Field Density Tests of Compacted Soils Method D-6938
Project: Proposed Residence Date: November 15, 2019
Address: 4419 Pressler Lane, Fort Pierce, FL 34982 Order#: 19CMT2941
Area Tested: Building Pad Permit#: O '00 a—J
Material Type: Brown Sand Tech: SL
Client: Groza Builders, Inc.
Address: 511 SW Port St. Lucie Blvd. Compaction Req.: 95%
Port St. Lucie, FL 34953 Proctor Method: ASTM D-1557
Test Probe Moist Dry Proctor Optimum
# TEST LOCATION Depth Elev. % Density Value Moisture Compaction Pass
PCF PCF %
1 NW Corner of Building Pad 12" FL 7.1 109.1 114.0 10.0 95.7% Yes
2 SW Corner of Building Pad 12" FL 9.9 108.9 114.0 10.0 95.5% Yes
3 SE Corner of Building Pad 12" FL 8.6 111.3 114.0 10.0 97.6% Yes
4 NE Corner of Building Pad 12" FL 9.3 109.5 114.0 10.0 96.1% Yes
5
6
7
8
9
10
11
12
13
14
Remarks: See Reverse Side(Page 2 of 2)for Additional Information for Disclaimer
This is a Compaction Test only on the top 12"of the pad and is not a verification of Soil Bearing Capacity.
Legend for Elevation: AlPR=Proofroll 1,2,3= 1 st,2nd,3rd Lift Submitted by: � �.
SL=Springline FL=Final Lift Keith LeBlanc, F.E.
SG=Subgrade BG=Below Grade Federal Engineering&-1estirg;Inc:
BC=Basecourse BOF=Bottom of Footing Florida Reg:No,59394 -
TOP=Top of Pipe FG=Finished Grade Certificate of..Authorization,#5471,
As a mutual protection to clients,the public and ourselves,all reports are submitted as the confidential property of clients, and-authorization for publication of'sta:e-ments,
conclusions or extracts from or regarding our reports is reserved pending our written approval.A density test determines the degree of-compF.rtiaa of tt a 3estea,layer of
material only.A density does not replace a soil bearing capacity determination.These density tests do not certify the underlying soi!-materials b�llow,the proposed'structure.
The results do not preclude or guarantee that future settlement and cracking will not occur.A soil boring test is required to certify that the:nidi3 l ying sofis-will support the
proposed structure without settlement.If no soil borings have been performed to verify the_underlying soils,we recommend that soil borings he performsc:`io evaluate the
suitability of the underlying soil to support the proposed structure.After laying dormant for a period of 90 days or after heavy rain/storms,retesting must be performed on this
work.
PAGE 1 of 2
r.
}
Compacted Soils Method ®-6936 Disclaimer
Pursuant to your request, Federal Engineering & Testing, Inc. (FET) has performed a compaction test-at the referenced
project on the reverse side. The purpose of our test was to determine the degree of compaction of the tested layer of
material only. In no way shall a compaction test replace a soil bearing capacity determination. A soil boring test must be
performed by the client prior to construction to verify subsoil conditions. Our scope of services only included testing the top
12" of added fill material. FET was not contracted to perform supervision of the building pad preparation. This testing of
the added fill material does not include an analysis of the underlying soil materials to determine if they are capable of
supporting the proposed structure without settlement. This density compaction test does not warranty any underlying soil
materials or conditions below the tested top 12 inches of material. If no soil borings have been performed in the location of
the proposed structure, we recommend performing soil borings below all foundation areas of the proposed structure to
verify the underlying soil conditions.
Environmental analysis of the soil materials is not part of the scope of services. If environmental analysis of the soils is
required, we can provide a proposal for performing an environmental analysis of the soil materials. The scope of services is.
for determination of the degree of compaction of the tested layer of material only. No other analysis is implied or warranted.
Job project specifications were not available at the time the work was performed. Determination of the pass/fail compaction
results are based on current common industry requirements of 95% of the ASTM D-1557 standard for building foundations
and 98% of the AASHTO T-180 standard for.paved areas such as roadways and parking lots. If different specifications are
required, Federal Engineering &Testing, Inc. shall be notified.
Our findings are relative to the date and areas of our site work and should not be relied upon to represent conditions on
other areas or dates. Any subsequent site disturbances due to water erosion, rain waters, construction activities, utility or
footing excavations, overgrown vegetation, traffic and other disturbances will void this test and the site must be re-
compacted and re-tested prior to construction.
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of our client
and authorization for use, publication of statements, conclusions or extracts from or regarding our reports is reserved
pending our written approval.
