Loading...
HomeMy WebLinkAboutChecklistST. LUCIE COUNTY CHECKLIST SUMMARY L*22120274*PLAN.BL BUILDING DIVISION CHECKLIST STATUS DATE OP ID DESCRIPTION / COMMENTS NO 12/31 02 BLD34 3. Building Department Review Complete ///Q/ COMMENT 12/31/02 aeo6 ✓1-WINDOWS IN INFANT CLASSROOM 1, 4 AND 5 DO NOT MEET 766— 7 ,EGRESS REQUIREMENTS. 2-NEED 2ND MEANS OF EGRESS IN CLASSROOMS 2, 3 AND 4. ,/3-NEED TO FIRE RATE ALL CORRIDORS. -/4-NEED TO HAVE RATED DOORS IN ALL CORRIDORS. WAITING FOR MECH., ELECTRICAL AND PLUMBING REVIEWS. ,/5-LOAD CALCS. COMPUTE LOAD AT 415.68 AMPS PROTECTED BY 320 AMP MAIN C.B.-NOT ACCEPTABLE. 1/6-CONDUIT SIZE TO PANEL TOO SMALL. L/7-11NEW" 200 AMP 3 PHASE PANEL NOT ACCEPTABLE FOR 416 ,AMP LOAD. 8-IF SUB PANEL FED FROM EXISTING 800 AMP MAIN, THEN PROVIDE EXISTING LOAD -SEE #9. ' '-/9-IF SUB PANEL NOT FED FROM 800 AMP EXISTING C.B. THEN PROVIDE MORE INFO. . L,/10-PROVIDE SERVICE RISER DIAGRAM WITH WIRE SIZES, SIZES AND ALL SERVICE INFO. ,CONDUIT 11-PROVIDE ALL INFO FOR DISCONNECTS AT AHU, A/C COMP AND WATER HEATER. t/12-PROVIDE PRODUCT INFO FOR LIGHTING, SWITCHES AND OUTLETS. L�/13-PROVIDE "SEALING" INFO FOR ANY ELECTRIC PENETRATIONS 71HRU FIREWALLS. 4-SPECIFY TYPES OF CONDUITS TO BE USED FOR SERVICE AND BRANCH CURCUITS. (EMT/PVC/AC CABLE). 15-SSPECIFY WIRE "TYPES" (THHN/THWN) OR OTHER FOR ELECTRIC. 16-PROVIDE FAULT CURRENT RATING FOR MAIN C.B.-FPL FAULT CURRENT RATING ALSO NEEDED. T.G.