HomeMy WebLinkAboutStructural Construction PlansALTAMIRA LOCATION MAP NOT TO SCALE GENERAL NOTES: CODES AND STANDARDS 1. THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES: 1.1. FLORIDA BUILDING CODE 2017, FBC EXISTING 2017, ASCE 7-10, ASD, RISC, & CITY OF MIAMI BEACH CODE OF ORDINANCES. 2. DIMENSIONS 2.1. BEFORE ORDERING ANY MATERIALS OR DOING ANY WORK, THE CONTRACTOR SHALL VERIFY ALL MEASUREMENTS TO PROPERLY SIZE OR FIT THE WORK. NO EXTRA CHARGE OR COMPENSATION WILL BE ALLOWED BY THE OWNER RESULTING FROM THE CONTRACTOR'S FAILURE TO COMPLY WITH THIS REQUIREMENT. u 2.2. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER BEFORE PROCEEDING WITH ANY WORK. F �# DIMENSION NOTES: 1. UNLESS SPECIFICALLY DETAILED ON THESE DRAWINGS, CONTRACTOR SHALL FURNISH AND INSTALL ADEQUATE SHORING BRACING AS REQUIRED DURING DEMO, ETC. REQUIRED TO SAFELY SUPPORT ALL CONSTRUCTION LOADS AND SHALL BE FULLY RESPONSIBLE FOR THE SAME. SHORING MUST COMPLY WITH ALL LOCAL AND OSHA REQUIREMENTS. 2. DETAILS AND CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE CONSTRUCTED IN ACCORDANCE WITH DETAILS SHOWN FOR SIMILAR CONDITIONS AND MATERIAL. STRUCTURAL DESIGN CRITERIA: MEAN ROOF HEIGHT 125 OCCUPANCY TYPE RESIDENTIAL — R2 CONSTRUCTION TYPE IIA WIND LOAD CHAPTERS 1, 2, 26, & 28 OF ASCE 7-10 WIND VELOCITY 165 MPH; ULTIMATE WIND SPEED WIND VELOCITY 128 MPH; NOMINAL WIND SPEED EXPOSURE "D"; ENCLOSED DESIGN Qz 52.96 PSF Kz 1.49 ROOF SLOPE FLAT LOAD COMBINATIONS ASCE 7-10 CHAPTER 2.4: DL+LL; DL+0.6WL; 0.6DL+0.6WL INTERNAL PRESSURE COEFFICIENT +/-0.18 PER TABLE 26.11-1 RISK CATEGORY II DEFLECTION CRITERIA: LIVE = L/360 DEAD + LIVE = L/240 MAIN FRAME: MAX. HORIZONTAL LOAD +71 PSF MAX. VERTICAL LOAD —70 PSF r� CONCRETE EDGE REPAIR DEMO AND INSTALLATION: 1. PRIOR TO INSTALLATIONTHE CONTRACTOR WILL VERIFY ALL DIMENSIONS. THE CONTRACTOR UNDERSTANDS THAT THE EXISTING BUILDING WILL REQUIRE MODIFICATION AS SHOWN IN THE DRAWINGS. 2. THE CONTRACTOR IS TO COMPLETELY REMOVE AND DISPOSE OF ALL MATERIALS THAT ARE SO INDICATED INCLUDING WOOD, DRYWALL, AND CONCRETE. 3. THE LOCATION OF ALL EXISTING UTILITIES ARE THE CONTRACTOR'S RESPONSIBILITY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR EXACT LOCATIONS. PRIOR TO THE START OF DEMOUTION'THE CONTRACTOR SHALL VISIT THE SITE AND DETERMINE THE LOCATION AND THE EXISTENCE OF ALL STRUCTURES AND UTILITIES SHOWN OR NOT ON THE PLANS. BUILDING EXIS ING NOTES: 1. THE CONTRACTO SHALL VISIT THE SITE PRIOR TO BID AND BE AWARE OF ALL EXISTING CONDITIONS AND INTERFERENCES.' 