FL # FL6332-R8
Application Type Revision
Code Version 2017
Application Status Approved
Comments
Archived ❑
Product Manufacturer ICP Adhesives & Sealants, Inc.
Address/Phone/Email 12505 NW 44th Street
Coral Springs, FL 33065
(888) 774-1419 Ext 201
rylipelkonen@icpadhesives.com
Authorized Signature Riku Ylipelkonen
rylipelkonen@icpadhesives.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Roof Tile Adhesives
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
❑ Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed
Robert Nleminen
the Evaluation Report
Florida License
PE-59166
Quality Assurance Entity
UL LLC
Quality Assurance Contract Expiration Date
02/07/2021
Validated By
John W. Knezevich, PE
D Validation Checklist - Hardcopy Received
Certiflcate of Independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
FI Fa32 R8 COI 2017 01 COI Nieminen.pdff
Standard
SSTD 11
Product Approval Method Method 1 Option D
Year
1997
Date Submitted
10/12/2017
Date Validated
10/14/2017
Date Pending FBC Approval
10/17/2017
Date Approved
12/12/2017
Summary of Products
FL #
Model, Number or Name
Description
6332.1
ICP Adhesives Polyset AH-160
Dual component expanding polyurethane roof tile adhesive
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Design Pressure: +n/a/-178
Installation Instructions
R8 II 2017 10 FINAL ER ICP AH160 1`1-6332-
FFL6332
R8TOdf
Verified By: Robert Nieminen PE-59166
Created by Independent Third Party: Yes
Other. 1.) The design pressure limitation in this application
refers to hip and ridge tiles in one configuration. Refer to
Table 2 of ER for all hip and ridge file limitations. 2.) Field
tiles are designed based on overturning moment resistance.
Evaluation Reports
E 6332 R8 AE 2017 10 FINAL ER ICP AH160 FL6332-
R8,pdf
Created by Independent Third Party: Yes
Refer to Table i of ER for field tile limitations. 3.) Refer to ER
Sections 5 for other Limitations of Use.
Back Next
Contact Us;; 2601 Blair stone Road. Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida Is an AA/EEO employer. Coovrlcht 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mall address released In response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section 455.275
(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have one. The
emalls provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal address,
please provide the Department with an email address which can be made available to the public. To determine If you are a licensee under Chapter 455, F.S., please
click here.
Product Approval Accepts:
FER
Credit Card
Safe
��TRINITYJERD
EVALUATION REPORT
ICP Adhesives and Sealants, Inc.
12505 NW 44th Street
Coral Springs, FL 33065
(888) 774-1419
EXTERIOR RESEARCH & DESIGN, I.I.C.
Certificate of Authorization 119503
353 CHRIS-HAN STREET, UNIT 13
OXFORD, CT 06478
(203)262-9245
Evaluation Report 02768.03.06-118
FL6332-R8
Date of Issuance: 08/08/2008
Revision 8:10/12/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: ICP Adhesives Polyset® AH-160
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity I ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 9.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/12/2017. This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
�f TRINITYIERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Roof Tile Adhesives
Compliance Statement: ICP Adhesives Polyset® AH-160, as produced by ICP Adhesives and Sealants, Inc., has
demonstrated compliance with the eh Edition (2017) Florida Building Code through testing in accordance with the
Standards set forth herein. Compliance is subject to the Installation Requirements and Limitations / Conditions of
Use set forth herein.
