HomeMy WebLinkAboutLetter from David Cleveland, response to comments■■ Cleveland Design Group,lnc.
772-464-2010 vidandl2Qyahoo.com 100 Avenue A, Suite 2E Fort Pierce Florida 34950
AUGUST 17, 2020
TO: WILLIAM DURDEN
RE: PERMIT# 2007-0648
PLAN REVIEW COMMENTS DATED 8/3/2020
MR. DURDEN,
THE FOLLOWING ARE RESPONSES TO YOU COMMENTS.
1- 5 WE WILL APPLY FOR SEPARATE PERMITS.
6. UNDERSTOOD
7. THE DESIGN CRITERIA IS ON SHEET 3 OF 4.
8. THE SHED THAT IS ATTACHED TO THE WEST END OF THE EXISTING
GARAGE IS CONSTRUCTED AS SHOWN ON THE DRAWINGS.
THE BLOCK WALL DOES NOT EXIST ANY LONGER.
THE FOUNDATION TYPE IS IN COMPLIANCE WITH R403.1.
9. THE CLADDING DETAIL IS ON SHEET 2 OF 4.
SECTION 107 OF THE FBC RESIDENTIAL IS RESERVED.
10. NON -HABITABLE SPACE
1 1. NON -HABITABLE SPACE
12. NON -HABITABLE SPACE
13. NON -HABITABLE SPACE
14. TO MY UNDERSTANDING THIS WAS AN ORIGINAL OPENING IN
THE EXISTING BLOCK WALL.
15. THIS IS A 2' WIDE PRESSURE TREATED WALKWAY ON GRADE.
16. NON -HABITABLE SPACE
17. IN ACCORD WITH R301.1.3 THIS IS AN ENGINEERED
CERTIFIED ALTERNATE DESIGN.
18. SECTION 107 OF THE FBC RESIDENTIAL IS RESERVED, THE
SCREW ANCHORS HAVE BY CERTIFIED BY THE STRUCTURAL
ENGINEER.
19. UNDERSTOOD
20. MOST ALL OF THE COST HAS BEEN INCURRED, THE LABOR IS
BEING SUPPLIED BY THE OWNER BUILDER.
ZONING REVIEW
21. UNDERSTOOD
22. THE HEALTH DEPARTMENT IS CURRENTLY REVIEWING THE PLAN REVIEW
APPLICATION.
23. THE SURVEY IS BEING AMENDED TO REFLECT THE PARCEL COMBINATION. THE
ELEVATIONS ARE NOT NEEDED BECAUSE THE SPACE IN QUESTION IS NON- HABITABLE
AREA.
WHEN THE COUNTY IS CALLED FOR INSPECTIONS 1 WILL MAKE MYSELF AVAILABLE TO
MEET THE INSPECTOR ON SITE, AND WE CAN ADDRESS ANY UNFORESEEN ISSUES IN
THE FIELD.
REGARDS
DAVID M. CLEVE ND
,Ie-7/H~ 4��o� i--.. .' - - -
Ptsrwift 3 Development services
8a k*V & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. U982
REVIEW COMMENTS
Comment: PHOTOS DATED 02/18/2010 SHOW SMALL ROOF STRUCTURE OVER A SLAB ON (3HADL WI I H UMU WALL
BEING CONSTRUCTED, AND PHOTOS DATED 08/06/2019 SHOWS AN ELEVATED FLOOR. PER THE PHOTOS
DATED 08/03/2020 THE STRUCTURE APPEARS TO BE CONSTRUCTED ON A WOOD SUB FLOOR SYSTEM;
S 8/3/2020
THE PLANS SHOW THE STRUCTURE ON A 4 INCH CONCRETE SLAB ANCHORED WITH A 48 INCH X 6 INCH
EARTH ANCHOR. PLEASE SHOW OR CLARIFY THE FOUNDATION SYSTEM USED. SEE SECTION 107 OF THE
2017 FLORIDA BUILDING CODE.
Comment: NO PRODUCT APPROVAL SUBMITTED FOR THE COMPONENTS AND CLADDING FOR THE ADDITION. SEE
9 8/3/2020
SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
Comment: NO SHOP DRAWINGS SUBMITTED FOR THE SECURITY BARS COMPLYING WITH EMERGENCY ESCAPE
10 8/3/2020
AND RESCUE. SEE R310 OF THE RESIDENTIAL BUILDING CODE.
