Evaluation Report P12060.02.09-R25
FL5259-R29
Date of Issuance: 02/24/2009
Revision 25: 10/14/2019
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for
use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described
herein have been evaluated for compliance with the 61h Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: Polyglass Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). NEMO I etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMO l etc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 16.
Prepared by:
Robert J.M. Nieminen, P.E.�s
fi
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen, P.E. on
10/14/2019. This does not serve as an electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO I etc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO I etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO I etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
02019 NEMO ETC, LLC
4.
4.18
4.19
4.20
F
ONEMOletc.
PRODUCT DESCRIPTION:
Product
Specification
Plant(s)
Description
Polystick MU-X
ASTM D1970
FL, NV, PA
Nominal 54-mil thick dual -layer rubberized asphalt
(See Section 5.8)
waterproofing membrane, fiberglass reinforced, with a
polypropylene film surface
Polystick TU Max
ASTM D1970
FL, PA, TX
Nominal 60-mil thick rubberized asphalt waterproofing
TAS 103
membrane with a 190 g/m2 polyester fabric surface
FRSA/TRI April 2012
Polystick TU P
TAS 103
TX
Nominal 130-mil thick rubberized asphalt waterproofing
FRSA/TRI April 2012
membrane, glass-fiber/polyester reinforced, with a
granular surface
Polystick TU Plus
ASTM D1970
FL, PA
Nominal 80-mil thick rubberized asphalt waterproofing
TAS 103
membrane, glass fiber reinforced, with a polyester fabric
FRSA/TRI April 2012
surface
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO l etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless
retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of
this product.
5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within
FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this
evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
Wood Shakes
Underlayment
Asphalt Shingles
Nail -On Tile
Foam -On Tile
Metal
& Shingles
Slate
Elastobase
Yes
Yes
Yes
Yes
Yes
Yes
(Base Sheet in 2-ply system)
(Base Sheet in 2-ply system)
Elastobase P
Yes
Yes
Yes
Yes
Yes
Yes
(Base Sheet in 2-ply system)
(Base Sheet in 2-ply system)
Polyglass Base
No
Yes
Yes
No
No
No
(Base Sheet in 2-ply system)
(Base Sheet in 2-ply system)
Polyglass G2 Base
No
Yes
Yes
No
No
No
(Base Sheet in 2-ply system)
(Base Sheet in 2-ply system)
Elastoflex G TU
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Elastoflex S6 G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Elastoflex S6 G FR
Yes
Yes
No
No
Yes
Yes
HydraGuard Dual Pro
Yes
No
No
Yes
Yes
Yes
HydraGuard Tile Pro
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
Mule -Hide SA-APP Cap
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Sheet
Mule -Hide SA-APP Cap
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Sheet(FR)
Polyflex G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Polyflex G FR
Yes
Yes
No
No
Yes
Yes
Polyflex SA P
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Polyflex SA P FR
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Polystick IR-Xe
Yes
No
No
No
Yes
Yes
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R25
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-1129
Polyglass Roof Underlayments; (954) 233-1230 Revision 25: 10/14/2019
Page 4 of 16
ONEMOjetc.
TABLE 1: ROOF COVER OPTIONS
Underlayment
Asphalt Shingles
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
& Shingles
Slate
Polystick MTS Plus
Yes
Yes
No
Yes
Yes
Yes
Polystick MU-X
Yes
No
No
Yes
Yes
Yes
Polystick TU Max
No
Yes
Yes (See 5.5.1)
Yes
No
No
Polystick TU P
No
Yes
Yes (See 5.5.1)
No
No
No
Polystick TU Plus
Yes
Yes
Yes See 5.5.1
Yes
s
Yes
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combin
TABLE 1A: ALLOWABLE TILE ADHESIVE / UNDERLAYMENT COMBINATIONS'
Florida Product
Adhesive
Approval
Underlayments
DAP Foam Touch `n Seal Storm Bond
FL14506
Polystick TU Max or Polystick TU Plus
Roof Tile Adhesive
Dow TileBond'm
FL22525
HydraGuard Tile Pro, Polyflex SA P, Polystick TU Max, Polystick TU P or
PolystickTU Plus
Elastoflex G TU, Elastoflex S6 G, HydraGuard Tile Pro, Mule -Hide SA-APP
ICP Adhesives Polyset® AH-160
FL6332
Cap Sheet, Mule -Hide SA-APP Cap Sheet (FR), Polyflex G, Polyflex SA P,
Polyflex SA P FR, Polystick TU Max, Polystick TU P or Polystick TU Plus
Elastoflex S6 G, HydraGuard Tile Pro, Mule -Hide SA-APP Cap Sheet, Mule-
