Residential Prescriptive, Performance or ERI Method Compliance
.2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction:St. Lucie County Permit#: 1901-0225
Job Information
Builder: Round Hill Development Group, Inc. Community:. Marsh Landing at the Reserve Lot: NA 72
Address:7233 Marsh Ter
City: Port St. Lucie State: FL zip: 34986
Duct Leakage Test Result s O Prescriptive Method Qf Performance/ERI Method
System 1 58 cfm25. 0_ Prescriptive Method cfm25 (Total)
System 2 cfm25 To qualify as"substantially leak free"Qn Total must be less than or
equal to 0.04 if air handler unit is installed. If air handler unit is not
System 3 cfm25 ,installed, Qn Total must be less than or equal to 0.03. This testing
method meets the requirements in accordance with Section R403.3.3.
Sum of any cfm25 Is the air handler unit installed during testing? ❑YES (!'A ❑ NO(5a�
Total of all 58 cfm25
QQ.Performance/ERI Method cfm25 (Out or Total)
To qualify using this method, Qn must not be greater than-the
58 _ 2055 = 0.028 Qn proposed duct leakage Qn specified on Form R405-2017 or R406-201
Total of all Total Conditioned
systems Square Footage .Leakage'Type selected on Form. Qn specified on Form R405-2017
R405-2017(EnergyCalc)or,R406-2017 (EnergyCalc)or R406-2017
J PASS FAIL
Proposed Leak Free 0.03
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5)or(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g)or(i), Florida Statutes.
Testing Company
Company Name: Ecolnnovative Phone: 772-501-0152
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building'Code requirements with the
selected compliance path aas stated
//above, either the Prescriptive Method or Performance Method.
Signature of Tester: Date of Test: April 16, 2020
Printed Name of Tester: Kathleen Connolly
License/Certification#: 5060036 Issuing Authority: BPI, INC.
6/11/2019 1:36:40 PM EnergyGauge®USA 6.0.03(Rev.1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
L
Duct Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction:St. Lucie County- Permit#: 1901-0225.
Job Information
Builder: Round Hill Development Group, Inc. Community: Marsh Landing at the Reserve Lot: NA 72
Address:7233 Marsh Ter
City: port St. Lucie State: FL Zip: 34986
Duct Leakage Test Results O ,Prescriptive Method Performance/ERI Method
System 1 58 cfm25 . O' prescriptive Method cfm25(Total)
System 2 cfm25 To qualify as"substantially leak free"Qn Total must be less than or
equal to 0.04 if air handler unit is installed. If air handler unit is not
System 3 cfm25 installed, Qn Total must be less than or equal to 0.03. This testing
method meets the requirements in accordance with Section R403.3.3.
Sum of any cfm25 Is the air handler unit installed during testing? ❑YES(S ❑ NO(S��
Total of all 58 cfm25
QQ Performance/ERI Method cfm25 (Out or Total)
To qualify using this method, Qn must not be greater.than the
58 _ 2055 = 0.028 Qn proposed duct leakage Qn specified on Form R405-2017 or R406-201
Total of all Total Conditioned
systems Square Footage Leakage Type selected on Form Qn specired on Form R405-2017
R405-2017(EnergyCalc) or R406-2017 (EnergyCalc)or R406-2017"
� PASS FAIL
Proposed Leak Free 0.03
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5)or(7),.Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g)or(i), Florida Statutes.
Testing Company
Company Name: Ecolnnovative Phone: 772-501-0152
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the
selected compliance path aas stated
/above,either the Prescriptive Method or Performance Method.
Signature of Tester: il�Yi�Y /y Date of Test: April 16, 2020
Printed Name of Tester: Kathleen Connolly
i
License/Certifii ation#: 5060036 Issuing Authority: 'BPI, INC.