Comment: • PLEASE FURNISH ENERGY CALULATIONS AND MANUAL J IN ACCORDANCE WITH SECTIONS 402 AND 403
t( 8/4/2020
OF THE 2017 FLORIDA ENERGY CODE. NOTE ONLY; ENERGIES MUST HAVE ORIGINAL SIGNATURE OF
PREPARER
Comment: • PLEASE FURNISH A DUCT PLAN SHOWING A BALANCED SYSTEM, DUCT SIZE, GRILL SIZE, AND ROOM BY
12 8/4/2020
ROOM CFMS PER 107.2.1 OF THE 2017 FLORIDA BUILDING CODE
Comment: • PLEASE FURNISH A INTERIOR WALL DETAIL SHOWING STUD SPACING, STUD SIZE, AND WALL FINISH IN
( 8/4/2020
.3
ACCORDANCE WITH 602.2 OF THE 2017 FLORIDA BUILDING CODE
Comment: NO DETAIL ON THE PLANS FOR THE ALTERATION OF THE ORIGINAL EXTERIOR WALL FOR OPENING. SEE
1-4 8/4/2020
SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
15
Comment: NO DETAIL ON THE PLANS FOR THE WOOD DECK AROUND THE ADDITION. SEE SECTION 107 OF THE 2017
8/4/2020
FLORIDA BUILDING CODE.
1110
Comment: NO DETAILS ON THE PLANS FOR THE CONVERSION OF THE GARAGE TO HABITABLE SPACE. SEE
8/4/2020
SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
Comment: NO FOOTING DETAILS ON THE PLANS MEETING THE MINIMUM SIZE, RESISTANCE TO UPLIFT,
rt 8/4/2020
FOUNDATION ANCHORAGE REQUIREMENTS OF CHAPTER 4, SECTION 403 OF THE 2017 FLORIDA
BUILDING CODE.
Comment: PLEASE SHOW THAT THE CALCULATIONS FOR THE SCREW TYPE ANCHORING OF THE ADDITION. SEE
($ 8/4/2020
SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
(4
Comment: UNABLE TO COMPLETE MY REVIEW OF THE ADDITION/RENOVATION DUE TO LACK OF INFORMATION ON
8/4/2020
THE PLANS. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
Comment: • COST OF CONSTRUCTION SEEMS LOW PLEASE SUBMIT A DETAILED ESTIMATE FOR THE COST OF
CONSTRUCTION. PERMIT VALUATIONS SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS
20 8/4/2020
AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED. AS PER SECTION 109.3 OF THE 2017 FLORIDA
BUILDING CODE SIXTH EDITION.
ZONING REVIEW
INCOMPLETE Lydia Galbraith 8W020
21 Comment: EACH INDIVIDUAL BUILDING AND THE ADDITION/GARAGE ENCLOSURE REQUIRES A SEPARATE PERMIT
APPLICATION. THE CURRENT APPLICATION WILL BE USED FOR THE HOUSE ADDITION/GARAGE
ENCLOSURE.
PLEASE INDICATE AT EACH APPLICATION THE SIZE OF THE BUILDING TO BE CLEAR WHICH APPLICATION
8/3/2020 BELONGS TO WHICH STRUCTURE..
GAZEBO + DIMENSION
1 STORY WOOD FRAME BUILDING + DIMENSIONS
SHED 13.8'X10.2'
SHED 11.7'X12.3' THIS SHED WILL NEED TO BE RELOCATED TO MEET 5' REAR SETBACK.,
DEMOLITION PERMIT FOR ALUMINUM SHED TO BE REMOVED.
