CHECKLIST SUMMARY
L*22120274*PLAN.BL
BUILDING DIVISION CHECKLIST
STATUS DATE
OP ID DESCRIPTION / COMMENTS
NO 12/31 02
BLD34 3. Building Department Review Complete
///Q/
COMMENT
12/31/02
aeo6
✓1-WINDOWS IN INFANT CLASSROOM 1, 4 AND 5 DO NOT MEET
766—
7
,EGRESS REQUIREMENTS.
2-NEED 2ND MEANS OF EGRESS IN CLASSROOMS 2, 3 AND 4.
,/3-NEED TO FIRE RATE ALL CORRIDORS.
-/4-NEED TO HAVE RATED DOORS IN ALL CORRIDORS.
WAITING FOR MECH., ELECTRICAL AND PLUMBING REVIEWS.
,/5-LOAD CALCS. COMPUTE LOAD AT 415.68 AMPS PROTECTED BY
320 AMP MAIN C.B.-NOT ACCEPTABLE.
1/6-CONDUIT SIZE TO PANEL TOO SMALL.
L/7-11NEW" 200 AMP 3 PHASE PANEL NOT ACCEPTABLE FOR 416
,AMP LOAD.
8-IF SUB PANEL FED FROM EXISTING 800 AMP MAIN, THEN
PROVIDE EXISTING LOAD -SEE #9.
'
'-/9-IF SUB PANEL NOT FED FROM 800 AMP EXISTING C.B. THEN
PROVIDE MORE INFO.
.
L,/10-PROVIDE SERVICE RISER DIAGRAM WITH WIRE SIZES,
SIZES AND ALL SERVICE INFO.
,CONDUIT
11-PROVIDE ALL INFO FOR DISCONNECTS AT AHU, A/C COMP
AND WATER HEATER.
t/12-PROVIDE PRODUCT INFO FOR LIGHTING, SWITCHES AND
OUTLETS.
L�/13-PROVIDE "SEALING" INFO FOR ANY ELECTRIC PENETRATIONS
71HRU FIREWALLS.
4-SPECIFY TYPES OF CONDUITS TO BE USED FOR SERVICE AND
BRANCH CURCUITS. (EMT/PVC/AC CABLE).
15-SSPECIFY WIRE "TYPES" (THHN/THWN) OR OTHER FOR
ELECTRIC.
16-PROVIDE FAULT CURRENT RATING FOR MAIN C.B.-FPL FAULT
CURRENT RATING ALSO NEEDED.
T.G.