?' S { r SHEET SIZE
68a7uina Avenue - ANSI B
W6 F L` n n
DQF #4 r o' - 'snkewood I11 ,' v 11 X 17
2) HANWHA Q.PEAK DUO BLK-G6+ m i 1?a; , 'r �i, ' SHEET NUMBER
10W n
LOPE: 18i.LUCIE COUNTY I " �^ ;,;7 �'7 „-00
ZIM.: 180° PLAN REVIEW - _ r "^ `' Tressuro Ccaatr
(: riIntemaRonal ;SIGNATURE WITH SEAL
Al endt( ts1`i�t
BLDG: Business Park,j SttLu
DATE
ELE �' 3 _ VICINITY MAP
DATE: !i^'
PLUMB: A-0D SCALE: NTS
Sf
DATE:
DATE:,
��; � _.. - - t:
';', ? ..
.. ' ,,; I , . 'r
c�
` 4�
� ��.�
.-` �\'
� q
�-�./_ f �
� / +' 1
_\`
�� �
�� J
�
l
_-•
\ ��
E
6801 COQUINA AVE
FRONT OF HOUSE
• 01
�?�C,a
1 SITE PLAN MODULE RATING IS -55.6 PSF SO MODULES
aa1 SCALE: 3132' =17 MAY BE INSTALLED IN ALL 3 ROOF ZONES
ROOF SECTIONS
ROOF
MODULE -
04
#01 I
SLOPE -
176
IVAZIMUTH
900
MATERIAL
COMPSHINGLE
RAFTER SIZE -
2'X4' @ 24' O.C.
FR—OO—Fl
MODULE -
05
#02
SLOPE
17°
ITAZIMUTH
360°
MATERIAL
COMPSHINGLE
RAFTER SIZE -
2'X4' @ 24" O.C.
ROOF
MODULE -
04
SLOPE -
170
AZIMUTH
2700
MATERIAL
COMPSHINGLE
RAFTER SIZE -
2'X4' @ 24' O.C.
ROOF
MODULE -
22
#04
SLOPE -
170
AZIMUTH -
1800
MATERIAL -
COMPSHINGLE
RAFTER SIZE - 2'X4' @ 24' O.0
CIRCUIT(S)
® CIRCUIT #1-12 MODULES
®CIRCUIT#2-11 MODULES
® CIRCUIT #3 -11 MODULES
PRESSURES DERIVED FROM PAGE 25
COMPONENTS AND CLADDING TABLE 2017
FBC 6TH ED RESIDENTIAL RISK II
ENCLOSED STRUCTURE USING 18 SQ FT
AFFECTED AREA 160MPH WIND
ADJUSTMENT FACTOR FROM EXPOSURE B
TO EXPOSURE C MEAN ROOF HEIGHT 12 FT
FT OF 1.21 ROOF PITCH 17.0 DEGREES
KD=.85 KZT =1.0 TERRAIN IS FLAT
GENERAL INSTALLATION PLAN NOTES:
1) ROOF ATTACHMENTS TO SEE RAFTERS SHALL BE INSTALLED AS
SHOWN IN SHEET S-01 AND AS FOLLOWS FOR EACH WIND ZONE:
WIND ZONE 1:4'-0" O.C.
WIND ZONE 2: 2'-0" O.C.
WIND ZONE 3:2'-O" O.C.
SYSTEM LEGEND
EXISTING INTERIOR MAIN SERVICE PANEL& POINT OF
INTERCONNECTION. TIED TO EXTERIOR UTILITY METER.
NEW SOLADECK JUNCTION BOX
J NEW DEDICATED PV SYSTEM COMBINER PANEL
34 NEW HANWHA QPEAK DUO BLK-G6+340W
MODULES WITH
NEW 34 - ENPHASE ENERGY I07-60-2-US 1240A
INVERTERS, MOUNTED ON THE BACK OF EACH
MODULES.
]O = ROOF OBSTRUCTIONS
= ATTACHMENT POINTS
_- =RAFTER
-- =RACKING SYSTEM
= CONDUIT EXTERIOR RUN
-- = CONDUIT ATTIC RUN
= WIND ZONE 1
= WIND ZONE 2
= WIND ZONE 3
MODULE, ARRAY WEIGHT
(LOAD CALC'S)
:r of Modules 34
a Weight 43.9 LBS
dodule (Array) Weiahl 1 1492.60 1 LBS
of Attachment point 71
1 System Weight 1.5
1599.10
21.02
Array Area 656.65
iuted Load 2.35
M WaAITMkWAm+)
Roof Area 1008
Percentage or Roof Covered 65.14%
YAmIWRa°l )"w
DESIGN CRITERIA
ND SNOW LOAD (psf)
SPEED (mph)
SURE CATEGORY
HEIGHT (ft.)
LENGTH (ft.)
WIDTH (ft.)
'ET HEIGHT (ft.)
DESIGN CALCULATION
2) THE PERIMETER WIDTH DIMENSION IS CALCULATED AS FOLLOWS:
LEAST HORIZINTAL DIMENSION OF BUILDING:15 FT X.1 =1.5 FT ZONE WIDTH
40% OF MEAN ROOF HEIGHT (12 FT) = 4.8 FT WIND ZONE I
USE THE SMALLER OF THE TWO, 3 FT
WHICH IS GREATER THAN THE MINIMUM OF 3 FT. WIND ZONE I
LBS
LBS
LBS
LBS
SgFt
SgFt
Per SgFt
SgFt
20
0
160
B
12
63
15
0
1 OF PRESSURE COEFFICIENT
X10%(ft.) 1 1.5
4.0'
-73.900
CLIMATIC SOLAR
rme.."eieme,yywwas
650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 772-567-3104
FAX: (772) 5674553
www.dimatiesolar.com
REVISIONS
DEWFUPIION
DAIS
REV
PROJECT NAME
LU
LU
W Q rn
I
z
LuZ
O
�
Z � d
LLI
LL 00 a
cc
C9
SHEET NAME
SITE PLAN
SHEET SIZE
ANSI B
11" x 17"
SHEET NUMBER
A; Q1
SIGNATURE WITH SFALI
/�y�zo
SEE
ENE
' 1 \ ATTACHMENT DETAIL (SIDE VIEW)_
gDt / SCALE: NTS
130
IRONRIDGE END / MID
CLAMP
PV MODULES
IRONRIDGE XR-100
RACKING SYSTEM
QUICKMOUNT L-FEET
QUICKMOUNT FLASHING
WASHER SEALING 5116" ID x
3/4"OD EPDM BONDED SS
2"X4" RAFTERS @ 24" OC
LAG BOLT, 5/16"
LAG BOLT TO BE SUPPLIED BY
QUICK MOUNT IN THE FLASHING
KIT AND IS 5/16" X 4" WITH 2-1/2"
THREADS AND EMBEDDED INTO
TRUSS 3-1/2"
ao�
150
115
wamm
HMm
Nadis"n
ub"y R snanrcs
Wablla
F med
Dme �
Notes:
1. Values are nominal design 3-second gust
1 wind speeds in miles per hour (m/s) at 33
ft (iem) above ground for Exposure [ cat-
egory.
