HomeMy WebLinkAboutProject Information ' � 1 ip I I v PROmOUCT SERVICES ;. BLOWERDOOR&DUCT LEAKAGETESTING TESTING-ADJUSTING-BALANCING y+� J U N 292020 �� tt re vit an-eint TESTING, ADJUSTING & BALANCING REPORT for RILL/VAH CONMR11MON COMPANY at thl pVartytyd one Planet 75fo W Highway f H Port it Lucie, FL 34952 June 22, 2020 +++ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES... certified�C Pi Pro-Duct Services, 1915 Rio Vista Rd,Fort Pierce, FL 34949 772.528.2076 pro-ductservicesfl@gmail.com �rM PROOUCT SERVICES BLOWERDOOR&DUCT LEAKAGE TESTING TESTING-ADJUSTING-BALANCING Pro-Duct Services is a National Balancing Council (NBC) certified firm,through the National Comfort Institute, NCI. The goal of the NBC certified technicians is to work with the design professionals, building owners and other tradesmen to achieve maximum system performance on all environmental systems. Due to the complexity of today's HVAC systems and the unique demands of struc- ture-occupants, having a qualified, certified Testing-Adjusting-Balancing (TAB) company balance these systems has now become more critical than it has ever been. NBC certified firms are able to achieve total system balance better than any other organization worldwide. Working in partnership with the other trades involved in your project is key to overall project success. Pro-Duct Services will work: closely with all involved to en- sure project schedules are met. By utilizing different pre-balance chechlists with the other trades, such as sheet metal, pipe fitters, HVAC and controls, project suc- cess can be achieved more reliably and timely. Utilizing NBC Procedural Standards is hey to achieving the design intent of today' sophisticated buildings. Understanding systems,their installation,their service maintenance requirements and procedures, and the manufacturer's start-up re- port helps in achieving system total balance for today's structures. Our technical testing and verification, coupled with repeat readings, ensure system functionality. With Pro-Duct Services you can be sure that our testing and verification process offers you the best value in the Testing, Adjusting, & Balancing industry. i p Certified IGO Pro-Duct Services, 1915 Rio Vista Rd, Fort Pierce,FL 34949 772.528.2076 pro-ductservicesjl@gmail.com I .. ,. .. ;; . .. . _. _ �t. .. _ . ..� - .. i -_ PRO=OUCT SERVICES BLOWER DOOR&DUCT LEAKAGE TESTING TESTING-ADJUSTING-BALANCING TEST & BALANCE INSTRUMENTS Evergreen Telemetry Capture Hood 151): Range: 100-2500 CFM Accuracy: +/- 3% Calibration: May 17, 2019 Evergreen Telemetry Capture Hood 8D-14: Range: 15-200 CFM Accuracy: +/- 3% Calibration: May 29, 2019 Evergreen Pressure/Velocity/Flow Sensing Module-Model S-PVF-1: Range: 1-2, 14-32 inches HG, 320 - 1580 F Accuracy: +/- 3% Calibration: June 5, 2019 Evergreen Wrist Reporter WR-401 Pro-Duct Services Technician: Michael Faurot Certified NCI Contractor/Supervisor/Technician NCI Commercial Certification ID: 19-229-03 —Equipment re-calibration is performed as required by testing guidelines. — Pro-Duct Services, 1915 Rio Vista Rd,Fort Pierce,FL 34949 772.528.2076 pro-ductservicesfl@gmaii.com . i CIN �11 CommerallAhr �� 7), wer ,r{- r MICHAEL FAUROT Has successfully completed the required training and passed r(}i rt 1. the written exam by the ` Nallunial No lore MIEN? In-C� to perform HVAC commercial system balancing up,to,20 tons J according to NO practical standards and procedures. ` _ ?I tflfo�"' Certified Since ;. May 9,2019, J .