2. THE CONTRACTOR SHALL CHECK CONDITION FOR EXISTING WIRING INSULATION AND NOTIFY THE OWNER, ARCHITECT, OR ENGINEER OF ANY DANGEROUS CONDITIONS. 3. THE CONTRACTOR IS TO COMPLETELY REMOVE AND DISPOSE OF ALL ITEMS AND THAT ARE SO INDICATED ON THE PLANS WITH THE OWNERS APPROVAL. 4. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR HAVING VISITED THE SITE AND HAVING FAMILIARIZED HIMSELF WITH ALL EXISTING CONDITIONS. ANY QUESTIONS OR DISCREPANCIES FOUND WITH REGARD TO THE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING ENGINEER BEFORE SUBMITTING A PROPOSAL. FIELD MEASURE EXISTING CONDITIONS PRIOR TO FABRICATION OF ALL MATERIALS. 5. ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE DRAWINGS SHALL BE FIELD VERIFIED BY THE CONTRACTOR/INSTALLER. 6. IF MATERIALS, QUANTITIES, STRENGTHS OR SIZES INDICATED BY THE DRAWINGS OR SPECIFICATIONS ARE NOT IN AGREEMENT WITH THESE NOTES, THE BETTER QUALITY AND/OR GREATER QUANTITY, STRENGTH OR SIZE. INDICATED, SPECIFIED OR NOTED SHALL BE PROVIDED AND APPROVED BY EOR. BUILDING ELEVATION NOT TO SCALE REVIEWED FOR CODE COV ST. LUCIE Wu vi o BOCC SCOPE OF WORK: FILE COPY 1. MOBILIZE 2. REMOVE STUCCO TO EXPOSE BARE CONCRETE FOR ENGINEER TO INSPECT 3. REPAIR EDGE OF FLAT PLATE SLAB PER PLANS 4. REMOVE, STORE, AND RE -INSTALL WINDOW AS REQUIRED 5. APPLY STUCCO, PRIME, &;PAINT TO REPAIRED AREA; OWNER TO SELECT COLOR 6. CLEAN SITE & DEMOBILIZE STRUCTURAL CONSTRUCTION PLANS SHEET DESCRIPTION S-1 COVER SHEET, MAP, AND NOTES S-1.1 GENERAL REPAIR NOTES S-2 UNIT 201 SOUTH PLAN VIEW S-3 CONCRETE REPAIR DETAILS 4310 N HWY A1A a; FORT PIERCE, FLORIDA 34949 n I sm�T_ EN G I N E E k LNG CIVIL • STRUCTURAL w MARINE CSM ENGINEERING, LLC 208 SW OCEAN BOULEVARD STUART, FLORIDA 34994 o: 772-220-4601 w: www.CSM—E.net CERTIFICATE OF AUTHORIZA11ON: 29057 THE ENGINEER HEREBY EXPRESSLY RESERVES HIS/HER COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED, CHANGED, COPIED, OR ASSIGNED TO ANY THIRD PARTY IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS WRITTEN PERMISSION AND CONSENT OF CSM ENGINEERING, I.I.C. THIS DOCUMENT, THE IDEAS, AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS PROPERTY OF CSM ENGINEERING, LLC AND IS NOT TO BE USED, IN WHOLE OR IN PART FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CSM ENGINEERING, LLC. f "tiM ENGINEERING, LLC COPYRIGHT 02020 h IG H II h N N k� N it N n a PERMIT SET: 8-7-2020 NOTES & COMMENTS ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL