Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutEnergy CodeHEATING & COOLING LOAD SUMMARY SHEET I1
Project Name: O�FI[.E eULLoioq "A„
Project Owner: ,4q-C-6rti—Y-lC. TOSS CoMpfr►JY
Project Address:
FT, Pta ae-a, F�La21 P A
Sizing Method Used: ASHRAE Handbook of Fundamentals, 1997, Chapter26
Compliance Criteria: Florida Building Code, 2001 Edition
Section 407.1.ABCD.1 Sizing, Exception #1
Heating/Cooling Zone (PHv tcu)
Conditioned Floor Area (sq.ft.)
IoSo
{13%
1G13
l(S2
Outdoor Dry Bulb ( °FDB)
91,0
91,o
9 (, O
q 1,,0
Outdoor Wet Bulb (°FWB)
78,0
78.b
78.0
76.o
Indoor Dry Bulb (°FDB)
79 O
-7S o
ZS,o
7a.0
Indoor Relative Humidity
6O7o
5oc7o
GbTb
S 6%
Difference Water Vapor (Grains/lb.)
5915
59.5
S4,S
34,S
Cooling Sensible Load (BTUH)
22,2 -t-
27/43o
2b
38)276
Cooling Latent Load (BTUH)
7121?0
-7
713 ?o
It, 9'6o
Cooling Total Load (BTUH)
with required outdoor air
MIS-3o
3S7,230
33,610
481230
Heating Total Load (BTUH)
with required outdoor air
l31SZo
14) S'70
'I1 26 o
L4�32p
HVAC systems and equipment sizes thus comply with Florida Building
Code, 2001 Edition, Section 407.1.ABCD.1.1: lbw 4, A- M 1
ENERGY EFFICIENCY CODE;TOR_BUILDING CONSTRUCTION
" Florida Department,of Community Affairs
} _ _ EnergyGauge FlaCom v121 FORM 400A 2001 � �-
Whole Building Performance Method; for Commercial Buudings
Jurisdiction: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
Short Desc: ATLTROFC03 Project: MFG PLANT - OFFICE
Owner: ATLANTIC TRUSS COMPANY
Address: Ft. Pierce
x
City: Ft. Pierce
State: Florida PermitNo: Pending
Zip: 34954 Storeys: 1
Type: Office (Business) GrossArea: 4952
Class: New Finished building Net Area: 4952
Compliance Summary
Component Design Criteria Result
Gross Energy Use 95.49 100.00 PASSES
Other Envelope Requirements - A PASSES
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
Yes/No/NA
10/7/03 EnergyGauge FlaCom FLCCSB v1.21 1
'COMPLIANCE CERTIFICATION:
I hereby certify that the plans and specifications Review of the plans and specifications covered by this
covered by this calculation are in compliance calculation indicates compliance with the Florida Energy
with the Florida Energy EfBcien Code. Efficiency Code. Before construction is completed, this building
will be inspected for compliance in accordance with Section
553.908, Florida Statutes.
PREPARED BY:
BUILDING OFFICIAL:
DATE: DATE:
I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Cod(
SYSTEM DESIGNER
ARCHITECT:
MECHANICAL:
ELECTRICAL:
LIGHTING:
REGISTRATION/STATE
1 4l
(") Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevantinformation is contained on signed/sealed plans.
10/7/03 EoergyGauge FlaCom FLCCSB v1.21
Project: ATLTROFC03
Title: MFG PLANT - OFFICE
Type: Office (Business)
Location: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
(WEA File: DAYTONABEACH.
Total
Design Reference
95.49
100.00
IlCredits & Penalties (if any): Modified Points: = 95.49 PASSES' III
ion/03
EnergyGauge FlaCom FLCCSB v1.21
3
Project: ATLTROFC03
Title: MFG PLANT - OFFICE
Type: Office (Business)
Location: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
(WEA File: DAYTONABEACH.
Other Envelope Requirements
Item Zone Description
Design
Limit
Meet Req.