2. Linear interpolation between contours I
is permitted.
1 3. Islands and coastal areas outside the
last contour shall use the last wind speed
contour of the coastal area.
4. Mountainous terrain, gorges, ocean
promontories, and special wind regions
shall be examined for unusual wind condi-
tions.
$, wind speeds correspond to approximately
a 7% probability of exceedance in 50 years
i (Annual Exceedance Probability = 0.00143,
MRI = 700 years).
_ s
AA��.�
15 130 NW%
CLIMATIC SOLAR
ren.�m.�,�,W�650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 772567.3104
FAX: (772) 567-4553
140 www.dimaticsolar.com
I REVISIONS
DESCRIPTON DAIS REV
0LU
i �,
V
LU
C3
Q
Dade
W
N
Lfi
_j U_ W
W
_ aMlh
IL
W d
U_
O
W d
18/0
co
° ° I MOUNT
DETAIL
Figure 1609A Wind -Borne Debris Region, Category II and III
Buildings and Structures except health care facilities
11" x 17"
SHEET NUMBER
S-01:
SI.NATUREMNSEALp
WIRE
WIRE
WIRE
WIRE TYPE
TEMP
WIRE
TEMP
CONDUIT
WIRE
TERMINAL
INVERTER
NOC:
NEC:
STRING
GRND
GRND WIRE
TAG#
WIRE FROM--
CONDUIT
QTY
GAUGE:
NCLUDESp1]GROOUallo
RATING:
AMP
DE -RATE:
FILL:
OCP:
75°CRATING:
CITY:
AMPS
SIZE
TYPE
O1
ARRAY TO JUNCTION BOX
PV WIRE
6
#10
TRUNK CABLE
90,
40A x 0.96A x 0.80A = 30.72A
35A
12 x 1.0 x 1.25 = 15.00A
#6
SBC
O2
JUNCTION BOX TO COMBINER PANEL
3/4
ELECTRICAL
6
#10
THWN-2
90,
40A x 0.76A x 0.80A = 24.32A
35A
12 x 1.0 x 1.25 = 15.00A
#8
THWN-2
CONDUIT
O
COMBINER PANEL TO MSP
ELECTRICAL
3
#8
THWN-2
75"
50A x 0.94A x 1.00A = 47.OA
50A
34 x 1.0 x 1.25 = 42.50A
#8
THWN-2
CONDUIT
Rooftop conductor ampacities designed in compliance
with art. 690.8, Tables 310.15(B)(2)(a), 310.15(B)(3)(a),
310.15(B)(3)(c), 310.15(B)(16), Chapter 9 Table 4, 5, & 9
Location specific temperature obtained from ASHRAE
2017 data tables
RECORD LOW TEMP
0"C
AMBIENT TEMP (HIGH TEMP 2%)
330C
CONDUIT HEIGHT
0.51
ROOF TOP TEMP
550C
CONDUCTOR TEMPERATURE RATE ON ROOF
900C
CONDUCTOR TEMPERATURE RATE OFF ROOF
75°C
i......mono, 1.0.01
Ieeeeeeeei Ieeeeeeeeeei IeeeeE
E 04.1eee flip
12 I= ....
TERMINATOR CAP ON LAST CABLE
CONNECTOR AC TRUNK CABLE (TYP)
ENPHASE Q CABLE TO BE ATTACHED TO RAIL
MIN. 3-1/2" ABOVE ROOF SURFACE
Solardeck box or UL 1741 Approved
Equivalent to transition from Q-Cable to
THWN-2 wire no fuse required r
(N) Combiner Panel Enphase IQ
Combiner X-IQ- AMl-240-3
64AI240V
16A
15A
I Envoy-S I
CLIMATIC SOLAR
.,nmrc"be^SOY Wulbw
650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 7725673104
FAX (772) 567-4553
v .cfhaticsolar.com
I REVISIONS I
DE$Q%PRON DATE I REV
Point of Interconnect, Supply Side
ILu
EXISTING 240V/225A BUS BAR
z
¢ rn
RATING, Main Service Panel, Single
LLI
`-J'
Phase, with a 200A Main Disconnect
N
z .
LJJ
lL'
ZD U- LLi
Cpw0
Z
U W _
M
LL.LL
� dCID
200A
(E)LOADS
45A
J 0------------------- ---
---------------------
ti G
—
I
Existing Grounding
Electrode System
120% RULE
BUS BAR RATING X 120%) - MAIN BREAKER RATING
= MAX. PV OCPD
(225A x 120%) - 200 = 70A
KINE
DIAGRAM
11" x 17"
SHEET NUMBER
E-01
3NATURE WITH f Ek,
, CI.
