1
®=LIFE SAFETY WARNING
This symbol identifies Life Safety Warnings that should be read
given special attention by all persons installing trusses.
5PAGING NOTE
ALL TRUSSES ARE TO BE SET
AT 2'-0: ON CENTER
EXCEPT AS NOTED
ASTENED TOGETHER PER ENGINEERIN
BEFORE SETTING. REFER TO
ENGINEERING DRAWING TO DETERMINE
A IF MULTIPLE PLY. A
DON'T LIFT TRUSSES
WITH SPANS LONGER THAN
30' BY THE PEAK.
CONSULT BCSI
30' Span or less 30, to 60' Span
so 'degrees Sprea er Bar
or less
r �.___ /2—� a9 4— Approx 2/3 to �
Tag Line span approx. a^p /2 of span
� REFER TO BCSI REFER TO SCSI
Truss must be set this way if crane .used
x Truss must beset this way if crane used.
Truss is on example, your truss may not match: This is on example, truss may not match.
Insist crane operator setstruss -this way. Insist. crane operator sets truss this way:.
%I
r
I
,
AIR HANE=>LIE=R IVOTF=
UNLESS NOTED ELSEWHERE ON THIS LAYOUT, THESE TRUSSES
ARE NOT DESIGNED FOR AIR HANDLERS IN THE ROOF OR FOR
ANY OTHER A/C REQUIREMENTS. THIS MAY BE IN CONFLICT
WITH BUILDING CODE AND A/C DESIGN REQUIREMENTS.
CONSULT WITH BUILDING DEPARTMENT AND A/C CONTRACTOR.
U REPRESENTS A RANGER
Carrying Girder
For Truss to Truss
=
Connections seeThe
hanger/connector
as
in engineeringe
de tabs oschedule
nails.
package.
Carried Truss
s _
•
SEAT PLATES BY CHAMBERS
INDICATES LOAD BEARING WALL
REQUIRED BY TRUSSES
SUPPLIED BY BUILDER
AT A HEIGHT OF 8'-1"
ABOVE FINISHED FLOOR
I
12
4.00 --
CD
co
upset=1/4" heel=315/16
PLUMB CUT END
1'
2 x 4 Top Chord
WALL HEIGHT 8'-1"
r;
I
TYPICAL END DETAIL
12
4.00 F
to
2.00 s-
M
2
upset=l/4" heel=315/16"
1'
PLUMB CUT END
"
2 x 4 Top Chord
WALL HEIGHT 8'-1"
END DETAIL: A
,
ARRANGE VVI �H CRANE OPERATOR IN ADVANCE FOR A SPREADER BAR OF 17'- 23'-1
4k Do not stand o� trusses until they are • -• BCSI & properly nailed
to straps & hangers
H \ -- - J T-4- 1 Q,-R-
GARAGE LEFT
N LENGTH
34'
14'
Tom- 1'-
FABRICATION AGREEMENT
TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED & RETURNED
The legal description of the property where the trusses will be Installed Is:
The underslgned acknowledges and agrees:
1: Trusses. will be made In strict accordance with this truss placement diagram layout,
which 13 the sole authority for deterniningsuccessfut fabrication of the trusses,
2.AN dimensions In this layout have been vedfled by the undersigned.
.3. Unless written notice is provided by certified mall to Chambers Truss within tan (10)
days of delivery the undersigned agrees that no bsckcharges will be allowed. in the event
such written notice Is furnished Chambers Trues shall have three (3) business days in which
to begin repairs required, or to substitute othectrvsses, at Chambers Oiatkin.
4. The undersigned acknowledges recelpt of "SCSI 1.03" summary sheet by'rPI & WTCA.
5. Delivery Is to Job site. It Is the buyers' responsibility to make the job site suitable for
delivery. Chambers Truss has the sole authority to determine the suitability of the Job site or a
portion of the Job she for delivery. Chambers Truss will be responsible for dump delivery only.