Zo 1 Zo l Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Zo2 Zo2 Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Zo3 Zo3 Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Zo4 Zo4 Exterior Roof - Max Uo Limit
0.05
0.09
Yes
Meets Other Envelooe Reauirements
External Lighting Compliance
Allowance
Area or
ELPA
CLP
Desc Category (W/Unit)
a
Length
(W)
(W)
10/7/03 EnergyGauge FlaCom FLCCSB vl.21
Project: ATLTROFC03
Title: MFG PLANT - OFFICE
Type: Office (Business)
Location: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
(WEA File: DAYTONABEACIL
Lighting Controls Compliance
Area
No. of
Design
Min
Compli-
Acronym ra9ehID
Description
(sq.ft)
Tasks
CP
CP
ance
Zolofc 32
Offices (Partitions<3.5 ft below
798
1
4
2
PASSES]
ceiling) Open plan offices 900 ft or
larger with partitions higher
ZOITIt 13
Toilet and Washroom
252
1
2
2
PASSES,]
Zo2-Ofc 32
Offices (Partitions<3.5 ft below
871
1
3
3
PASSESJ
ceiling) Open plan offices 900 ft or
larger with partitions higher
Zo2-Sto 44
Storage & Warehouse - Inactive
266
1
2
2
PAS901
Storage
Zo3-Ofc 32
Offices (Partitions<3.5 ft below
780
1
3
3
PASSES
ceiling) Open plan offices 900 ft or
larger with partitions higher
Zo3-Sto 44
Storage & Warehouse - Inactive
150
1
2
2
fiX StE
Storage
Zo3-Corr 2
Corridor
683
1
2
2
1?ASSES
Zo4-Ofc 32
Offices (Partitions<3.5 ft below
991
1
5
3
]?A$SES
ceiling) Open plan offices 900 ft or
larger with partitions higher
Zo4-Tlt 13
Toilet and Washroom
161
1
2
2
PASSES?
10/7/03 EnergyGauge FlaCom FLCCSB vl.21
Project: ATLTROFC03
Title: MFG PLANT - OFFICE
Type: Office (Business)
Location: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
(WEA File: DAYTONABEACH.
System Report Compliance
Zol
AHU/CU-1
Unitary Systems
Caps- Design
Eff Design
IPLV
Comp -
Component
Category
city
Eff
Criteria IPLV
Criteria
liance
Cooling System
Air Cooled < 65000 Btu/h
30200
12.40
10.00 12.40
PASSES
Cooling Capacity
Heating System
Electric Furnace
16380
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
10
0.80
0.80
PASSES
System -Supply
Constant Volume
Zo2
AHU/CU-2
Unitary Systems
Capa- Design
Eft Design
IPLV
Comp -
Component
Category
city
Eft
Criteria IPLV
Criteria
liance
Cooling System
Air Cooled < 65000 Btu/h
35600
12.40
10.00 12.40
PASSES
Cooling Capacity
Heating System
Electric Furnace
16380
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
10
0.80
0.80
PASSES
System -Supply
Constant Volume
Zo3
AHU/CU-3
Unitary Systems
Caps- Design
Eff Design
IPLV
Comp -
Component
Category
city
Elf
Criteria IPLV
Criteria
liance
Cooling System
Air Cooled < 65000 Btu/h
35600
12.40
10.00 12.40
PASSES
Cooling Capacity
Heating System
Electric Furnace
16380
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
10
0.80
0.80
PASSES
System -Supply
Constant Volume
Zo4
AHU/CU-4
Unitary Systems
Capa- Design
Eff Design
IPLV
Comp -
Component
Category
city
Eff
Criteria IPLV
Criteria
liance
Cooling System
Air Cooled < 65000 Btu/h
47000
12.30
10.00 12.30
PASSES
Cooling Capacity
Heating System
Electric Furnace
16380
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
10
0.80
0.80
PASSES
System -Supply
Constant Volume
10/7/03 EnergyGauge FlaCom FLCCSB vl.21
Plant Compliance
Installed
Design Min Design Min
Comp
Description No
Size Eff Eff IPLV IPLV Category
liance
Project: ATLTROFC03
Title: MFG PLANT - OFFICE
Type: Office (Business)
Location: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
(WEA File: DAYTONABEACH.