i=
.;1
WIRE
WIRE
WIRE
WIRE TYPE
TEMP
WIRE
TEMP
CONDUIT
WIRE
TERMINAL
INVERTER
NOC:
NEC:
STRING
GRND
GRND WIRE
TAG#
WIRE FROM --
CONDUIT
CITY
GAUGE:
IINNCWDDEESa1zGROUNDD
RATING:
AMP
DE -RATE:
FILL:
OCP:
75°CRATING:
QTy;
AMPS
SIZE
TYPE
O1
ARRAY TO JUNCTION BOX
PV WIRE
6
#10
TRUNK CABLE
900
40A x 0.96A x 0.80A = 30.72A
35A
12 x 1.0 x 1.25 = 15.00A
#6
SEC
O2
JUNCTION BOX TO COMBINER PANEL
3/4
ELECTRICAL
6
#10
THWN-2
900
40A x 0.76A x 0.80A = 24.32A
35A
12 x 1.0 x 1.25 = 15.00A
#8
THWN-2
CONDUIT
O3
COMBINER PANEL TO MSP
3/4°
ELECTRICAL
3
#8
THWN-2
75°
50A x 0.94A x 1.00A = 47.00A
50A
34 x 1.0 x 1.25 = 42.50A
#8
THN-2
W
CONDUIT
®
[COMBINER PANEL TO MSP
ELECTRICAL
3
#6
THWN-2
750
65A x 0.94A x 1.00A = 61.10A
65A
34 x 1.0 x 1.25 = 42.50A
#8
THWN-2
CONDUIT
Rooftop conductor ampacities designed in compliance
with art. 690.6, Tables 310.15(B)(2)(a), 310.15(B)(3)(a),
310.15(B)(3)(c), 310.15(B)(16), Chapter 9 Table 4, 5, & 9
Location specific temperature obtained from ASHRAE
2017 data tables
RECORD LOW TEMP
0°C
AMBIENT TEMP (HIGH TEMP 2%)
33°C
CONDUIT HEIGHT
0.5'
ROOF TOP TEMP
55°C
CONDUCTOR TEMPERATURE RATE ON ROOF
90°C
CONDUCTOR TEMPERATURE RATE OFF ROOF
75°C
11 MICRO -INVERTERS IN BRANCH CIRCUIT#3
11 MICRO -INVERTERS IN BRANCH CIRCUIT#2
12 MICRO -INVERTERS IN BRANCH CIRCUIT#1
TERMINATOR CAP ON LAST CABLE
CONNECTOR AC TRUNK CABLE (TYP)
ENPHASE Q CABLE TO BE ATTACHED TO RAIL
MIN. 3-1/2" ABOVE ROOF SURFACE
(N) Combiner Panel Enphase IQ
Combiner X-IQ- AM1-240-3
64A/240V Continuous, protection
max 80A breaker on solar ouput;
with 10 KAIC circuit breakers
Solardeck box or UL 1741 Approved
Equivalent to transition from Q-Cable to
THWN-2 Wire no fuse required
2
I Envoys
3
l��
CLIMATIC SOLAR
nn°waplamerpywlW°na
650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 772567-3104
FAX (772) 5674553
www.climalicsolar.com
It1 DESCRIPRDN I DAIS I REV I
Point of Interconnect, Supply Side
ul
EXISTING 240V/225A BUS BAR
W
Q
RATING, Main Service Panel, Single
z i
Phase, with a 200A Main Disconnect
V5
W
w
Z) LLLU
O LLI ZO
Z
U of _
(N) Lockable Blade Type M
LL
w a
Fusible AC Disconnect
L
00 a
NEMA 3R 60A-2P
120/240VAC
45 A FUSES 200A
(E) LOADS
Existing Grounding
Electrode System
120% RULE
BUS BAR RATING X 120%) - MAIN BREAKER RATING
= MAX. PV OCPD
(225A x 120%) - 200 = 70A
3-LINE
DIAGRAM
11" x 17"
SHEET NUMBER
E-01.1 : I C) "Ir
SIGNATUREWITH SEAL' dl�
2 � I
/��010
ELECTRICAL NOTES:
1. ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND
LABELED FOR ITS APPLICATION.
2. ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND
90 DEGREE C WET ENVIRONMENT.
3. WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS
SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE
AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
4. WORKING CLEARANCES AROUND ALL NEW AND EXISTING
ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
5. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF
SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY
OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO
FULFILL APPLICABLE CODES AND STANDARDS.
6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND
CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL
SIZE THEM ACCORDINGLY.
7. ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY
LABELED AND READILY VISIBLE.
B. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN
MODULE FRAME AND MODULE SUPPORT RAIL, PER THE
GROUNDING CLIP MANUFACTURER'S INSTRUCTION.
9. MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS
COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY -IN
LUG.
10. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL
PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE
SERVICE ENTRANCE.
11. WORKING CLEARANCES AROUND THE EXISTING AND NEW
ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH NEC ARTICLE 110.26.
12. ALL EQUIPMENT INSTALLED SHALL BE LISTED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL)
PER NEC ARTICLE 110.3.
13. RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
14. ALL LABELS OR MARKINGS SHALL BE VISIBLE AFTER
INSTALLATION. THE LABELS SHALL BE REFLECTIVE, AND ALL
LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM
HEIGHT OF 9.5 MM (3/8 IN) IN WHITE ON A RED BACKGROUND.
15. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS
SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND
ARTICLE 310.8 (D).
16. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE
SUITABLE FOR USE IN WET LOCATIONS PER NEC ARTICLE
310.8 (C).
SYSTEM NOTES:
1. ENPHASE IQ7 / 7PLUS MICROINVERTERS DO NOT REQUIRE
GROUNDING ELECTRODE CONDUCTORS OR EQUIPMENT
GROUNDING CONDUCTORS. THE MICROINVERTERS ITSELF HAS
CLASS II DOUBLE -INSULATED RATING, WHICH INCLUDES GROUND
FAULT PROTECTION.
2. ENPHASE Q CABLE HAS NO NEUTRAL WIRE -(2 WIRE DOUBLE
INSULATED CABLING)
3. MODULES ARE BONDED TO RAIL USING IRON RIDGE INTEGRATED
GROUNDING.
4. RAILS ARE BONDED WITH UL 2703 RATED LAY -IN LUGS
5. SYSTEM IS UNGROUNDED
6. BARE COPPER IS TRANSITIONED TO THHN/THWN-2 VIA
IRREVERSIBLE CRIMP; GEC TO BE CONTINUOUS PER CEC
250.64(C)
7. SUB -BRANCHES ARE CENTER -FED AT JBOX TO MAKE ONE TOTAL
BRANCH CIRCUIT.
