Loading...
HomeMy WebLinkAbout204252-1d Compaction signedHeadquarters 11345 U.S. Highway 1 Sebastian, FL. 32958 Orlando 723 Progress Way Sanford, FL. 32771 Mailing PO Box 78-1377 Sebastian, FL. 32978 Phone: 772-589-0712 C.A.# 5693 KSMengineering.net DATE TESTED:KSM JOB #:204252-1d/CF/jo PERMIT #:NUC #234 CONTRACTOR:Wynne Development Nuc Model:MC-DR JOB LOCATION:14477 Azucena Court Nuc Serial #:MD60308234 Spanish Lakes Fairways Fort Pierce, Florida ITEM TESTED:Compacted Foundation Fill TEST LOCATION OF SAMPLE DEPTH PEN READ DRY DENSITY MAX. DRY PROCTOR VALUE (P.C.F) PERCENT COMPACTION 1. S.E.0" - 12"40+108.4 112.9 96.0% 2. S.W.""107.8 "95.5% 3. Center ""109.1 "96.6% 4. N.W.""108.2 "95.8% 5. N.E.""108.0 "95.7% 101.1 0.9 Soil Description: Brown Clayed Sand In Place Moisture: 6.2% Proctor Optimum Moisture: 11.0% Proctor Max. Dry Density: P.C.F. 112.9 @ Test Locations the Density & Penetrometer readings indicate the Degree of Compaction Meets Minimum Requirement for Staked Foundation Respectfully Submitted: Julie E. Keller, P.E. President PE # 68366 9/3/2020 Email to: St Lucie Building Department Disclaimer:Contractor is responsible to maintain the tested area in the condition that KSM completed the indicated passed compaction test. KSM is not responsible if the tested area has been altered from the approved inspected condition. Proudly Serving Florida since 1990 SOIL COMPACTION REPORT ASTM D 1557 and ASTM D 6938 September 2, 2020 2005-0393 109.0 110.0 111.0 112.0 113.0 114.0 8 9 10 11 12 13 14 15 W E I G H T P . C . F . D R Y Moisture -% of Dry Weight