Water Heater Compliance
Design
Min Design
Max Comp
Desc Type
Category
Eff
Eff Loss
Loss liance
Water Heater 1 Storage Water Heater - <=120 [gal] & <= 12 1.00
0.88 0.12
PASSES '
Electric
[kW]
PASSES ' �"
Project: ATLTROFC03
Title: MFG PLANT - OFFICE
Type: Office (Business)
Location: FORT PIERCE, ST L
Piping System Compliance
Pipe Dia Is Operat Ins Cond Ins Req Ins Comp
Category
[inches] Runout Temp ]F] Btu-in/h Thick [in] Thick [in] liance
r.SF.F
Domestic and Service Hot Water Systems
0.75 False 120.00 0.28 1.35 1.33 PASSES
10/7/03 EnergyGauge FlaCom FLCCSB v1.21
:t: ATLTROFC03
MFG PLANT - OFFICE
Office (Business)
ion: FORT PIERCE, ST L
Other Required Compliance
11Category Section Requirement (write N/A in box if not applicable) Check II
filtration
406.1
Infiltration Criteria have been met
rstem
407.1
HVAC Load sizing has been performed
entilation
409.1
Ventilation criteria have been met
DS
410.1
Duct sizing and Design have been performed
& B
410.1
Testing and Balancing will be performed
lectrical
413.1
Metering criteria have been met
otors
414.1
Motor efficiency criteria have been met
ighting
415.1
Lighting criteria have been met
& M
102.1
Operation/maintenance manual will be provided to owner
oof/Ceil
404.1
R-19 for Roof Deck with supply plenums beneath it
10/7/03 EnergyGauge FlaCom FLCCSB v1.21 8
L
ENERGY -EFFICIENCY CODE'EOR BUILDING CONSTRUCTION{ f <n;
Florida Department Of COu11RUnity Affairs
EuergyGaage FlaCom v1.21 Input Data report
Proiect Data
Proiect Name:' ATLTROFC03
Address: g
Ft. Pierce
State• Florida Zip: 34954
Owner: ATLANTIC TRUSS COMPANY
Building Type: Office (Business) Bmlam Classification: New Finished building
No.of Storevs: 1 Azimuth: 0.00 GrossArea: 4952
Zone Report
Acronym
Description
Type
Load Profile
1 Zol
Zone I
CONDITIONED
Uses Building Load Profile
❑
2 Zo2
Zone 2
CONDITIONED
Uses Building Load Profile
❑
3 Zo3
Zone 3
CONDITIONED
Uses Building Load Profile
❑
4 Zo4
Zone 4
CONDITIONED
Uses Building Load Profile
❑
10/7/03 EnergyGauge FlaCom FLCCSB v1.21 I
Space Report
Description Acronym Depth Width Height Multi Area Volume
ft It It plier SF CF
aces in Zone: Zol
1 Ofc ZolOfc 57.0 14.0 10.0 1.00 798 7980
Offices (Partitions<3.5 ft below ceiling) Open plan offices 900 ft or larger with
partitions higher -
2 Toilets Zo1T1t 10.0 25.2- 10.0 1.00 252 2520
Toilet and Washroom
Spaces in Zone: Z02
1 Office Zo2-Ofc 10.0 87.1 10.0 1.00 871 8710
Offices (Partitions<3.5 ft below ceiling) Open plan offices 900 ft or larger with
partitions higher
2 Storage Zo2-Sto 10.0 26.6 10.0 1.00 266 2660
Storage & Warehouse - Inactive Storage
aces in Zone:
Zo3
1 Offices
Zo3-Ofc 15.0 52.0 10.0 1.00 780 7800
Offices (Partitions<3.5 ft below ceiling) Open plan offices 900 ft or larger with
partitions higher
2 Storage
Zo3-Sto 15.0 10.0 10.0 1.00 150 1500
Storage & Warehouse - Inactive Storage
3 Corridors
Zo3-Corr 68.3 10.0 10.0 1.00 683 6830
Corridor
Spaces in Zone: Zo4
1 Offices Zo4-Ofc 10.0 99.1 10.0 1.00 991 9910
Offices (Partitions<3.5 ft below ceiling) Open plan offices 900 ft or larger with
partitions higher
2 Toilets Zo4-Tlt 23.0 7.0 10.0 1.00 161 1610
Toilet and Washroom
10/7/03 EnergyGauge FlaCom FLCCSB v1.21 2
Lighting Report
No Type
Power
Control Type
No.of
W
Ctrl pts
Lights in Zone: Zol
Lights in Space
ZolOfc
1 4
1260
ManualOn/Off
4
Lights in Space
ZO1TIt
1 9
140
ManualOn/Off
2
Lights in Zone: Zo2
Lights in Space
Zo2-Ofc
1 4
1680
ManualOn/Off
3
Lights in Space
Zo2-Sto
1 4
210
ManualOn/Off
2
Lights in Zone: Zo3
Lights in Space
Zo3-Ofc
1 4
1560
ManualOn/Off
3
Lights in Space
Zo3-Sto
1 4
140
ManualOn/Off
2
Lights in Space
Zo3-Corr
1 4
1100
ManualOn/Off
2
Lights in Zone: Zo4
Lights in Space
Zoo-Ofe
1 4
1610
ManualOn/Off
5
Lights in Space
Zoo-Tlt
1 9
210
ManualOn/Off
2
Wall Report
Wall Description
Width H (Effec)
Multi
Area Azimut
ft ft
plier
sf It
Walls in Zone: Zol
1 CBS+R3
14.00 11.17
1.00
156.38
0
cont...