8. ENPHASE IQ ENVOY INSIDE IQ COMBINER REQUIRES A NEUTRAL
TO BE LANDED AT THE NEUTRAL BUSS AT MAIN PANEL PER
ENPHASE INSTALLATION INSTRUCTIONS,
9. ENPHASE MICROINVERTERS ARE ALL RAPID SHUTDOWN READY
PER NEC 690.12
SYSTEM DATA
# STRINGS:
03
SMALLEST STRING:
11
LARGEST STRING:
12
TOTAL MODULES:
34
TOTAL INVERTERS:
34
SYSTEM RATINGS:
11.560kW DC STC
BATTERY RATING:
N/A
INVERTER SPECIFICATIONS
MANUFACTURER
ENPHASE ENERGY IQ7-60-2-US
MAX. DC VOLT RATING
48 VOLTS
MAX. POWER AT 40 C
240 WATTS
NOMINAL AC VOLTAGE
240 VOLTS
MAX. AC CURRENT
1.0 AMPS
MAX. OCPO RATING
20 AMPS
MAX. PANELS/CIRCUIT
16
SHORT CIRCUIT CURRENT
15 AMPS
PV MODULE RATING @ STC
MANUFACTURER HANWHAQ.PEAKDUO BLK-G6+34OW
MAX. POWER -POINT CURRENT (IMP)
10.02AMPS
MAX. POWER -POINT VOLTAGE (VMP)
33.94 VOLTS
OPEN -CIRCUIT VOLTAGE (VOC)
40.66VOLTS
SHORT-CIRCUIT CURRENT (ISC)
10.52AMPS
NOM. MAX. POWER AT STC (PMAX)
340 WATT
MAX. SYSTEM VOLTAGE
1000 VDC
VOC TEMPERATURE COEFFICIENT
-0.27' °/d°C
FSEC CIRTIFICATION
# 401259
LABLES
PHOTOVOLTAIC DC PER INVERTER
RATED MPP CURRENT
10.02 A
RATED MPP VOLTAGE
33.947V
MAX SYSTEM VOLTAGE
40.66 V
SHORT CIRCUIT CURRENT
10.52 V
PHOTOVOLTIAC AC OUTPUT
AC OUTPUT CURRENT
34.00A
NOMINAL AC VOLTAGE
240V
I JOHN ALGER, A PE #74730
PURSUANT TO CHAPTER 471
OF THE FLORIDA STATUTES,
HAVE EVALUATED THIS
SYSTEM AND IT'S INDIVIDUAL
COMPONENTS AND CERTIFY
THAT IT MEETS OR EXCEEDS
THE MINIMUM STANDARDS IN
2017 FLORIDA BUILDING CODE
6TH EDITION 2017 FLORIDA
BUILDING CODE 6TH EDITION
RESIDENTIAL 2014 NEC
CERTIFICATE OF
AUTHORIZATION#
31930
ENGINEER OF RECORD
JOHN L. ALGER
PROFESSIONAL ENGINEER
FL. LICENSE NO.74730
kilill*
CLIMATIC SOLAR
mn ble CMYWU1
650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 772-567-3104
FAX. (772) 5674553
www.climaUcsolar.com
REVISIONS
DEB Fnm
DATE
REV
PROJECT NAME
W
W Q rn
o a�i
ai Z J .�.
W � LL. W
0 0
W
LL 0
m
C7
SHEETNAME
ELECTRICAL
NOTES
SHEET SIZE
ANSI B
11" x 17"
SHEETNUMBER
E-02
, ,
SIGNATURE WITH SEAL ,'i _
C,
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): CEC 2019: 690.17(B),
NEC 2014: 690.17(E), NEC 2011: 690.17(4)
DUAL POWER SUPPLY
SOURCES: UTILITY GRID
AND PV SOLAR ELECTRIC
SYSTEM
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN SERVICE
PANEL.
PER CODE(S): NEC 2014:705.12(D)(3),
NEC 2011:705.12(D)(4)
PHOTOVOLTAIC SYSTEM
COMBINER PANEL
I DO NOT ADD LOADS I
LABEL LOCATION:
PHOTOVOLTAIC AC COMBINER (IF APPLICABLE).
PER CODE(S): CEC 2016:705.12(D)(2)(3)(c), NEC
2014:705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION:
ADJACENT TO PV BREAKER (IF APPLICABLE).
PER CODE(S): CEC 2019:705.12(B),
NEC 2014: 705.12(1))(2)(3)(b), NEC 2011: 705.12(D)(7)
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, AT EACH
TURN, ABOVE AND BELOW PENETRATIONS, ON EVERY JBIPULL
BOX CONTAINING DC CIRCUITS.
PER CODE(S): CEC 2019: 690A3, NEC 2014: 690.31(G)(3),
690.31(G)(4), NEC 2011: 690.31(E)(3), 690.31(E)(4), IFC 2012:
605.11.1.4
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER COOE(S): CEC 2019: 690.53, NEC 2014: 690.54, NEC 2011: 690.54
NOTES AND SPECIFICATIONS:
• SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2014
ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED
BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
• SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING
EFFECTIVE WORDS, COLORS AND SYMBOLS.
.LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE HAND WRITTEN.
.LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
• SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT
SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
• DO NOT COVER EXISTING MANUFACTURER LABELS.
CLIMATIC SOLAR
m,.,.uw•�nvrwmuo,n
650 2nd LANE
VERO BEACH, FL 32962, USA
PHONE: 772-5673104
FAX: (772) 567-4553
www.dimafesolar.com
I DESDWPTION I DATE I � IN
W
U
Z
w
0
as
W
w
QLo
rn
ch
Q
Z J
LL. LLI
Cr LLO
rya
�w
ca
co
co
LABELS
SHEET SIZE
ANSI B
11" x 17"
SHEET NUMBER
:SIGNATURE WITH SEAL '
powered by
lq�WDUO
THE IDEAL SOLUTION FOR:
LtresideRooftop al buldiays n
residential bulMinBs
Engineered in Germany
I
p(ELLS '
I
MP BRRND PV-
O`ua11��Teeta4
4
.:.. �" \.2019
,G y.