DIMENSIONS. ALL SCALES INDICATED PERTAIN TO 24X36" PLOTS 1 2 3 4 5 DESIGNED BY: CHARLES DARDEN DRAWN BY: CHECKED BY., CHARLES DARDEN SCALE: AS SHOWN PROJECT f. ``"TiTITJrit�� 1 IN���' 4'iglt%igned by `k._ h a r � �p , IOW1es N4:_Darden Dar ✓ 004'00' ,F. f r NAT 4 �� - -a CHARLES A DARDEN JR DATE FLORIDA REGISTERED PROFESSIONAL ENGINEER NO, 76910 SHEEP NAME COVER SHEET, MAP, AND NOTES SHEET J: S-1 r GENERAL NOTES: MIXING AND CONVEYANCE 1. ALL CONSTRUCTION SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA 1. READY —MIXED CONCRETE SHALL BE MIXED IN ACCORDANCE WITH ACI 304 j BUILDING CODE & EXISTING FBC 2017; 6TH EDITION AND ASCE 7-10. AND DELIVERED IN ACCORDANCE WITH ASTM C94. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON SITE BEFORE SELECT PROPORTIONS FOR NORMAL WEIGHT CONCRETE IN ACCORDANCE CONSTRUCTION HAS BEGUN. ALL OBSERVED DISCREPANCIES SHALL BE REPORTED WITH ACI 301. — ,' IMMEDIATELY TO THE ENGINEER. CONCRETE SHALL BE CONVEYED FROM MIXER TO PLACE OF FINAL 3. DESIGN LOADS: DEPOSIT BY METHODS THAT WILL PREVENT SEPARATION OR LOSS OF MATERIAL. ALL LOADS ARE EXISTING TO REMAIN; NO NEW 'LOADING ONLY REPAIRS. u 21. CONVEYING EQUIPMENT SHALL BE CAPABLE OF PROVIDING A SUPPLY OF CONCRETE AT THE SITE OF PLACEMENT WITHOUT SEPARATION OF INGREDIENTS AND WITHOUT INTERRUPTIONS SUFFICIENT TO PERMIT LOSS 4. CONCRETE: ALL REINFORCED CONCRETE WORK SHALL BE DONE IN ACCORDANCE i OF PLASTICITY BETWEEN SUCCESSIVE INCREMENTS. WITH ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", I AND ACI 301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE 5. DURING HOT WEATHER, PROPER ATTENTION SHALL BE. GIVEN TO FOR BUILDINGS". ALL CONCRETE REPAIR WORK SHALL BE IN ACCORDANCE WITH INGREDIENTS, PRODUCTION METHODS, HANDLING, PLACING, PROTECTION ACI "CONCRETE REPAIR MANUAL" LATEST EDITION. AND CURING TO PREVENT EXCESSIVE CONCRETE TEMPERATURES OR ACI 311, "RECOMMENDED PRACTICE FOR CONCRETE INSPECTION". WATER EVAPORATION THAT MAY IMPAIR REQUIRED STRENGTH OR ' ACI 347, RECOMMENDED PRACTICE FOR CONCRETE FORM WORK„ 'I SERVICEABILITY OF THE MEMBER STRUCTURE. ACI 304R, "GUIDE FOR MEASURING, MIXING, AND PLACING CONCRETE". ALL STRENGTHS NOTED BELOW ARE 28—DAY STRENGTHS: CONCRETE REBAR AND REPLACEMENT: POURED —IN —PLACE STRUCTURAL CONCRETE: 5000 PSII EXTERIOR CONCRETE SHALL HAVE 4% MINIMUM ENTRAINED AIR. 1. CONCRETE REPAIRS SHALL BE PROVIDED FOR THOSE AREAS IDENTIFIED WITH SPALLING, DETERIORATION, AND UNACCEPTABLE CONCRETE. t 4a. THE MIX DESIGN SHALL MEET THE FOLLOWING MINIMUM