ICP Adhesives Polyset° RTA-1
FL6276
Hide SA-APP Cap Sheet (FR), Polyflex G, Polyflex SA P, Polyflex SA P FR,
Polystick TU Max, Polystick TU P or Polystick TU Plus
5.6 Allowable Substrates:
TABLE 2: SUBSTRATE OPTIONS FOR ADHERED UNDERLAYMENTS
Substrates (designed to meet wind loads for project)
Underlayment
Application
Type
Primer
Material(s)
Deck /
(Optional) ASTM D41
plywood, OSB, Southern Yellow Pine or Huber
HydraGuard Dual Pro,
Engineered Woods "ZIP System" Panels
HydraGuard Tile Pro,
sheathing
ASTM D41
structural concrete
Polystick (all variations),
Mule -Hide SA APP Ca p
self-
(Optional) ASTM D41
ASTM C1289 Type II Class 1 polyisocyanurate, ASTM
Sheet, Mule -Hide SA-APP
adhering
Insulation
or WB-3000
C1289 Type V polyisocyanurate-composite, DensDeck
Cap Sheet (FR), Polyflex
Prime or SECUROCK Gypsum -Fiber Roof Board
Base
N/A
ASTM D226 felt, Elastobase, Elastobase P or Mule -Hide
SA P or Polyflex SA P FR
Sheet
Nail Base
Deck
ASTM D41
structural concrete
Elastoflex G TU, Elastoflex
Insulation
(Optional) ASTM D41
DensDeck Prime or SECUROCK Gypsum -Fiber Roof Board
S6 G or Elastoflex S6 G FR
hot asphalt
Base
ASTM D226 felt, Elastobase, Elastobase P, Mule -Hide Nail
N/A
Sheet
Base or Polyglass G2 Base
Deck
ASTM D41
structural concrete
Polyflex G or Polyflex G FR
torch-
Insulation
(Optional) ASTM D41
DensDeck Prime or SECUROCK Gypsum -Fiber Roof Board
Base
N/A
Elastobase, Elastobase P, Mule -Hide Nail Base, Polyglass
applied
Sheet
G2 Base or Polyglass Base
'Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R25
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-1129
Polyglass Roof Underlayments; (954) 233-1230 Revision 25: 10/14/2019
Page 5 of 16
6.4
NNEMOjetc.
HydraGuard Dual Pro, HydraGuard Tile Pro, Mule -Hide SA-APP Cap Sheet, Mule -Hide SA-APP Cap Sheet (FR), Polyflex SA P,
Polyflex SA P FR, Polystick IR-Xe, Polystick MTS Plus, Polystick MU-X, Polystick TU Max, Polystick TU P or Polystick TU Plus:
6.4.1 General:
All seal -lap seams (selvage laps) must be firmly rolled with a in
accordance with Polyglass requirements to ensure full contact
and adhesion. For HydraGuard Dual Pro and HydraGuard Tile
Pro, align the edge of the top sheet to the end of the glue
pattern (the sheet will overlap the fabric).
View of Ovelap Seam of HydraGuard Dual Pro and HydraGuard Tile Pro
6.4.2 Non -Tile Applications:
Shall be installed in compliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment in FBC
Table 1507.1.1 for the type of prepared roof covering to be installed and Polyglass published requirements.
6.4.3 Tile Applications (excludes HydraGuard Dual Pro, Polystick IR-Xe and Polystick MU-X):
Shall be installed in compliance with the requirements for Self -Adhered Membrane set forth in FRSA/TRI April 2012 (04-12) and
Polyglass published requirements.
For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet
fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1.
For adhesive -set tile applications, refer to Section 5.6.1 herein.
6.4.4 Multi -Ply Underlayment Systems:
Polystick MTS Plus followed by HydraGuard Tile Pro, Polyflex SA P, Polystick MTS Plus, Polystick MU-X, Polystick TU Max,
Polystick TU P or Polystick TU Plus is allowable for use under mechanically attached prepared roof systems. Limits of use are
those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is
desired.
Polystick MTS Plus followed by HydraGuard Tile Pro, Polyflex SA P, Polystick TU Max, Polystick TU P or Polystick TU Plus is
allowable for use under adhesive -set tile systems. Limits of use are those associated with the top -layer material. This is not a
requirement, but is allowable if a 2-ply underlayment system is desired.
6.5 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR:
6.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published installation
requirements. For use in tile applications:
✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing' (ASTM D6380, Class M) in the "Single Ply System"
from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet"
in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems.
✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System"
from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet"
in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems.
✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap
Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems.
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R25
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R29
Polyglass Roof Underlayments; (954) 233-1230 Revision 25: 10/14/2019
Page 15 of 16