2. STANDARDS:
Sections
Property
Standard
Year
1504.2.1.1
Overturning resistance
SSTD 11
1997
3. REFERENCES:
KnDy
Examination
Reference
Date
ERD (TST 6049)
Static Uplift—SSTD 11
P39740.02.12
02/20/2012
ERD (TST 6049)
Static Uplift—SSTD 11
P39740.11.13-R1
01/02/2015
ICC-ES (EVL2396)
2012 IBC Compliance
ESR-1709
12/01/2016
Miami -Dade (CER 1592)
HVHZcompliance
17-0322.03
04/27/2017
PRI (TST 5878)
Static Uplift—SSTD 11
ECM-001-02-01
09/21/2001
PRI (TST 5878)
Static Uplift —SSTD 11
PFI-006-02-01
05/09/2005
PRI (TST 5878)
Static Uplift—SSTD 11
PFI-006-02-02
05/09/2005
PRI (TST 5878)
Static Uplift — SSTD 11
PFI-007-02-01
10/11/2005
PRI (TST 5878)
Static Uplift—SSTD 11
PFI-008-02-04
02/21/2006
PRI (TST 5878)
Static Uplift —SSTD 11
PFI-009-02-03
02/21/2006
PRI (TST 5878)
Static Uplift—SSTD 11
TGRI-001-02-03
10/30/2006
PRI (TST 5878)
Static Uplift—SSTD 11
TGRI-001-02-03
10/30/2006
PRI (TST 5878)
Static Uplift — SSTD 11
PFPI-010-02-01
12/07/2006
PRI (TST 5878)
Static Uplift — SSTD 11
PFPI-011-02-01
12/07/2006
PRI (TST 5878)
Static Uplift— SSTD 11
PFPI-012-02-01
12/07/2006
PRI (TST 5878)
Static Uplift—SSTD 11
PFPI-013-02-01
12/07/2006
PRI (TST 5878)
Static Uplift — SSTD 11
PFPI-014-02-01
12/07/2006
PRI (TST 5878)
Static Uplift—SSTD 11
ECM-003-02-01
06/13/2008
PRI (TST 5878)
Static Uplift — SSTD 11
ECM-004-02-01
06/13/2008
PRI (TST 5878)
Static Uplift—SSTD 11
ECM-005-02-01
06/13/2008
PRI (TST 5878)
Static Uplift — SSTD 11
ECM-006-02-01
06/13/2008
PRI (TST 5878)
Static Uplift — SSTD 11
ECM-007-02-01
06/13/2008
PRI (TST 5878)
Static Uplift—SSTD 11
ECM-008-02-01
06/13/2008
UL LLC (QUA 9625)
Quality Assurance
Service Confirmation
Exp. 06/05/2018
4. PRODUCT DESCRIPTION:
4.1 ICP Adhesives Polyset® AH-160 is a two -component
expanding polyurethane
roof tile adhesive that is mixed
and dispensed from
a dispensing system provided by ICP Adhesives and Sealants, Inc. The components are
available in refillable
tanks or disposable cylinders (ICP Adhesives ProPacko 30 & 100).
S. LIMITATIONS:
5.1 This is a building code
evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in anyway, the Designer
of Record for any project on which this Evaluation
Report, or previous versions
thereof, is/was used for
permitting or design
guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
Exterior Research and Design, LLC.
Evaluation Report 02768.03.06-RS
Certificate of Authorization #9503
6T" EDITION (Z017) FBC NON-HVHZ EVALUATION
F1.6332-118
ICP Adhesives Polyset® AH-160; (888) 774-1419
Revision 8:10/1212017
Page 2 of 9
\I TRINITY ERD
5.3 Fire classification is not part of this evaluation. Refer to a current Roofing Materials Directory for fire ratings
of this product and FBC 1505.2.
5.4 ICP Adhesives Polyset® AH-160 can be used with flat, low and high profile tiles or any rigid, discontinuous roof
assembly having a current Florida Statewide Product Approval or approved on a local -level by the Authority
Having Jurisdiction.
5.5 Minimum underlayment shall be per FRSA/TRI April 2012 (04-12) or having a current Florida Statewide
Product Approval or approved on a local -level by the Authority Having Jurisdiction for use with ICP Adhesives
Polyset® AH-160.