REQUIREMENTS: REMOVE ALL UNSOUND CONCRETE IN THE AREA OF THE DETERIORATION. REMOVAL SHALL BE PERFORMED WITH SMALL POINTED TOOLS RATHER THAN WIDE CHISEL EDGES TO PREVENT MICRO CRACKING AND CONTINUED SPALLING OF CONCRETE WHICH IS TO REMAIN. THE AREA OF CONCRETE TO BE REMOVED SHALL EXTEND ALONG THE LENGTH OF THE REINFORCING, BEYOND THE LIMITS OF THE REINFORCING DETERIORATION A MINIMUM OF 2" INTO SOUND CONCRETE. PROVIDE A Y2" MINIMUM DEPTH SAW -CUT, PERPENDICULAR OR SLIGHTLY UNDERCUT TO THE CONCRETE SURFACE AT THE LIMITS OF THE REPAIR TO 5. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. PREVENT FEATHERING OF THE PATCH MATERIAL. DO NOT CUT ANY TENSION SPLICES: 48 BAR FOR #3, #4, & #5 REINFORCING, EXCEPT AS ACCEPTED BY THE ENGINEER. x 5• REMOVE ALL RUST AND SCALING OF THE REINFORCING THOROUGHLY BY 6. ALL CONNECTIONS EXPOSED TO WEATHER OF STEEL TO STEEL AND STEEL ISAND BLASTING OR WIRE WHEELING. TO MASONRY/CONCRETE, MUST BE STAINLESS STEEL BOLTS. 7. THESE DRAWINGS ARE NOT VALID UNLESS SIGNED AND SEALED WITH AN 6. THOROUGHLY CLEAN THE EXPOSED CONCRETE SURFACE OF ALL TRACES EMBOSSED SEAL OF AN ENGINEER EMPLOYED BY CSM ENGINEERING, LLC OF DIRT, GREASE, OIL, DUST, AND OTHER CONTAMINANTS WHICH MAY ANY CHANGES TO THE DOCUMENTS MUST HAVE THE WRITTENCONSENT OF PREVENT PROPER BONDING OF THE REPAIR MATERIALS. CSM ENGINEERING, LLC. ALL ORIGINAL DRAWINGS, TRACINGS, AND " - SPECIFICATIONS MUST BE RETAINED IN THE OFFICES OF CSM F =�1 THE PREPARED CONCRETE SURFACE* SATURVfiED SURFACE DRY � ENGINEERING, LLC AND ARE -THE SOLE PROPE ENG�INEERIN (SSD), BUT FREE OF STANDING WATER. APPLY A BOND. COAT OF SLURRY; t , LLC. PREPARED WITHTHEREPAIR CONCRETE, WITH A STIFF BRISTLE BRUSH � COVERI''NG ALL 'EXPOSED STEEL AND ALL CONCRETE SURFACE AREAS. 8. CSM ENGINEERING, LLC. SHALL BE AFFORDED THE OPPORT 0 PROVIDE CONSTRUCTION OBSERVATION SERVICES DURING " HE CONCRETE 8. WHILE SCRUB COAT IS STILL WET, PLACE REPAIR CONCRETE MIX DESIGN RESTORATIONS AND REPAIR WORK OF THE STRUCTURAL RETAINING WALL. IN ACCORDANCE WITH ACI 301 IN A CONTINUOUS POUR. IN THE EVENT THAT CSM ENGINEERING, LLC. IS NOT RETAINED IN THIS CAPACITY, CSM ENGINEERING, LLC. CAN ASSUME NO RESPONSIBILITY FOR I PERFORM REPAIRS IN ACCORDANCE WITH ICRI GUIDELINE 03730, GUIDE THE CONSTRUCTION DEFECTS FOR THE RECOMMENDATIONS PROVIDED IN THESE FOR SURFACE PREPARATION FOR THE REPAIR OF DETERIORATED DOCUMENTS. CONCRETE RESULTING FROM REINFORCING STEEL CORROSION. 