The buyer is responsible for additional delivery. expenses If Chambers Truss has to redeliver
because Job site Is not prepared for delivery or buyer is not prepared for delivery of trusses.
Buyer Is responsible to Chambers Truss for towing costs due to she conditions.
5. Price as shown Iq paragraph 7 below Is subject to change If any changes are. made In
this. leyoul. A $50 per hour fee for revisions may be charged by Chambers Truss.
7. This is a PURCHASE ORDER to Chambers,Truss of the sum agreed to, or If nei
agreement a reasonable price. Invoice will be made on derwery and paid within terms of net
on delivery. Invoice may. be made at scheduled date of delivery If buyer cannot accepi,
delivery of fabricated trusses. The undersigned agrees to pay Chambers. Truss reasonable
shomey's fee for collections In event of payment not timely made. 1.12 % per month servJoe
charge will be added for all sums not paid -within terms.
8. Signature or Initials anywhere on this sheet constitutes agreement to all terns heroin.
- 0, In consideration of Chambers Truss extending credit for this material the undersigned
unconditionally guarantees payment when due of any and all indebtedness owed to
Chambers Trues by any entity receiving material and the undersigned agrees to pay such
Indebtedness Including attorneys fees, If default In payment for material be made by the
recipient.-
10, In the event of any litigation conceming this agreement, the hems furnished hereunder
or payments referred to herein, the. parties agree that the sole venue for any such action wlli
be saint Lude County, Florida.
11. Design responsibilities are per "National Standard And Recommended Guidelines On
Responsibilities For Construction Using Metal Plate Connected Wood Trusses
ANSUTPIIWTCA 4-2002 _
DATEp ......
SIGNED
FOR_. TITLE_,
Aspreaderbarmaybe requInid per"BCSI 1-0s"m pfe+entiNury& damage.
Multiple ply trusses must be fastened togithar per engineering
before they are set, failure to do so can result -in roof collapse,
Temporary and permanent bracing are required and can save life
and property and Is the responsibility of the truss erector.
Study the contents of the Information packet Included on delivery
before settings trusses,
7}uestia must be setand braced per design to PWIDIlt injury & damage -
Trusses must be sot plumb and square
Do noteet bunks or stack of plywood, roofing material or any
other concentrated loads on trusses, this can cause collapse.
DO NOT SET TRUSSES USING THIS LAYOUT
USE LAYOUT DELIVERED WITH TRUSSES TO SET TRUSSES
CHAMBERS TRUSS INC
3105 Oleander Avenue
Fort Pierce; Florida 34982-6423
800-551-5932
Fort Pierce 772-465-2012 Fax hh 772.465.8711
Vero Beach 77A-619,1V2t 5 or ArchSt'U `s . r2e286-3a302 s
shop drawing approval is NOT a
�i "double check" of the contractor.
FORThe contractor shall remain responsiblq
LIANCE for checking field measurements and
other construction criteria. Architect's.
�IJNTY approval covers general roof shape,.'(
1Y i review of truss strapping, and loading. on
structurefrom gravity and uplift loads nd
' .their respe locations
Approved By - �I
92.0/93.2 MITEK 4.2 D,
ate.
DESIGN CRITE�i,�Braden A.I.A. P.A.
County SAINT LUCIE
Building Department SAINT LUCIE COUNTY
Wind Design Criteria ASCE 7-2010
Wind Design Method MWFRS/C-C hybrid Wind ASCE 7-10
Roofing Material Shingle or Shake
rLj Loading in PSF Roof R.D.L.
o Top Chord Live 20
Top Chord Dead 7 4.2
wL" Bottom Chord Live 10 Non -Concurrent
Bottom Chord Dead 10 3
to
fn TOTAL Load 37 7.2
o Duration Factor 1.25
M Wind Speed 165mph
to Top Chord C.B. Sheeting by builder.
I--- Bottom Chord C.B. Sheeting by builder.