5.6 Field tiles, meeting the limitations of FBC 1609.5.3, using ICP Adhesives Polyset® AH-160 are limited to
projects having an Aerodynamic Uplift Moment (M.), determined in accordance with FBC 1609.5.3 or Tables
2A and 213 of FRSA/TRI April 2012 (04-12), not greater'than the following Allowable Overturning Moment
values. Refer to Section 10 and ICP Adhesives and Sealants, Inc. published installation instructions for
Adhesive Paddy Placement details.
TABLE 1 FIELD TILES IN ICP ADHESIUES'POtYk AH 160 . ;
ALLOWABLE OVERTURNING MONIEN7 PERFORMANCE DATA
MARfifNOFSAFEIYAIREADPAPP/JEDFQR�INOhPENDENT(SINGLE.ORCbNZIN000S PA6i*0,110EMENT
UFSAAgY.. LREADYAPPIIED FQR•ll{IY'ERDEPENDENT (T4YO PA. DDY) PI 6MEM
Tile (FBC 1609.5.3)
Adhesive Paddy Placement
Allowable
Type
Profile
Mverturning
oment (ft Ibf)
Independent; Single Paddy, Medium (2x7-inch, ^30 gram)
60
Clay
Flat
independent; Single Paddy, Large (WO -inch, —45 gram)
112
Concrete
Interdependent; Two Paddy (4x4-inch on underlayment, 2x4-1nch at the overlap)
54
Independent, Single Paddy, Medium (2x7-inch, —30 gram)
39
Clay
Low/
Independent; Single Paddy, Large (2x10-inch, —54 gram)
67
Concrete
te
Medium
Interdependent; Two Paddy (44-inch on underlayment, 2x4-inch at tile overlap)
58
Clay
High
Independent, Single Paddy, Large (2x10-inch, —45 gram)
134
Independent; Single Paddy, Medium (2x7-inch, —30 gram)
65
Clay
High
Independent; Single Paddy, Large (W.0-inch, —63 gram)
109
Concrete
Interdependent; Two Paddy (44-inch on underlayment, 2x4inch at the overlap)
40
Clay
Barrel
2x10-inch x "35 gram for pans; 2 @ WO -inch x-17 gram for cap
147
Concrete
Barrel
2x10-inch x —35 gram for pans; 2 @ WO -inch x —17 gram for cap
107
Clay
Cap atop 2x
Independent: Continuous Paddy (-34 gram/ft)
135
stringer
Concrete
Cap atop 2x
Independent: Continuous Paddy (^' 34 gram/ft)
116
stringer
Clay
Cap atop 2x
Interdependent:
105
stringer
Head: One (1) #10 x 234" screw; Overlap: 1 x 6 inch (-10.5 gram)
Cap atop 2x
Interdependent:
I
76
Concrete
stringer
Head: One (1) #10 x 2%" screw; Overlap:1 x 6 inch (-10.5 gram)
5.6.1 Data in Table 1 relates to installation over a '30/90' underlayment system, as detailed in the FRSA/TRI April
2012 (04-12). Alternate underlayment systems include those having a current Florida Statewide Product
Approval and/or approved on a local -level by the Authority Having Jurisdiction specifically for use with ICP
Adhesives Polyset® AH-160.
5.6.2 Tile roof systems using tile types or profiles other than those listed above acquiring acceptance for use with
ICP Adhesives Polyset® AH-160 shall be tested in accordance with SSTD 11 or Testing Application Standard
TAS 101. For the interdependent two -paddy method, an additional 2-to-1 margin above that specified in
SSTD 11 or Testing Application Standard TAS 101 shall be applied in determining the 'allowable overturning
moment'.
Exterior Research and Design, LLC. Evaluation Report 02768.03.06-R8
Cerdfrcate ofAuthorizodon #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AN-160; (338) 774-1419 Revision 8:10/12/2017
Page 3 of 9
\,t TRINITY I ERD
5.7 Hip and ridge tiles using ICP Adhesives Polyset® AH-160 are limited to projects having hip/ridge design pressure
requirements, determined in accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater than the
following values. Refer to ICP Adhesives and Sealants, Inc. published installation instructions for Adhesive
Paddy Placement details.