2 CBS+R3
75.00 11.17
1.00
837.75
90
cont...
Walls in Zone: Zo2
1 CBS+R3
25.00 11.17
1.00
279.25
90
cont..
2 CBS+R3
50.00 11.17
1.00
558.50
180
cant..
3 CBS+R3
21.00 11.17
1.00
234.57
270
cant..
Walls in Zone: Zo3
1 CBS+R3
13.00 11.17
1.00
145.21
0
cont..
Walls in Zone: Zo4
1 CBS+R3
87.00 11.17
1.00
971.79
270
cont..
2 CBS+R3
23.00 11.17
1.00
256.91
0
cont..
10/7/03 EnergyGauge FlaCom FLCCSB v1.21
Wall Report Cont.........
Wall
Description
Type
Cond.
Dens.
Sp Heat
R
Btu/lu. Sf. F Ib/cr
Btu/Ib. F h.sLFBtu
Walls in Zone:
I CBS+R3
Zol
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
0.20
4.9
2
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
0.20
4.9 ❑
Walls in Zone:
Zo2
1 -
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5"
0.20
4.9 ❑
2
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
0.20
4.9
3
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
0.20
4.9 ❑
Walls in.
Zone:
Zo3
1
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
0.20
4.9
Walls in Zone:
Zo4
1
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
0.20
4.9 ❑
2
CBS+R3
Stucco/8"CMU/R3insul/GypBd
0.20
60.5
,, 0.20
4.9
Window Report
Zone
Wall Window Description
Type
Men
(Btu/hr Sf F)
1
1
1
North -A
Window
1.00
cont...
1
2
1
East -A
Window2
1.00
coat...
1
2
2
East-B
Window
1.00
cant...
1
2
3
East-Al/GI Door
Window 2
1.00
cont...
2
1
1
AL/GI Door
Window 2
1.00
cant...
2
2
1
South-B
Window 2
1.00
cant...
2
3
1
West -A
Window 2
1.00
cont...
4
1
1
West -A
Window 2
1.00
cont...
4
1
2
West-AI/GI Doors
Window 2
1.00
cons...
4
2
1
North -A
Window
1.00
cont...
10/7/03 EnergyGauge FlaCom FLCCSB vl.21
Window Report Cont....
Zone Wall Wind
Shaded SC
Vis.Tr
W
H (Effec Multi
Area
Total Area
(Y/N)
(ftl
(ft) plier
(Sf)
(St)
CHI
I 1 1
True
1.0
1.0
4.0
6.0 1.00
20.19
20.19
1 2 1
True
1.0
1.0
4.0
6.0 1.00
20.19
20.19
1 2 2
True
1.0
1.0
4.0
2.0 1.00
8.59
8.59
1 2 3
True
1.0
1.0
2.0
6.0 1.00
15.00
15.00
2 1 I
True
1.0
1.0
2.0
6.0 1,00
15.00
15.00
2 2 1
True
1.0
1.0
4.0
2.0 6.00
8.59
51.53
2 3 I
True
1.0
1.0
4.0
6.0 1.00
20.19
20.19
❑
4 1 1
True
1.0
1.0
4.0
6.0 5.00
20.19
100.93
❑
4 1 2
True
1.0
1.0
5.0
6.0 1.00
30.00
30.00
❑
4 2 1
True
1.0
1.0
4.0
6.0 1.00
20.19
20.19
❑
Door Report
Door Description
Shaded
Width H (Effec) Multi
Area
?
it
ft plier
sf
Doors in Zone: Zol
Doors in Wall:
Zol-Ea
1.00 Al -GI Door
False
3.00
2.00 1.00
6.00
Doors in Zone: Zo2
Doors in Wall:
Zo2-Ea
1.00 Fast-Al/GI Door
False
3.00
2.00 1.00
6.00
Doors in Zone: Zo4
Doors in Wall:
Zo4-We
1.00 AUGI Doors
False
6.00
2.00 1.00 12.00
10/7/03 EnergyGauge FlaCom FLCCSB v1.21
Door Report Cont....