9. ENGINEER SHALL BE NOTIFIED A MINIMUM OF 24 HOURS PRIOR TO ALL OBSERVATIONS. CURING OF CONCRETE: TYPICAL CONCRETE REPAIR "AQUA 1. ALL REPAIR. AREAS SHALL RECEIVE AN APPLICATION OF BURKE 1. CONCRETE SHALL BE REMOVED USING A 15# CHIPPING HAMMER. RESIN" MEMBRANE CURING COMPOUND AFTER FINISHING IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND 2. WHERE REINFORCEMENT IS EXPOSED BY CONCRETE REMOVAL, EXTRA CAUTION SHALL BE RECOMMENDATIONS OR APPROVED EQUAL. EXERCISED TO AVOID DAMAGING DURING REMOVAL OF ADDITIONAL UNSOUND CONCRETE. ?. ALL CONCRETE SHALL CURE A MINIMUM OF 28 DAYS PRIOR TO 3. IF RUST IS PRESENT ON REINFORCEMENT, ADDITIONAL CONCRETE SHALL BE REMOVED UNTIL APPLICATION OF ANY COATINGS OR FINISHES. CLEAN, SOUND REINFORCEMENT AND CONCRETE IS FOUND AND COVERED WITH "SIKADUR 110, ARMATEK" OR "THOROC ZINC -RICH PRIMER". THIS WILL ONLY BE DONE AT THE ENGINEERS 3. AN OBSERVATION SHALL BE CONDUCTED BY THE ENGINEER PRIOR TO DIRECTION. APPLICATION OF ANY COATINGS ON THE CONCRETE. ANY CRACKS IN THE REPAIR AREAS SHALL BE REPAIRED IN ACCORDANCE WITH THE 4. UPON REMOVAL OF ALL DAMAGED CONCRETE, AND PRIOR TO STARTING REPAIR, A REVIEW BY REQUIREMENTS FOR CRACK REPAIRS. REPAIR OF CRACKS SHALL BE AT THE ENGINEER OF RECORD SHALL BE CONDUCTED. NO ADDITIONAL COST TO THE OWNER. 5. ALL EXPOSED' CONCRETE AND STEEL SHALL BE SAND BLASTED CLEAN OR WIRE WHEELED. A; ZINC ANODE SHOULD BE INSTALLED TO BARE STEEL. THEN A THIN COAT OF PENETRATING EPDXY SEALER SHALL BE APPLIED OVER THE BARE METAL REINFORCEMENT IMMEDIATELY AFTER SAND BLASTING. 6. THE CUT AREA OF THE CONCRETE SHALL BE CLEAN AND IN THE STATE OF "SSD" (SURFACE SATURATED DRY) PRIOR TO COMMENCEMENT OF PATCHING REINFORCING REPLACEMENT: 1. ALL REINFORCING WITH DETERIORATION OF MORE THAN 15% OF THE ORIGINAL BAR DIAMETER, AS DETERMINED BY THE ENGINEER, SHALL BE REPLACED. 2. TO PERMIT LAPPING OF THE NEW REINFORCING STEEL, THE CONCRETE SHALL BE REMOVED ALONG THE LENGTH OF THE REINFORCING, A MINIMUM OF 12" BEYOND THE DETERIORATION INTO SOUND CONCRETE TO PERMIT SPLICING OF THE REINFORCEMENT. 3. AFTER THE REINFORCING HAS BEEN PREPARED, LAP THE NEW REINFORCING' BESIDE THE ENTIRE LENGTH OF THE EXPOSED REINFORCING, SECURE IN PLACE WITH WIRE TIES. 4. FOLLOW ALL OTHER PROCEDURES FOR THE CONCRETE REPAIR AS INDICATED. 5. WHERE THE REMOVAL OF CONCRETE TO ACHIEVE THE REQUIRED LAP LENGTH IS NOT PRACTICAL AS DETERMINED BY THE ENGINEER, BAR DEVELOPMENT CAN BE ACHIEVED BY EMBEDDING THE REINFORCING INTO SOUND 'CONCRETE A MINIMUM OF 9" WITH SIKADUR 35, HMLV, A HIGH STRENGTH EPDXY GROUT. 