TABLE2. HIP&RIDGE-761- okICPAbhESIVES:POLYSEf®AH'160
ALOWABLE UPLIFT:RESISTANCE PERFORNIAryCEDATA
=2 'TO. -1 MARGINOFSAFFfYA11tEAbYAPPuO FOR INDEPENDENT (CONi7N190}/S PADDY PLACEMENT
:.
4TDLINARGINOFSA ETYACREAAYAPPLIEDPOR/NIERDEPENOENT.109C?EM.:.
Allowable
Tile
Substrate
Attachment Method
Design Pressure
(Psf)
Clay
2x PT ridge board
Independent: Continuous Paddy (~34 gram/ft)
116
Concrete
2x PT ridge board
Independent: Continuous Paddy (- 34 gram/ft)
107
Interdependent: Head: One (1) #10 x 2%z" screw;
90
Clay
2x PT ridge board
Overlap: 1 x 6 inch (-10.5 gram)
Interdependent: Head: One (1) #10 x 2%' screw;
56
Concrete
2x PT ridge board
Overlap:1 x 6 inch (-10.5 gram)
Clay or
Hip & Ridge Channel Metal (FL5374):
Independent: Continuous Paddy (-34 gram/ft)
169
Concrete
galvanized only
Clay or
Trim Lock" (FL5374): aluminum,
Independent: Continuous Paddy (-34 gram/ft)
173
Concrete
galvanized, Galvalume® or stainless steel
Clay or
Trim Lock'" Plus (FL5374): aluminum,
Independent: Continuous Paddy (^ 34 gram/ft)
178
Concrete
galvanized, Galvalume® or stainless steel
Clay
Top Notch (FL8095)
Independent: Continuous Paddy (^ 32 gram/ft)
125
Concrete
Top Notch (FL8095)
Independent: Continuous Paddy (^ 32 gram/ft)
146
6. INSTALLATION:
6.1 ICP Adhesives Polyset® AH-160 and the tile roof assembly shall be installed in accordance with FRSA/TRI
April 2012 (04-12) and ICP Adhesives and Sealants, Inc. published installation instructions, subject to the
limitations outlined in Section 5.
6.2 Hip and ridge boards or hip/ridge metal shall be installed in accordance with the FRSA/TRI April 2012 (04-12).
Proprietary hip and ridge metal shall be installed in accordance with the manufacturer's Florida Product
Approval.
6.3 Installation shall be performed by applicators who hold a valid Qualified Applicator Card presented by ICP
Adhesives and Sealants, Inc.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the
installation of this product.
8. MANUFACTURING PLANTS:
Tomball, TX
9. QUALITY ASSURANCE ENTITY:
UL, LLC. - QUA9625; (847) 664-3623; LeAnna.Gradecki@ul.co_m
Exterior Research and Design, LLC. Evaluation Report 02768.03.06-118
Certiricate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH-160, (888) 774-1419 Revision 8:10/12/2017
Page 4 of 9
�TRINITYIERD
10. PADDY PLACEMENT DETAILS (FROM ICP ADHESIVES AND SEALANTS, INC. PUBLISHED LITERATURE):
10.1 Independent, Medium Paddy:
Nail through plastic cement
(when required)
(Beneath Tile) I
7 in�
Battens optional
Flat/Low Profile Tile
0
',— Eave Closure
Fascia
Medium Profile Tile
Nail through plastic cep-*--,
(when required) Paddy (Beneath Tile)
Undedayment
o
W
7 in. "*
2 in.