V, Highest Mean Height 14'-0"
Building Type ENCLOSED
Building Category II:Non Restrictive
Exposure Category C
Barrier Island No
Conforms to FBC 2017
C.
GARAGE RIGHT G'
13 TRUSS (DRAWINGS ARE ATTACHED TO I AYOUIT
i..v.t.—r�cauannrr Ucau LudU tam.=t.onunuous bracing
verify DESIGN CRITERIA shown above with the
building department and your engineer.
Design Criteria is the responsibility of the
Buildinq Desiqner and/or Enaineer of Record_
Chambers Truss Inc. Drawing Name: M11323
Scale: 1/4 = 1'
72 total trusses, 13 different trusses.
MI 4: SAE ACAD: SAE Reviewed By:
Date:04/24/12 Revised:02/21/18
FOR Revised: 3/05/2020
WYNNE BUILDING CORP.
DESCRIPTION:
CARLTON
PAGE 1 of 1 CUSTOMER INITIALS EACH PAGE
M11323
MiTek'
Sol
RE: M11323
M11323,
Site Information::
Customer: WYNNNE`DEVELOPEMENT CORP Project Name
Lot/Block: Model: CARLTON
Address: N/A Subdivision:
City: PORT ST LUCIE State: FL
M11323
MiTek USA, Inc.
6904 Parke East Blvd.
Tampa, FL 33610-4115
General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special
Loading Conditions):
Design Code: FBC2017/TP12014 Design Program: MiTek 20/20 8.1
Wind Code: ASCE 7-10 Wind Speed: 165 mph
Roof Load: 37.0 psf Floor Load: N/A psf
This package includes 13 individual, dated Truss Design Drawings and 0 Additional Drawings.
With my seal affixed to this sheet, I hereby certify that I am the Truss Design Engineer and this index sheet
conforms to 61G15-31.003, section 5 of the Florida Board of Professional Engineers Rules.
No.
Seal#
Truss Name
Date
1
T19884596
A
5/5/2020
2
T19884597
A5
5/5/2020
3
T19884598
A6
5/5/2020
4
T19884599
A7
5/5/2020
5
T19884600
A8
5/5/2020
6
T19884601
A9
5/5/2020
7
T19884602
GRA
5/5/2020
8
T19884603
GRB
5/5/2020
9
T19884604
J2
5/5/2020
10
T19884605
J4
5/5/2020
11
T19884606
J6
5/5/2020
12
T19884607
J8
5/5/2020
13
T19884608
KJ8
5/5/2020
This item has been electronically signed and sealed by Velez, Joaquin using a Digital Signature.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies
The truss drawing(s) referenced above have been prepared by
MiTek USA, Inc under my direct supervision `III111111111
based on the parameters provided by Chambers Truss. ,,��OPC U I N 1/F� �e
Truss Design Engineer's Name: Velez, Joaquin `-.. �.. ** G E N 5�.,� "'..
My license renewal date for the state of Florida is February 28, 2021.
Florida COA: 6634 No 68182
IMPORTANT NOTE: The seal on these truss component designs is a certification
that the engineer named is licensed in the jurisdiction(s) identified and that the
designs comply with ANSIITPI 1. These designs are based upon parameters
shown (e.g., loads, supports, dimensions, shapes and design codes), which were
given to MiTek. Any project specific information included is for MiTek
customers file reference purpose only, and was not taken into account in the preparation of
these designs. MiTek has not independently verified the applicability of the design
parameters or the designs for any particular building. Before use, the building designer
should verify applicability of design parameters and properly incorporate these designs
into the overall building design per ANSI/TPI 1, Chapter 2.