ID.40032 587
^ Q.ANTUM TECHNOLOGY: LOW LEVELIZED COST OF ELECTRICITY
Higher yield per surface area, lower BOS costs, higher
power classes, and an efficiency rate of up to 19.5%.
INNOVATIVE ALL-WEATHER TECHNOLOGY
Optimal yields, whatever the weather with
excellent low-Ilght and temperature behavior.
7- ENDURING HIGH PERFORMANCE
O ` Long-term yield security with Anti LID and Anti PID Technology',
Hot -Spot Protect and Traceable Quality Tra.QThe.
EXTREME WEATHER RATING
High-tech aluminum alloy frame, certified for high snow
(5400 Pa) and wind loads (4000 Pa).
p A RELIABLE INVESTMENT
Inclusive 25-year product warranty and 25-year
linear performance warranty'.
Q� STATE OF THE ART MODULE TECHNOLOGY
or '� Q.ANTUM DUO combines cutting edge cell separation
and innovative wiring with Q.ANTUM Technology.
1 APT test conditions according to IEC/TS 62804-1:2015, method B (-1500V. 168N
2 See data sheet on rear for further information
MECHANICAL SPECIFICATION
Format 68.5 x 40.6 x L26 in (Including frame)
(1740 x 1030 x 32mm) .. zu`iuu x
Weight 43.91bs(19.91g)
Front Cover 0.13in(3.2mm) thermally pre -stressed glass + - +
with anti -reflection technology „awaew.ealrrl.ar
Back Cover Composite film _ aerPumm3
Frame
Black anodized aluminum
Cell
6. 20 menocrystelline Q.ANTUM solar half cells
Junction8ox
2.09-3.98x1.26-2.36 x 0.59-0,71 In (53-101 x 32-60 x
15-18mm), Protection class IP67, with bypass diodes
Cable
4mm2 Solar cable; (+) e45.31n (1160 mm), 1-) 1,45.3In(1150mm)
Connector
Staubil MC4, Hanwha Q CELLS HQC4, Amphenol UTX,
Renhe 05-6, Tangling TL-CableOlS, JMTHY JM601; IP68 or
Friends PV2e; IP67
O
I'0° L .avmmmro
e.s
ELECTRICAL CHARACTERISTICS
j POWER CLASS
330
335
340
345
MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC' (POWER TOLERANCE+5 W /-0 W)
Powaret MPP1
Fur,
IWI
330
335
340
345
Short Circuit Current3
Isc
IA]
10.41
10.47
10.52
10.58
Open Circuit Voltage*
E
Vac
IV]
40.15
40.41
40.66
40.92
Cumentat MPP
I,
(A]
9.91
9.97
10.02
10.07
Voltage at MPP
VaRa
IV]
33.29
33.82
33.94
34.25
Efficiency`
a _
[%]
a18.4
a18.7
1,19.0
a19.3
MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NMOT2
Power at MPP Pew [W) 247.0 250.7 254.5 258.2
E Short Circuit Current 1¢ [A] 8.39 8.43 8.48 8.52
Open Circuit Voltage Vac IV] 37.86 38.10 38.34 38.59
Currentat MPP I, IAI 780 784 789 Z93
Voltegeat MPP V°°a IV] 31.66 31.97 32.27 32.57
'Meesurememtolerances Pw. s3%: lu: Vae s6%at STC: 1000 W/m; 25x2°C, AM 1_5 according to IEC 60904-3 •'800 W/m2, NMOT, spectrum AM Lb
Q CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE j
IS
b. ...
°3 a --'------"'-"._.---------
Eg
-------------
a
F
°u ^
Po YELRe
At least 98%of nominal power during
first year. Thereafter max. 0.54%
degradation per year. At least93.1%
of nominal power up to 10 years. Al
least 85%of nominal power up to
25years.
All data within measurement toleranc.
as. Full warranties in accordance with
the warranty terms of the O CELLS
sales organization of your respective
country.
8°O ----- r---------- n_____-
?
I
a
en zw Rae . Roa 3aoR
OO IRR1pLWCarW/mr/
Typical module performance under low trmdlence conditions In
comparison to STC conditions (25°C, 1000 W/m2)
Temperature Coefficient of l.c a [%/Kl +0.04 Temperature Coefficient of Vw B (%/Kl -0.27
Temperature Coefficient of Puw y (%/K] -0.36 Normal Module Operating Temperature NMOT IT] 109t5.4(43x3°C)
PROPERTIES FOR SYSTEM DESIGN
Maximum System Voltage Veee M 1000(IEC)/1000(UL) Safety Class II
Maximum Series Fuse Rating [ADC] 20 Fire Rating based on ANSI/UL 1703 C(IEC)/TYPE2(UL)
Max. Design Load, Push/Pull' )Ibs/ftq 75(3600Pa)/55(2667Pa) Permitted Module Temperature -40°F up to+185°F
Me.. Test Load, Push/Pull' [Ibs/ftq 113(5400Pa)/84(4000Pa) °^Continuous Duty (-40°C up to+85°C)
3See Installation Manuel
QUALIFICATIONS AND CERTIFICATES PACKAGING INFORMATION
UL1703, VDE Quality Tested. CE-compliant, IEC 61215:2016, IEC 61730:2016.
Application Class II, U.S. Patent No. 9.893,215 (solercells)
DVE C E Acgus
Number of Module. per Pallet
KY
Number of Pallets per 53' Trailer
28
Number of Pellets per 40' HC-Contalner
24
Pallet Dimensions (LxWx H)
71.5 x 45.3 x 48.0in(1815 x 1150 x 1220mm)
Pallet Weight
15051bs(683 kg)
Note: Installation insWctions must be followed. See the installation and operating manual or contact our technical service department for further Information on approved Installation and use
of this product.
Q CELLS 400 Spectrum
LLS Center Drive,
lne.
