DATE: 8/8/20
CLIENT: Cardinal Roofin & Si
ADDRESS: 1601 S.E. South Niem
PROJECT: Care Spot Medical Of
ADDRESS: 784 Prima Vista Blvd;
Job Order No.: 2
ircle; Port St. Lucie, FL 34952
Flat Wood Roof Do
St. Lucie. FL 34952
ASCE 7-10 DESIGN PRESSURE CALCULATIONS
In Accordance with Chapter 30, Part I
Project Information: Flat Wood Deck
Height = 23' Exposure: C Ultimate Windspeed: Vait= 170
Length = 55' Category: II Basic Windspeed: Va,d = 132 r,
Width = 38' Slope: < 7° KZ = 0.93 Kd = 0.85
Parapet Wall: < 3'
Design Calculations:
Velocity Pressure: q = 0.00256*[(0.93)(0.85)(1.00)(132)2]
=35.3 psf
Width of Pressure Coefficient:
0.1(3 8') — 3.8'
0.4(23') = 9.2'
use:
3.8'
Effective Wind Tributary Area:
<10ft2
For parapet height 3 feet or larger, zone three (3) can be
treated as zone two (2) (ASCE 7-1
External Pressure Coefficient:
Internal Pressure Coefficient:
1) GCP1 = -1.0
1)
GCPi =
0.18
2) GCP2 = -1.8
3) GCP3 = -2.8
Design Pressures:
Zone 1 Field:
P1 — 35.3*(-1.0 -
0.18) =
-41.6 psf
Zone 2 Perimeter:
P2 = 35.3*(-1.8 -
0.18) =
-69.8 psf
Zone 3 Corners:
P3 — 35.3*(-2.8 -
0.18) =
-105.1 psf
1
AASHTQR.
a is ; �®� f
__.� Ap;rroved Laboratory
one: 954-784-2941
Fax: 954-784-7875
min@fed-eng.com
vw.fed-eng.com
Pederal
13i nginee ring
goesting, Inc.
DATE:
8/8/20
CLIENT:
Cardinal
ADDRESS:
1601 S.1
PROJECT:
Care Sp(
ADDRESS:
784 Prin
Ni
Job Order No.:
St.
ASCE 7-10 DESIGN PRESSURE CALCULATIONS
In Accordance with Chapter 30, Part I
Project Information: Flat Wood Deck
Height = 23'
Length = 55'
Width = 38'
Parapet Wall: < 3'
Design Calculations:
Velocity Pressure:
Exposure: C Ultimate Windspeed: V,,,,= 170
Category: 11 Basic Windspeed: Vasd = 132 r
Slope: < 7° KZ = 0.93 Kd = 0.85
q = 0.00256*[(0.93)(0.85)(1.00)(132)21
=35.3 psf
Width of Pressure Coefficient: 0.1(38') = 3.8'
0.4(23') = 9.2' } use: 3.8'
Effective Wind Tributary Area: <1Oft'
For parapet height 3 feet or larger, zone three (3) can be treated as zone two (2) (ASCE 7�1fi
External Pressure Coefficient: Internal Pressure Coefficient:
1) GCP1 = -1.0 1) GCPi = 0.18
2) GCP2 = -1.8
3) GCP3 = -2.8
Design Pressures:
Zone 1 Field: P1 = 35.3*(-1.0 - 0.18) — -41.6 psf
Zone 2 Perimeter: P2 = 35.3*(-1.8 - 0.18) = -69.8 psf
Zone 3 Comers: P3 = 35.3*(-2.8 - 0.18) — -105.1 psf
�"WTO�t4i� .W$i'1- !�
.-.0p,
MGM
Approved Laboratory
one: 954-784-2941
Fax: 954-784-7875
min@fed-eng.com
vw.fed-eng.com
FD OT
Page 2
8/8/20
Care Spot Medical Office
784 Prima Vista Blvd.
Port St. Lucie, FL
RAS 117 Design Pressure Calculations:
Net Width = 2.95 feet
Net Length = 33.9 feet
Side Lap Row = 33.9 fasteners / square
Center Rows = 67.9 fasteners / square
0.98 ftz / fastener
Fy = 51.6 lbs per fastener
Base Sheet Attachment Requirements:
Based on RAS-117 and F.L. #1654-R19; Table 1F-2; System Type E; System No. W-134. with a design
pressure of -52.5 psf; Appendix l; page 22 of 45, the following are our recommended base sheet fastening
requirements:
Zone 1 Field: 12" o.c. @ laps and 2 staggered rows 12" o.c.
Zone 2 Perimeter: 12" o.c. @ laps and 3 staggered rows 12" o.c.
Zone 3 Corners: 8" o.c. @ laps and 3 staggered rows 8" o.c.
Notes: Corners and perimeter area dimension shall not be less than a = 3.8'
All work shall be in compliance with the local building code product cot 1 notice of
acceptance and manufacturer specifications and Florida Building Code 2017 edition.
Wind load calculations based on ASCE 7-10 and information provided by client.
All work shall be inspected by our field engineer or city inspector to verify compliance
with specifications.
Sincerely,
_Z�el
Keith LeBlanc, F.E.
Federal Engineering & Testing, Inc.
Florida Reg. No. 59394
Certificate of Authorization #5471
Miami -Dade County Certification #18-1105.02
ms'.0.�c' =a FDoT�
�v •� � Appraved taboralary 7 .0 '
Page 2
8/8/20
Care Spot Medical Office
784 Prima Vista Blvd.
Port St. Lucie, FL
RAS 117 Design Pressure Calculations:
Net Width = 2.95 feet
Net Length = 33.9 feet
Side Lap Row = 33.9 fasteners 1 square
Center Rows = 67.9 fasteners / square
0.98 ft2 / fastener
Fy = 51.61bs per fastener
Base Sheet Attachment Requirements:
Based on RAS-117 and F.L. #1654-R19; Table 1F-2; System Type E; System. No. W-13 M�ith a design
pressure of -52.5 psf, Appendix l ; page 22 of 45, the following are our recommended base heet fastening
requirements:
Zone 1 Field: 12" o.c. @ laps and 2 staggered rows 12" o.c.
Zone 2 Perimeter: 12" o.c. @ laps and 3 staggered rows 12" o.c.
Zone 3 Corners: 8" o.c. @ laps and 3 staggered rows 8" o.c.
Notes: Comers and perimeter area dimension shall not be less than a = 3.8'
All work shall be in compliance with the local building code product co trill notice of
acceptance and manufacturer specifications and Florida Building Code 201 edition.
Wind load calculations based on ASCE 7-10 and information provided by client.
All work shall be inspected by our field engineer or city inspector to verify compliance
with specifications.
Sincerely,
Keith LeBlanc, P.E. .;A, �Pr.�
Federal Engineering & Testing, Inc.
Florida Reg. No. 59394