2 Z Comment: ACCORDING TO THE APPLICATION THE PROPERTY IS ON SEPTIC.
8/3/2020 PLEASE PROVIDE A LETTER OF APPROVAL FROM THE HEALTH DEP. FOR THE PROPOSED ADDITION
(ENCLOSURE OF GARAGE TO EXERCISE ROOM AND THE ADDITION OF THE CRAFTSROOM. AND A COPY
OF THE SURVEY WITH APPROVAL STAMP FROM HEALTH DEP.
2 5 Comment: THE SURVEY IS INCOMPLETE OR HAS CONFLICTING INFORMATION. PLEASE UPDATE WITH FOLLOWING
INFORMATION:
INDICATE PROPERTY AS ONE LOT.
- INDICATE THE FLOOR ELEVATION OF THE HOUSE, THE GARAGE AND THE CRAFT ROOM. WE WILL NEED
8/3/2020 TO KNOW FROM EACH AREA WHAT THE FLOOR ELEVATION IS.
ELEVATION OF THE CENTER LINE OF THE ADJACENT ROAD.
INDICATE THE RELOCATED SHED AND GAZEBO AT THE PROPOSED LOCATION.
DIMENSIONS AND SETBACKS FROM ALL PROPOSED BUILDINGS.
THE SHED 117'X12.3' WILL NEED TO BE RELOCATED TO MEET V REAR SETBACK.
Planning & Deveiopment Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce. FL. 34982
PROPERTY INFORMATION
Address: 3307 Avenue J
City / State / Zip: Fort Pierce, FI 34947
Parcel #: 2405-701-0103-000/3
Zoning: RS-4
APPLICATION INFORMATION
Permit Number: 2007-0648
Permit Type: BUILD RESID ADDITION
CONTRACTOR INFORMATION
Contractor Name:
Business Name:
Business Addr:
City / State / Zip:
REVIEWS AND COMMENTS
Review Type Status
DOCUMENTS MISSING PENDING
Comment:
ENVIRONMENTAL REVIEW
Comment:
FRONT COUNTER REVIEW
Comment:
NOTIFIED FOR PICK UP
Comment:
PLANS EXAMINER
REVIEW
1
8/3/2020
Comment:
2
8/3/2020
Comment:
3
8/3/2020
Comment:
8/3/2020
Comment:
8/3/2020
Comment:
(0
8/3/2020
Comment:
8/3/2020
Comment:
PENDING
COMPLETE
PENDING
REVIEW COMMENTS
Page 1
Owner(s):
Deseriee Wiley / Robert J Wiley
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 4 Block: 43
Stories: Automatic Sprinkler System? No
Fax Number:
Reviewed By Date Started
Ellen Vaughn 7/30/2020
Email:
Date Completed Date Released
7/30/2020 7/30/2020
INCOMPLETE William Durden 8/3/2020
A SEPARATE PERMIT IS REQUIRED FOR THE RELOCATION OF THE GAZEBO.
A SEPARATE PERMIT IS REQUIRED FOR THE RELOCATION OF THE 13.30 X 24.27 SHED.
A DEMO PERMIT IS REQUIRED FOR THE DEMOLITION OF THE SHED ON LOT 6.
A SEPARATE PERMIT IS REQUIRED FOR THE 10.2 X 13.8 SHED WITH WOOD DECK.
A SEPARATE PERMIT IS REQUIRED FOR THE 11.7 X 12.3 SHED WITH WOOD DECK.
UNABLE TO COMPLETE MY REVIEW ON THE ITEMS LISTED ABOVE. ADDITIONAL INFORMATION MAY BE
REQUIRED FOR REVIEW. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
THE DESIGN INFORMATION WAS NOT ON THE PLANS, PLEASE SUBMIT THE DESIGN LOAD COMPLIANCE
FORM OR ADD TO THE PLANS.