400ah.0C Center erica In.. 1400,Irvine, CA 92618, USA I TEL+19497485996 IEMAIL inquiry@us.q-cells.comI WEB www.q-cells.us
Data Sheet
Enphase Microinverters
Region: AMERICAS
Enphase
IQ 7 and IQ 7+
Microinverters
N
To learn more about Enphase offerings, visit enphase.com
The high-powered smart grid -ready
Enphase IQ 7 Micro' and Enphase IQ 7+ Micro'
dramatically simplify the installation process while
achieving the highest system efficiency.
Part of the Enphase IQ System, the IQ 7 and
IQ 7+ Microinverters integrate with the Enphase
IQ Envoy'", Enphase IQ Battery'", and the Enphase
EnlightenTM monitoring and analysis software.
IQ Series Microinverters extend the reliability
standards set forth by previous generations and
undergo over a million hours of power -on testing,
enabling Enphase to provide an industry -leading
warranty of up to 25 years.
Easy to Install
Lightweight and simple
Faster installation with improved, lighter two -wire cabling
Built-in rapid shutdown compliant (NEC 2014 & 2017)
Productive and Reliable
Optimized for high powered 60-cell and 72-cell* modules
More than a million hours of testing
Class II double -insulated enclosure
UL listed
Smart Grid Ready
• Complies with advanced grid support, voltage and
frequency ride -through requirements
• Remotely updates to respond to changing
grid requirements
• Configurable forvarying grid profiles
• Meets CA Rule 21 (UL 1741-SA)
• The IQ 7+ Micro is required to support 72-cell modules.
Enphase IQ 7 and IQ 7+ Microinverters
Commonly used module pairings'
235 W - 350 W +
235 W -440 W + I
Module compatibility
-_ 60-cell PV modules only - - _
_ 60-cell and 72-cell PV modules
-
MaxiuI mm nput DC voltage - _
, 48 V
60 V
Peak power tracking voltage
27 V -37 V
- -27 V; 45 V
r Operating range
16V-48V
16V-60V
Min/Max start voltage
22 V / 48 V
22 V / 60 V
'Max DC short circuit current (module lsc)
15.A -_--__15A
Overvoltage class DC port--
�
DCporttiackfeedcurrent
PV array configuration
- 1 x 1 ungrounded array; No additional DC side protection required;
AC side protection requires max 20A per branch circuit
OUTPUT DATA (AC)
IQ 7 Microinverter
IQ 7+ Microinverter
Maximum continuous output power
240 VA
290 VA
----- - —,
-------- — ---- —
I Nominal (L-L) voltage/range- '—
240 V // -
206 V % -W
- 240 V %
208 V %
211-264V
V_
183-229V -----_-----__._--
Maximum continuous output current
1.0 A (240 V)
_183-229V__
1.15 A (208 V)
T211-264
1.21 A (240 V)
1.39 A (208 V)
L,Nominal frequency
Extended frequency range
47-68 Hz
47-68 Hz
-i- --_
Cd hort circuftfaultcurrent ovei35ycles -
5.8Arms
,2
Maximum units per 20 A (L-L) branch circuit'
16 (240 VAC)
13 (208 VAC)
13 (240 VAC)
11 (206 VAC)
•Overvoltageclass ACportIII----_�__
--III--—.-_.-__.___-__--.---.
AC port backfeed current-
) -Power factor setting
LO
_ ________
Power factor (adjustable)
—v_-_._.,
0.851eading...
0.85 lagging
0.85 leading...
0.85 lagging
pppiriprary
fa 240 V
0208 V
0240 V
(d208 V
CEC weighted efficiency
97.0 % 97.0 % 97.0 % 97.0 %
MECHANICAL DATA
Ambient temperature range. _ _ _ _ -
_
_ 40°C to+65°C _ _ _ _
Relative humidity range
4%to 100%(condensing)
i____ _ct_-
I Connectortype _
—_-1
_ _. __. -- - - to _ ___ _
MC4 (or Amphenol H4 UTXwith additional Q DCGSadapter)'-
_ _ _—
--_—____ --_
Dimensions (HxWxD)
212 mm x 175 mm x 30.2 mm (without bracket)
Weight
1.08 kg (2.3816s)
Cooling
Natural convection - No fans
I Approved for wet locations
Pollution degree
PD3
.__._-.._
Enclosure
_-_- __-.. ___. .____.-____ __. _.__.
Class II double -insulated, corrosion resistant polymeric enclosure
-- - -_--
_
-Environmental category/ UV exposure rating
NEMA Type 6/outdoor
Communication
Power Line Communication (PLO) I
Monitoring
__.___.
Enlighten Manager and MyEnlighten monitoring options.
Both options require installation of an Enphase IQ Envoy.
rDisconnecting means
The ACand DCconnectorshavebeen evaluatedand approved by UL for use as the load: ea I
f
required by NEC 690.
- -- - -- -
Compliance
^` ,disconnect
-- - ---- - ----- -- -
CA Rule 21 (UL 1741-SA)
UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B,
CAN/CSA-C22.2 NO. 107.1-01
This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and
NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC
and DC conductors, when installed according manufacturer's instructions.
1. No enforced DC/AC ratio. Seethe compatibility calculator at https'//ennhas om/n-uW,noort/module-comnatlbllity.
2. Nominal voltage range can be extended beyond nominal if required by the utility.
3. Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
vEN PHAS E. To learn more about Enphase offerings, visit enphase.com -0:1 EN PHASE.
02020 Enphase Energy. All rights reserved. Enphase, the Enphase logo, Enphase IQ 7, Enphase IQ 7+, Enphase IQ Battery,
Enphase Enlighten, Enphase IQ Envoy, and other trademarks or service names are the trademarks of Enphase Energy, Inc. Data subject to change. 2020-01-06
Data Sheet
Enphase Networking
Enphase
IQ Combiner 3
(X-IQ-AM1-240-3)
U�
LISTED
To learn more about Enphase offerings, visit enphase.com
The Enphase IQ Combiner 3' with Enphase
IQ Envoy'' consolidates interconnection
equipment into a single enclosure and
streamlines PV and storage installations by
providing a consistent, pre -wired solution for
residential applications. It offers up to four
2-pole input circuits and Eaton BR series
busbar assembly.