Battens optional
Eave Course Fascia
Weephole
loin. in. Eave closure
Drip edge
High Profile Tile
Exterior Research and Design, LLC. Evaluation Report 02768.03.06-R8
Certicate ofAuthorhadon #9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH-160; (839) 774-1419 Revision 8:10/12/2017
Page S of 9
10.2 Independent, Large Paddy:
Flat/Low Profile Tile
\,I TRINITY I ERD
Nall through plasticcement
(when required)
Underlayment
10 in.x
2 in.wide
Battens optional
Medium Profile Tile
Nail through plasticce
(when required) Paddy (Beneath Tile)
UI nderlayment
W
2in.wide
Battens
optional
Eave Course Fascia
Weephole
loin. in. Eave closure
Drip edge
High Profile Tile
Paddy (Beneath Tile)
`--- Eave Closure
Fascia
Exterior Research and Design, LLC. Evaluation Report 02768.03.06•R8
Certricate ofautharizadon #9503 6P EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH-160, (888) 774-1419 Revision 8:10/12/2017
Page 6 of 9
10.3 Interdependent, Two Paddy:
Nail through plastic cement Pad dy(between tiles)
(when required)
Battens optional °
o Paddy (under tile)
Single paddy
on top of the
4X41h.
Single paddy
underUl
Single paddy
on underlayment 2 x 4 in.
0 0
10 in.
Fascia
2 in.
Eave Closure
Flat/Low Profile Tile
Nail through plastic
(when required)
Battens
�innal � o x
on unneriayment
�4x4in.
Single 2x4in;�l�
paddyon
top of tile
Eave Course —
1Qin. 2in.
\,,1 TRINITY I ERD
Nail through plastic cement
Single paddy under tile
(when required)
Paddy (between tiles)
Battens
Paddy (under tile)
(optional
1 Single paddy
top of Ula�
��..on
x4in.
x4in.
Singla paddy on
underlayment
10 in.
2 in.
Eave Closure
Eave Course
Fascia
Medium Profile Tile
paddy under tile
Paddy (between tiles)
--VPaddy (under tile)
High Profile rile
weephole
Eaveclosure
Drip edge
Exterior Research and Design,LLC. Evaluation Report02768.03.06-R8
Certificate ofauthorization #9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polysete AH-160, (888) 774-1419 Revision 8:10/12/2017
Page 7 of 9
10.4
10.5
Two Piece Barrel (Cap & Pan) Tile:
t) Piece enough adhesive to achieve 65 to 70
in contact with the pantile.
2) Tum Covers upside down. Place adhesive
4121n. to Iinch in from outside edge of cover the.
Install cover tile.
Ensuro 20 to 25 sq. in. contact area on/�
:each side or cover Ole. _
Underlaymetn
(motarsh'own)
Fascia
Steep pitch applications
(when required)
Remove top portion of the eave course cover tite. Abut to second course of
pan tiles.Ensure eave end of pan and cover tiles are flush ateave fine.
Two Piece Barrel - High ProfileTile
Hip and Ridge (independent placement):
A bead of[CP Po4metZAH•160 way be appW above the 5614.
& surfice on both sides of the hiphidge board or s_atvm¢ed
metal frame to provxcitweawetblockmg.
To attach kibrlce Sks, ahead 0f1C9kPotystt8AH-1d0 VW
be applied do= the center ofthe hVidd¢e board or Vtvhdzed
frame.
\,/ TRINITY I ERD
Exterior Research and Design, LLC. Evaluation Report 02768.03.06-R8
Certificate ofAuthorizatlon 89503 6Ta EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH-160; (888) 774-1419 Revision 8:10/12/2017
Page 8 of 9
10.6 Hip and Ridae (interdependent placement):
Exterior Research and Design, I.I.C.
Certificate ofAuthorization #9503
- END OF EVALUATION REPORT -
e" EDITION (2017) FBC NON-HVHZ EVALUATION
ICP Adhesives Polyset® AH-160, (888) 774-1419
V I RINITY ERD
Evaluation Report 02768.03.06-118
FL6332-RS
Revision 8:10/1212017
Page 9 of 9