,duly 24, 2020
IVOILAR
IKI%
Eric Machado
Secure Gas, Inc.
1064 Persian Lane
Sebastian, Florida 32958
Re: 500 Gallon Underground Tank
Conifer Drive, Lot 69
Fort Pierce, Florida
KSM Project #: 203410-lpgas
Dear Mr. Machado:
ng
F N A i N�� R) N A P.O. Box 78-1�3t77
Sebastian, FL. 32978
ANOTESTING Phone: 772 599 0712
C.A. # 5693
KSMengineering.net
Please see attached detail for how to tie down the 500 gallon underground tank
at the referenced site. The following are general notes concerning the attached
drawing.
1. Prior to installing the earth augers, check for underground utilities.
2. Earth auger and cables shown are designed to resist buoyancy forces
from an empty tank fully submerged.
3. Earth augers type and length is dependent of Soil Class. For this site soil
is assumed as Class 4 Soil. If the onsite soils are not Class 4, engineer is
to be notified.
4. Earth auger shall have a tested minimum pull out value of 3000 lbs.
5. Location of tanks are dependent on local codes and are the responsibility
of the persons obtaining the permit.
questions, please feel free to contact the office.
5 �
R • A EL
Proudly Serving Florida since 1990
GROUND LEVEL
\\ \\ \\ \ \ 114 GALVANIZED VINYL COATED
500 GAL. WIRE ROPE WI CABLE CLAMP,
/' (2 REQUIRED)
\\ \\ \\ LP GAS
TANK /
518 x 48 TRAILER ANCHOR
WITH 6" HELIX (4 REQUIRED)
GROUND LEVEL_
114" GALVANIZED VINY�COATED
i
2 REQUIRED E ROPE
500 GAL.
LP GAS 5/8" x 48" TRAILER ANCHOR /\
TANK WITH 6" HELIX, 4 REQUIRED
ENGINEERS SEAL SHOULD BE BLUE IN COL 'R; 44aT
CONTACT ENGINEER TO VERIFY SEAL IS AUTHENTIC +\ \\ \\ \
PROJECT: Secure Gas:, Conifer Drive Lot 69, Fort Pierce, Florida
SHEET 1 OF 1 %F CP Sk .9 ENGINEERING DRAWN BY: J.L.
DESIGNED BY. J.K.
66 4VL
AND TESTING
DATE: 0712412020