It has been a pleasure working with you and we look forward to doing so in the near future.
Page 2 of,2
Dederal Phone: 954-784-2941
E-Fax: 954-784-7875
Ong I neerl ng admin@fed-eng.com
www.fed-eng.com
®[vesting, Inc. ITEM
No. 200 Wash Sieve Analysis
Date: Friday,November 15, 2019 Job Order Number 19CMT2941
Groza Builders,Inc.
511 SW Port St. Lucie Blvd.
Port St. Lucie, FL 34953
RE: Engineering Services
Proposed Residence
4419 Pressler Lane
Fort Pierce, FL 34982
RESULT OF TESTS
Location: Building Pad
Sampled By: SL Reported To: Client
Sample Description: Brown Sand
Weight: 621.16 g
Cumulative Wt. Cumulative % Cumulative %
Sieve Size Retained (g) Passing Retained
#200 561.66 9.6% 90.4%
Pan ---- ---- ----
Tested By: SJ (TIN#J32378081-000)
Checked By: KL
Respectfully Submitted
Keith LeBlanc, P.E: _ ,��., r
Federal Engineering 8:Testing, Inc. ,
Florida Registration#59394=
Certificate of Authorization.#_5471 -
MSM �CI �M�^ ` k�®® ■
-� Approved Laboratory �7
®ederal Phone:954-784-2941
E-Fax: 954-7844875
G."n9ineering admin@fed-eng.com
www.fed-eng.com
esting, Inc.__7
Organic Content Test(AASHTO T-267)
Date: Friday,November 15,20.19 Job Order Number 19CMT2941
Groza Builders,Inc.
511 SW Port St. Lucie Blvd.
Port St. Lucie,FL 34953
RE: Engineering Services
Proposed Residence - - -- - --- __
4419 Pressler Lane
Fort Pierce, FL 34982
RESULT OF TESTS
Location: Building Pad
Sampled By: SL Reported To: Client
Sample Description: Brown Sand
Crucible Weight Crucible Weight
Crucible +Material +Material Organic
Weight Content
Before Burn After Burn
(grams) (grams) (grams) (% by Weight)
IF22.98 59.11 58.65 1.27
_- -- -_ Tested By:-^ SJ (TIN#J3237808 1-000) .-
Checked By: . KL
Respectfully Submitt ,
Keith LeBlanc, P.E.
Federal Engineering'&�T-_esting,`hic
Florida RegiAration`#59394 ,`
Certificate of Autho`izatiori#`547 a
Oakland Park,Florida 33334s
aci; �E �l�:�.'=�=1, Ctl1'FDOT
_�� _ Approved Laboratory �'T
Dederal Phone: 954-784-2941
E-Fax: 954-784-7875
ngineering admin@fed-eng.com
Q
www.fed-eng.com
(goesting, inc.
PROCTOR COMPACTION TEST
DATE SAMPLED: 11/15/2019 DATE TESTED: 11/18/2019 SAMPLE#: 19CMT2941
CLIENT: Groza Builders, Inc.
ADDRESS: 511 SW Port St. Lucie Blvd.
Port St. Lucie, FL 34953
PROJECT: Proposed Residence
LOCATION: 4419 Pressler Lane, Fort Pierce, FL 34982 Sampled from Building Pad
MATERIAL DESCRIPTION: Brown Sand MATERIAL#: N/A
SAMPLED BY: SL TESTED BY: Si TIN#: J32378081-000
SPECIFICATION GOVERNING: ASTM D-1557 LAB NO: 104035
RESULTS OF TEST:
The following compaction test was conducted in accordance with the Standard Methods of Moisture Density Relations of soil using a 10 lb.Hammer and
an 18"drop as per the above specified method.
MOISTURE% WET DENSITY(PCF) DRY DENSITY(PCF)
7.8 119.9 111.2
9.0 123.8 113.6
10.8 126.1 113.8
13.1 125.7 111.1
114.5 Optimum Moisture (Percentage)
114.0 10.0 %
LL 113.5 ---- --_--_ - — -- Maximum Dry-Density (lbs./cu. Ft.) - ---- --
a 113.0 114.0 PCF
N 112.5
c
a�
112.0 Respectfully Submitted,
L
111.5
111.0
Keith LeBlanc, P.E. .
110.5 Federal Engineering 9�Testing, Inc.f
7 8 9 10 11 12 13 14 Florida Reg. No 55394
Moisture (%) Certificate of Authorization No.'S471-_ -
r _
MIAMF�AD
®� F®®
�L qCl i �-1-
O ROImMIq' / � Approved Laboratory