6. REINFORCING STEEL SHALL BE ASTM A615 GRADE 60 MINIMUM AND BE GALVANIZED OR EPDXY COATED. TYPICAL SPALLED CONCRETE REPAIR 1, THE CONTRACTOR SHALL LOCATE ALL SPALLS BY S❑UNDING THE CONCRETE SURFACES, USING A HAMMER, UPON L❑CATI❑N OF THE LOOSE CONCRETE A DISTINCT HOLLOW SOUND WILL BE HEARD, THESE AREAS SHALL BE MARKED WITH CHALK OR PAINT BY THE ENGINEER, 2, DELAMINATED, SPALLED, AND UNSOUND CONCRETE AREAS SHALL HAVE THEIR MARKED B❑UNDARIES SAW -CUT TO A MINIMUM OF DEPTH OF 1' INT❑ THE CONCRETE SURFACE. ALL EDGES SHALL BE STRAIGHT AND PATCHED AREAS ARE TO BE AS SQUARE AND RECTANGULAR AS P❑SSIBLE. 3, CONCRETE SHALL BE REMOVED USING A 15# CHIPPING HAMMER, 4, WHERE REINF❑RCEMENT IS EXPOSED BY CONCRETE REMOVAL, EXTRA CAUTI❑N SHALL BE EXERCISED TO AV❑ID DAMAGING DURING REMOVAL OF ADDITI❑NAL UNSOUND CONCRETE, 5, IF RUSTIS PRESENT ON REINF❑RCEMENT, ADDITI❑NAL CONCRETE SHALL BE REMOVED UNTIL CLEAN, SOUND REINF❑RCEMENT AND CONCRETE IS FOUND AND COVERED WITH "SIKADUR 110, ARMATEK', 6. UPON REMOVAL OF ALL DAMAGED CONCRETE, AND PRIpR TO" STARTING REPAIR, A REVIEW BY THE ENGINEER OF RECORD SHALL BE CONDUCTED, 7, ALL EXPOSED CONCRETE AND STEEL SHALL BE SAND -BLASTED OR WIRE WHEELED CLEAN, A ZINC ANODE SHOULD BE INSTALLED TO BARE STEEL, THEN A THIN COAT OF PENETRATING EPDXY SEALER SHALL BE APPLIED OVER THE BARE METAL REINF❑RCEMENT IMMEDIATELY AFTER SAND —BLASTING OR WIRE WHEELING. 8, THE CUT AREA OF THE CONCRETE SHALL BE CLEAN AND DRY P7Ii1F TO COMMENCEMENT OF PATCHING, 9, REPAIR FOR SPALLS LESS THAN 1 1/2' IN DEPTH: A) THE CONCRETE SURFACE AREA SHALL BE COATED WITH BONDING OR SIMILAR APPROVED AGENT AND ALLOWED TO COMPLETELY DRY. B) THE SPALLED AREA SHALL THEN BE FILLED WITH 'SIKAT❑P 123' AND FINISHED FLUSH WITH THE EXISTING CONCRETE SURFACE, 10. REPAIR FOR SPALLS GREATER THAN 1 1/2' IN DEPTH: A) THE FINISH CONCRETE SURFACE AREA SHALL BE SCRATCH COATED W/ "SIKAT❑P 123", B) APPLY ANOTHER LAYER OF EPDXY GROUT DIRECTLY OVER THE NEW SURFACE AND FLUSH W/ EXIST. SURFACE. A LTA M I RA I a 4310 N HWY A1A FORT PIERCE, FLORIDA 34949 a � - n �f CIVIL * STRUCTURAL MARINE CSM ENGINEERING, LLC 208 SW OCEAN BOULEVARD STUART, FLORIDA 34994 o: 772-220-4601 w: www.CSM—E.net CERTIFICATE OF AUTHORIZATION: 29057 THE ENGINEER HEREBY EXPRESSLY RESERVES HIS/HER COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED, CHANGED, COPIED, OR ASSIGNED TO ANY THIRD PARTY IN ANY FORM OR MANNER WHATSOEVER WTEHOUT FIRST OBTAINING THE EXPRESS WRITTEN PERMISSION AND CONSENT OF CSM ENGINEERING, LLC. THIS DOCUMENT, THE