Smart
• Includes IQ Envoy for communication
and control
• Flexible networking supports Wi-Fi,
Ethernet, or cellular
Optional AC receptacle available for PLC
bridge
Provides production metering and optional
consumption monitoring
Simple
• Reduced size from previous combiner
• Centered mounting brackets support single
stud mounting
• Supports back and side conduit entry
Up to four 2-pole branch circuits for 240 VAC
plug-in breakers (not included)
80 A total PV or storage branch circuits
Reliable
• Durable NRTL-certified NEMA type
3R enclosure
• Five-year limited warranty
• UL listed
IQ Combiner 3
rear data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60
far data plan) microinverters. (Available in the US, Canada,Mexico, Puerto Rico, and the US Virgin Islands,
d LTE-M/5-year data plan) _where there is adequate cellular service in the installation area.)_
CT Split core current transformers enable whole home consumption metering (+/- 2.5 0).
• Consumption monitoring Is required for Enphase Storage Systems _ _
rWireless USB adapter _ - -' � Installed at the Iq E'nvoy. Forcolnmsnicatiolis witft Enphase Encharge"' strrage asd Enphase j
ICOMMS-KIT-01
Enpower' smart switch. Includes USB cable for connection to IQ Envoy or Enphase IQ Combiner' I
and allows redundant wireless communication with Encharge and Enpower�
_
circuit Breakers
Supports Eaton BR210, BR215, BR220, BR230, BR240, BR250, and BR260 circuit breakers.
BRK-10A-2-240
Circuit breaker, 2 pole, 10A, Eaton BR210
BRK-15A-2-240
Circuit breaker, 2 pole, 15A, Eaton BR215
BRK-20A-2P-240
Circuit breaker, 2 pole, 20A, Eaton BR220
Power lrnecamer(communicatlontindge pair),, quant I7FInepair -
J
XA-PLUG-120-3�
Accessory receptacle for Power Line Carrier in IQ Combiner 3 (required for EPLC-01)
System voltage~' -_—�-_ 120/240 VAC, 60 Hz-
ff Eaton BR series busbar rating 125
Max. continuous current rating (output to grid) 65 A
rrM''ax.fuse%circuit rabng(output) 90A T r
Branch circuits(solar and/or storage) w Upto four 2-pole Eaton BR series Distributed Generation(DG) breakers only (not included)
Max. continuous current rating
Max. total branch circuit breaker rating (input) 80A of distributed generation / 90A with IQ Envoy breaker included
_— _.. _..m --- --- —_-._-._ ._-_.__..______.._____ __-__ ._._ --- __
(PfOdUCl100 Metering CT 200 A solid core pre -installed and wired to IQ Envoy i
ht-...__._____
ent ternperature ran
ng
(sure environrrental-
sizes
cm
--Natural convection, plus heat shield
20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors
60 A breaker branch input: 4 to 1/0 AWG copper conductors
Main lug combined output: 10 to 2/0 AWG copper conductors
Neutral and ground: 14 to 1/0 copper conductors
ways follow local code requirements for conductor sizing.
!Integrated WI-Fi 802.11b/g/n
__--__--
Ethernet Optional, 802.3, CatSE (or Cat 6) UTP Ethernet cable (not Included)
'Cellular Optional, CELLMobEM-01.(3G)or CELLMODEM-03(4G)or CELCMODEM-M1 (4G based LTE-M) -1
f—f lnrh,dndl i
compnance, rAmomer " "", ..«. ., ,�,.,. �, , o„ ---
i Production metering: ANSI C12.20 accuracy class 0.5(PV prgduction)____�_____,_;�______
Compliance, IQ Envoy �,. UL 60601-1/CANCSA 22.2No. 61010-1-1
To learn more about Enphase offerings, visit enphase.com
0 2018 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ Combiner 3, and other trademarks or service names are the
ENPHASE. trademarks of Enphase Energy, Inc.
2019-11-04
0M ENPHASE.
AM& IRON RIDGE
Solar Is Not Always Sunny
Over their lifetime, solar panels experience countless
extreme weather events. Not just the worst storms in years,
but the worst storms in 40 years. High winds capable of
ripping panels from a roof, and snowfalls weighing
enough to buckle a panel frame. A
XR Rails are the structural backbone preventing
these results. They resist uplift, protect
against buckling and safely and efficiently
transfer loads into the building structure. l
Their superior spanning capability
requires fewer roof attachments,_
reducing the number of roof 1 ,
penetrations and the amount
of installation time.
i
Force -Stabilizing Curve
Sloped roofs generate both vedical and lateral
forces on mounting rails which can cause them
to bend and twist. The curved shape of XR Rails
Is specially designed to Increase strength in both
directions while resisting the twisting. This unique
feature ensures greater security during extreme
weather and a longer system lifetime.
Compatible with Flat & Pitched Roofs
XR Rails are konRidge offers
compatible with a range of tilt leg
FlashFoot and options for flat
other pitched roof roof mounting
attachments. applications.
XR Rail Family
Corrosion -Resistant Materials
All XR Rails are made of marine -grade _ o,
aluminum alloy, then protected with an
anodized finish. Anodizing prevents surface a'
and structural corrosion, while also providing
a more attractive appearance. �®
XR Rail Family
The XR Rail Family offers the strength of a curved rail in three targeted sizes. Each size supports specific
design loads, while minimizing material costs. Depending on your location, there is an XR Rail to match.
XR10
XR10 is a sleek, low -profile mounting
rail, designed for regions with light or
no snow. It achieves 6 foot spans, while
remaining light and economical.
6'spanning capability
Moderate load capability
Clear anodized finish
Internal splices available
Rail Selection
Ir
XR100
XR100 is the ultimate residential
mounting rail. It supports a range of
wind and snow conditions, while also
maximizing spans up to 8 feet.
• 8' spanning capability
• Heavy load capability
• Clear & black anodized finish
• Internal splices available
XR1000
XR1000 is a heavyweight among
solar mounting rails. It's built to handle
extreme climates and spans 12 feet or
more for commercial applications.