� as administered.and recognized by. p Eertifled CammerU9JW8nlnm L� i �.� \ SSSSLL����pp --• r� E.p+ma 9 2021 L r m n�^ ' nadlmar c�rr ru►c nspit F Ina Rot Falke;President QI- I Pro-Duct Services, 1915 Rio Vista Rc4 Fort Pierce,FL 34949 772.528.2076 pro-ductservicesfl@gmail.com �4�0� Ittat PRO=OUCT SERVICES BLOWERDOOR&DUCT LEAKAGETESTING TESTING-ADJUSTING-BALANCING AIR OUTLET CHARACTERIZATION for Sullivan Construction Company One Planet 7510 US Hwy 1 N, Port St Lucie, FL AIR HANDLER 1—East Side Vent FINAL Section Type Size Design CFM Number Type CFM 1 South Lobby CDP 24 x 24 350 356 2 Center Lobby CDP 24 x 24 350 331 3 North Lobby CDP 24 x 24 350 337 4 Restroom Lobby CDP 24 x 24 100 101 5 Restroom West CD 12 x 12 65 57 6 Restroom East CD 12 x 12 65 61 7 Break Room CDP 24 x 24 200 198 8 Office Confer CDP 24 x 24 150 138 9 Office Main CDP 24 x 24 150 146 Total 1725 Mechanical components cooling, working as designed and match COMMENTS plan requirements. +++ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES+++ Pro-Duct Services, 1915 Rio Vista Rd, Fort Pierce,FL 34949 772.528.2076 pro-ductservicesfl@gmail.com mom PRO-DUCT SERVICES BLOWERDOOR&DUCT LEAKAGE TESTING TESTING-ADJUSTING-BALANCING AIR OUTLET CHARACTERIZATION for Sullivan Construction Company One Planet 7510 Us Hwy 1 N, Port St Lucie, FL AIR HANDLER 2—West Side Vent Grill FINAL Number 4eetion Type faze Design CFM CFN 1 North Waiting Area CDP 24 x 24 350 341 2 South Waiting Area CDP 24 x 24 350 343 3 Main Area CDP 24 x 24 350 338 4 West Office CD 12 x 12 125 131 Total 1153 Mechanical components cooling, working as designed and match COMMENTS plan requirements. +++ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES+++ Pro-Duct Services, 1915 Rio Vista Rd,Fort Pierce,FL 34949 772.528.2076 pro-ductservicesfl@gmail.com I PRO-DUCT SERVICES BLOWERDOOR&DUCT LEAKAGE TESTING TESTING-ADJUSTING-BALANCING TESTING, ADJUSTING, & BALANCING WARRANTY for Sullivan Construction Company c One Planet, 7510 Us Highway 1 N, Port St Lucie, FL All Testing,Adjusting, & Balancing performed on this project by Pro-Duct Services is under warranty for a period of One Year from the date of completion of the Test & Balance, unless otherwise noted. Warranty will be considered null and void if another TAB company is brought in to evaluate the project without notifying Pro-Duct Services to be present at the time of the additional testing. Date of TAB Testing: June 22,2020 Warranty Expiration Date: June 30, 2021 Pro-Duct Services Authorized Signature: Pro-Duct.Services Technician: Michael Faurot Certified NCI Contractor/Supervisor/Technician NCI Commercial Certification ID: 19-229-03 BPI Certification ID: 5059122 +++ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES... �mfo , -i 4 O [ertlfled�C c-�ar...r.n. BPI `. J 1 � i Pro-Duct Services, 1915 Rio Vista Rd,Fort Pierce,FL 34949 772.528.2076 pro-ductse"icesfl@gmail.com v�emr'�- _.._ •' � I s. _ � � .. � i i PROmOUCT SERVICES BLOWER DOOR&DUCT LEAKAGE TESTING TESTING-ADJUSTING-BALANCING Pro Duct Services, 1915 Rio Vista Rd,Fort Pierce,FL 34949 772.528.2076 pro-ductservicesfl@gmail.com