Wall Type
Cond.
Dens. Sp Heat
R
Btu/hr. SE F lb/cf Btu/Ib. F
h.sf.F/Btu
Doors in Zone: Zol
Doors in Wall: Zol-Ea
1.00 Aluminum door, 1.25 in. polystyrene
0.19
43.67 0.11
5.21 [
Doors in Zone: Zo2
Doors in Wall: Zo2-Ea
1.00 Aluminum door, 1.25 in. polystyrene
0.19
43.67 0.11
5.21 [
Doors in Zone: Zo4
Doors in Wall: Zo4-We
1.00 Aluminum door, 1.25 in. polystyrene
0.19
43.67 0.11 5.21 [
Roof Report
Roof Description Width
H (Effec)
Multi
Area
Tilt
ft
ft
plier
sf
deg
Roofs in Zone: Zol
1 MtVAttic/R19/Acous 14.00
75.00
1.00
1,050.00
0.00 Cont
Roofs in Zone: Zo2
1 Mtl/Attic/R19/Acous 50.00
22.74
1.00
1,137.00
0.00 cont
Roofs in Zone: Zo3
1 M1VAttic/RI9/Acous 161.30
10.00
1.00
1,613.00
0.00 cont.
Roofs in Zone: Zo4
1 Mtl/Attic/R19/Acous 115.20
10.00
1.00
1,152.00
0.00 cont.
Roof Report Cont........
Roof Description Type
Cond.
Dens. Sp Heat
R
Btu/hr.
SE F Ib/cf Btu/1b. F
h.sf.FBtu
Roofs in Zone: Zol
1.00 Mtl/AUic/RI9/ ShngVI/2"WD Deck/WD Truss/6'Batt/
0.05
10.89 0.22
21.24
Roofs in Zone: Zo2
1.00 MtVAttic/RI9/ ShngVl/2"WD Deck/WD Truss/6'Batt/
0.05
10.89 0.22
21.24
Roofs in Zone: Z03
1.00 MtVAttic/RI9/ ShngVl/2"WD Deck/WD Truss/6'Batt/
0.05
10.89 0.22
21.24
Roofs in Zone: Zo4
1.00 MtVAttic/R19/ Shngl/1/2"WD Deck/WD Truss/6'Batt(
0.05
10.89 0.22
21.24
10/7/03 EnergyGauge FlaCom FLCCSB v1.21
Skylight Report_
Zone Roof Sky Description
Type
UCen Shading
(BhDbr Sf Coeff
cont..
Skylight Report Cant.....
Zone Roof Skyli Vis.Tra
W H (Effec Multiplier
Area
Total Area CHK
ght
(ftl (ftl
(SO
(SO
El
FloorReport
Floor Description
Width
H (Effec)
Multi Area
ft
ft
plier sf
Floors in Zone: Zol
1.00 Slab on Grade
14.00
75.00
1.00 1,050.00
Floors in Zone: Zo2
1.00 Slab on Grade
50.00
22.74
1.00 1,137.00
Floors in Zone: Zo3
1.00 Slab on Grade
161.30
10.00
1.00 1,613.00
Floors in Zone: Zo4
1.00 Slab on Grade
115.20
10.00
1.00 1,152.00
Plant Report
Equipment
Category Incl. Size
Inst.N Eft IPLV CHK
Water Heater Report
W-Heater Description
Cap Cap.Uni UP Rt. I/P Rt.Uni' EM
EffUni Loss LossUnt CHK
1 Storage WaterHeater- Electric
40.00 1 4.50 1 1.00
1 0.12 1 ❑
10/7/03 EnergyGauge FlaCom FLCCSB v1.21
Ext-Lighting Report
Description Categories. Area Wattag CHK
(Si) (kW)
10MO3 EnergyGauge FlaCom FLCCSB v1.21 8