IDEAS, AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS PROPERTY OF CSM ENGINEERING, LLC AND IS NOT TO BE USED, IN WHOLE OR IN PART FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CSM ENGINEERING, LLC. CSM ENGINEERING, LLC COPYRIGHT 02020 'r. I �I i r i q I NOTES & COMMENTS r ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL DIMENSIONS. ALL SCALES INDICATED PERTAIN TO 24"X36" PLATS r17 4 Lu— — DESIGNED BY: CHARLES DARDEN DRAWN BY: CHECKED BY: CHARLES DARDEN SCALE: AS SHOWN PROJECT: A. DARQ signet \ �' 7bCf �'rI�s A. C h a is �. . "'Dardei-E ®a r � I . JjrA.T 20.0&07 04'00' NAL CHARLES A DARDEN JR`' DATE FLORIDA REGISTERED PROFESSIONAL ENGINEER NO. 76910 SHEET NAME: GENERAL REPAIR NOTES SPED II>.rrca—.�mas: c..av�e FILE COP" CONCRETE EDGE SPALL REINFORCEMENT AT THE EDGE OF THE CONCRETE SLAB NOT TO SCALE HAS CORRODED AND EXPANDED THE CONCRETE CAUSING A SPALL RECOMMEND REMOVING ALL DAMAGED CONCRETE. CHLORIDE CONTAMINATED CONCRETE UNCONTAMINATED CONCRETE GALVANIC ANODE — SACRIFICIALY CORRODES TYPICAL- CORROSION PREVENTION DETAIL GALVASHIELD XP COLUMN REPAIR INSTALLATION NOTES 1. REMOVE DAMAGED CONCRETE AS WITH STANDARD REPAIR METHODS. 2. REPLACE/CLEAN CORRODED REINFORCING STEEL 3. ENSURE ALL EXPOSED STEEL IS SECURELY FASTENED TOGETHER WITH TIE WIRE TO PROVIDE GOOR CONTINUITY 4. ATTACH GALVASHIELD XP ANODES TO CLEAN REINFORCING STEEL AT SPACING OUTLINED IN CONTRACTOR SPECIFICATION. REFER TO GALVASHIED XP DATA SHEET FOR MAXIMUM SPACING GUIDLINES 5. POUR BACK REPAIR AREA WITH MATERIAL AS PER ENGINEER'S SPECIFICATIONS. EXISTING CONCRETE BALCONY EDGE EXISTING CONCRETE LIMITS OF CONCRETE I. REPAIR (TYP.) /21MIN x / �rafi •� 4.. .fit ^1�{ 3O" MIN. >_ EXISTING REBAR TO BE CLEANED PER NOTES ON S-02. IF BAR IS DETERIORATED MORE THAN 15% LEAVE IN PLACE AND ADD MATCHING BAR SPLICE 5-02 AS REQUIRED TRANSVERSE RCLEANED PER NOTES ON TO EXTEND W PAST DETERIORATION. IF BAR IS RED PROVIDE Y2" MIN. CONT. MORE THAN 50% DETERIORATED THEN IT MUST BE SAW CUT TOP & BOT. (TYP.) EXISTING REBAR (TYP.) COMPLETELY REMOVED AND REPLACED WITH #5 BAR AND EPDXY INTO EXISTING CONCRETE MIN. 6" FULL DEPTH SLAB REPAIR CONCRETE OVERHEAD SPALL & CRACK NOT TO SCALE EXISTING CONCRETE HOLLOW CORE PLANK `a I IST RATCH COATED L WITH "SIKA TOP 123 PLUS" OR O PATCH REPAIR MORTAR CR211 ISTING REBAR/TENDON (TYP.) REPAIR IN ACCORDANCE WITH I.C.R.I. GUIDELINE No. 03730 OVERHEAD ',�PAI I Fn rnNrRFTF RFPAIR 1/2" GYPSUM WOOD BOARD PT. WOOD FURRING PT. WOOD BLOCKING PER PLANS' FRAME PER PLANS