• 12'spanning capability
• Extreme load capability
• Clear anodized finish
• Internal splices available
The following table was prepared in compliance with applicable engineering codes and standards. Values are
based on the following criteria: ASCE 7-10, Roof Zone 1, Exposure B, Roof Slope of 7 to 27 degrees and Mean
Building Height of 30 ft. Visit IronRidge.com for detailed span tables and certifications.
L-Mount I QMLM / QMLM-ST
Elevated Water Seal Technology®
ITEM
NO.
DESCRIPTION CITY.
THIS EDGE TOWARDS ROOF RIDGE
FLASHING, ROUNDED CORNERS, 9" X 12" X .040", .438" HOLE, 5052. 1
I
MILL
2
L-FOOT, 7' X 3.30" FOR .438" O.D. FASTENER, 2-1 /16" SLOT, 6061- 1
T6 6005A-T61, MILL
3
WASHER, SEALING, 5/16" ID X 3/4" OD, EPDM BONDED SS 1
4
LAG SCREW, HEX HEAD, 5/16" x 4', 18-8 SS 1
30 HEX WASHER HEAD, 5/16" X 4-1/2',
P5 STRUCTURAL SCREW, QMPV, T18-BSS 1
12.00
�5
(4.20)RAL
3.00
E ON
ST
�-- 4.50
ONLY
YINISHES
9.00 —
2.00
0.408 1.00
O
N MILL,
3.3� .90
FINISHES
to
Quickly{- PV°
40
TITLE:(25
(354)
4.04
275
QMLM 8 QMLM-SMOUNT, 2
1 /16"SLOT
QMLM
QMLM-ST
UNL OMERWBESPKnED: SIZE DRAWNBY: AAP REV
DIMFntI0NSA9EW WCHES
rote+AucEs: „ DATE 4/d/2019
9¢puOvw.M"""1l ugowl,tC4wvpg6m[SpevRs9nc(cN6eww'Iw. unPwCCVCIW w9M0ewSwwM ewmIW,11rt
wnmr"Pv m9oxaavc""ouwws�aarzP. C0PYRIGR02019GUICKM0UMPV
IRAC11011P1: 1/8
00 N01SC/.1E M.�WMG N`'OPIA EDEIMN. !.I9
iHRai PIACEDKlwt a09R SCNE 1:1 waGM:0.9565 SHEETI OFI
5 4
3 2 1
BI 7.2.3-44
(wick Mount PV°
RESPECT THE ROOF
Apr-2019 Rev 6
L-Mount Installation Instructions
Installation Tools Required: tape measure, roofing bar, chalk line, stud finder, caulking gun, sealant compatible with roofing
materials, drill with 7/32" or 1/8" bit, drill or impact gun with 1/2" socket.
Locate, choose, and mark centers of rafters to be Carefully lift composition roof shingle with rooting insert hashing Derween rsc anG am comae. ague
mounted. Select the courses of shingles where bar, just above placement of mount. Remove up so top edge of flashing is at least YV higher
mounts will be placed. nails as required and backfill holes with aproved than the butt -edge of the 3rd course and lower
sealant. See "Proper Flashing Placement" on next flashing edge is above the butt -edge of lst course.
page. Mark center for drilling.
If attaching with lag bolt use a *ha" bit (Lag). Use a
'/e" bit (ST) for attaching with the structural screw.
Drill pilot hole into roof and rafter, taking care to
drill square to the roof. Do not use mount as a drill
guide. Drill a 2" deep hole into rafter.
Prepare lag bolt or structural screw with sealing
washer. Using a 1k-inch socket on an impact gun,
drive prepared lag bolt through L-foot until L-foot
can no longer easily rotate. DO NOT over -torque.
NOTE: Structural screw can be driven with T-30 hex
head bit.
BI 7.2.3-44
Clean off anysawdust, and Fit hole with sealant Place L-foot onto elevated flute and rotate L-foot to
compatible with roofing materials. desired orientation.
You are now ready for the rack of your choice.
Follow all the directions of the rack manufacturer
as well as the module manufacturer. NOTE: Make
sure top of L-Foot makes solid contact with racking.
Apr-2019 Rev 6
Reference and Tips
flashing positioned tab low:
Nails not removed.
Keyway allows water'entry: -Remove nails..
�
3rdcour3e
Moisture/debris
�� 2nd course
accumulation can ® ��
cause early shingle
degradation: e tst course.
NOMM
INCORRECT Position Correct Position Acceptable Position
No, shingle cutting required If shinglecutting is required, a %!'
gap between blockand shingle is
recommended.
Additional tips and information for installing mounts:
Is See Quick Tips videos on nail removal, and more at:
http://www.quickmountpv.com/support/videos.htmt
■ It is not necessary or advisable to use nails or other fasteners to secure the perimeter of
the flashing.
■ The L-Mount is made to work with standard and high -definition composition/asphalt and wood shingle
roofs with 5" to 5-5/8" courses. If the exposed surface of the course exceeds this measurement you may
need to use our Classic Shake Mount instead.
■ Depending on the season and climate, size and location of seal tabs, and quality of the shingles, the
seal tabs that adhere the shingle courses together may not effectively seal the shingles to the flashings.
If this is the case, simply add several quarter -sized dabs of manufacturer accepted sealant or asphalt
roofing cement, meeting ASTM D 4586 Type II, between the flashing and the shingle above.
■ Mounts should not be installed in areas of the roof susceptible to ice damming. Water ponding under
the shingles can reach the bolt penetration.
Is Take care not to damage the roofing material while working on the roof. Removing stone granules and
deforming the shingles in any way can shorten the lifespan of the roofing. The value of the solar array is
directly affected by the condition of the roof it is attached to.
■ CAUTION: Prior to installation, check that proper screw embedment will be achieved for the necessary site
load and roofing configurations.
Apr-2019 Rev 6
Quick Mount P1 /®
RESPECT THE ROOF
925-478-8269 1 www.quickmountpv.com I info@quickmountpv.com
2700 Mitchell Dr. I Walnut Creek, CA 94598
BI 7.2.3-44
0 2019 by Quick Mount PV. All rights reserved.