ILA 'LASHING/SEALANT SHALL EXTEND TO THE SURFACE )F THE EXTERIOR WALL FINISH AND SELF —ADHERED LASHING SHALL COMPLY WITH AAMA 711. SIDING FINISH 8" C.M.U. PER PLANS CONC. FILLED CELL. TYPICAL JAMB FLASHING DETAIL SCALE: N.T.S. INJECT CRACK WITH "SIKADUR 35 HI -MOD LV LPL" AS SPECIFIED DRILL J" DIA. HOLES AND INSTALL PORTS AT 8"O.C. ALONG ENTIRE LENGTH OF CRACK SEAL CRACKS AND SECURE PORTS WITH "SIKA HI -MOD GEL" REINFORCEMENT IN THE CONCRETE SLAB HAS CORRODED AND EXPANDED THE CONCRETE CAUSING A SPALL RECOMMEND REMOVING ALL DAMAGED CONCRETE. VERTICAL CONC CRACK REPAIR POUR NEAT MATERIAL (SIKADUR 32 HI -MOD OR APPROVED EQUAL) INTO PRE VEE-NOTCHED CRACK UNTIL CRACK IS COMPLETELY FILLED, SEAL UNDERSIDE OF SLAB PRIOR TO FILLING IF CRACK REFLECTS THROUGH APPLY CAULK DAM ALONG LENGTH OF CRACK HORIZONTAL GRAVITY CONC CRACK REPAIR NOTE: CHIP OFF LOOSE CONCRETE MECHANICALLY SAND BLAST EXPOSED REBAI OF RUST AND DUST APPLY SCRATCH COAT AND ANTI -CORROSION AGENT OVER CLEAN REBAR AND FILL WITH "SIKA 211" OR "STO PATCH REPAII MORTAR CR311" AND FINISH TO MATCH EXISTING CONIC. SURFACE. REPAIR IN ACCORDANCE WITH I.C.R.I. GUIDELINE No. 03730 SECTION PALL CONC. ING CONIC NOTE SCRATCH COATED rwuiw.wl. MR € ALTAMIHA 4310 N HWY A1A FORT PIERCE, FLORIDA 34949 4 ti s ml .... `ENGINEERING CIVIL STRUCTURAL. + MARINE GSM ENGINEERING, LLC 20B SW OCEAN BOULEVARD STUART, FLORIDA 34994 o: 772-220-4601'' w: www.CSM-E.net' CERTIFlCATE OF MMORIZATION: 29057 THE ENGINEER HEREBY EXPRESSLY RESERVES HIS/HER COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED, CHANGED, COPIED, OR ASSIGNED TO ANY THIRD PARTY IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS WRITTEN PERMISSION AND CONSENT OF CSM ENGINEERING, LLC. THIS DOCUMENT, THE IDEAS, AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS PROPERTY OF CSM ENGINEERING, LLC AND IS NOT TO BE USED, IN WHOLE OR IN PART FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CSM ENGINEERING, LLC. CSM ENGINEERING, LLC COPYRIGHT 02020 r t r, I� y G NOTES & COMMENTS ,._. ALL DIMENSIONS SHALL BE. VERIFIED IN THE FIELD BY THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL DIMENSIONS. ALL SCALES INDICATED PERTAIN TO 24"X36" PLATS 1 2 3 II 4 5 — DESIGNED BY: CHARLES DARDEN DRAWN BY: CHECKED BY: CHARLES DARDEN SCALE; AS SHOWN PROJECT : ,e��•ned by Chadps A'(9:harle*Darden Dar y dte; 2 �0.08.07 %� �.. •.F<ol-04'00' CHARLES A DARDEN JR DATE FLORIDA REGISTERED PROFESSIONAL ENGINEER NO. 76910 SHEET NAME CONCRETE REPAIR DETAILS m ..m..a S-3 i