STATE OF .' 4/
1
i�'; I&/ONAl.��.�`,,
111111111I
Joaquin Velez PE No.68182
MITek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610 May 05, 2020
1 of 1 Velez, Joaquin
Job
Truss
Truss Type
City
Ply
M11323
T19884596
M11323
A
COMMON
9
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:27 2020 Page 1
i1--00-0-0 I D:a3B4PavKnnZweXyJckSFBgyuFUN-bAjL909k_1 Hpv5SDpc—PEKrtnVLQuvtwTtLrJWzUUjw
7-124 7 21-7-3 7-43 34-0-0 35g
5-9725-9-0 6-7-13 1-0-0'-7 66-43
�1
6
4.00 12 45 =
27
Scale=1:57.8
17 15 "" "' 14 12
3x6 — 2x3 II 4x6 = 3x8 = 3x8 = 4x6 = 2x3 II 3x6 =
6-7-13 12-4-13 21-7-3 271-3 34-0-0
6-7-13 5-9-0 9-2-7 5-9-0 6-7-13
LOADING (psf)
SPACING-
2-0-0
TCLL
20.0
Plate Grip DOL
1.25
TCDL
7.0
Lumber DOL
1.25
BCLL
0.0
Rep Stress Incr
YES
BCDL
10.0
Code FBC2017frP12014
CSI.
DEFL.
in (loc)
I/deft
Lid
TC 0.39
Vert(LL)
0.3214-15
>999
360
BC 0.58
Vert(CT)
-0.61 14-15
>670
240
WB 0.65
Horc(CT)
0.12 10
n/a
n/a
Matrix -MS
LUMBER- BRACING-
" TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30 BOT CHORD
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Horz 2=-179(LC 8)
Max Uplift 2=-832(LC 10), 10=-832(LC 10)
Max Grav 2=1362(LC 1), 10=1362(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3419/2395, 3-5=-2771/2031, 5-6=-2770/2152, 6-7=-2770/2152, 7-9=-2771/2031,
9-10=-3419/2395
BOT CHORD 2-17=2132/3213, 15-17=-2132/3213, 14-15=-1269/2000, 12-14=-2132/3213,
10-12=-2132/3213
WEBS 6-14=635/983, 7-14=-313/362, 9-14=-689/499, 6-15=-635/983, 5-15=-313/362,
3-15=689/499
PLATES GRIP
MT20 2441190
Weight: 163 lb FT = 0%
Structural wood sheathing directly applied or 3-7-12 oc pudins.
Rigid ceiling directly applied or 4-11-7 oc bracing.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 24-13 to 13-7-3, Extedor(2) 13-7-3
to 20-4-13, Interior(1) 20-4-13 to 31-7-3, Exterior(2) 31-7-3 to 35-0-0 zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
'
This item has been
4) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL=1o.opsf.
electronically signed and
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
sealed by Velez, Joaquin, PE
2=832, 10=832.
using a Digital Signature.
6) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 50 lb down and 47 lb up at
Printed copies of this
15-0-0, and 50 lb down and 47 lb up at 19-0-0 on top chord. The design/selection of such connection device(s) is the responsibility
of others.
document are not considered
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
signed and Sealed and the
signature must be verified
LOAD CASE(S) Standard
on any electronic copies.
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Joaquin Velez PE No.68182
Uniform Loads (plf)
Vert: 1-6=-54, 6-11=-54, 18-21=-20
MiTek USA, Inc. FL Cart6634
Concentrated Loads (lb)
6904 Parke East Blvd. Tampa FL 33610
Vert: 26=-50(F) 27=-50(F) ,
Date:
April 3,2020
AWARNING - verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 111II.7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall�e
building design. Bracing indicated is to prevent buckling of Individual truss web andfor chord members only. Additional temporary and permanent bracing MiTek♦
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP/y Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safelylnfo nnaffon available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
T19884597
M11323
A5
SPECIAL
�Qty
9
1
�M11323
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:28 2020 Page 1
ID:2GIScwwyYShnGhXVARzUkuyuFUM-3MHjMkAMIKQgXE1 PNJV2mXOxRucedNo4iX50ryzUUjv
7-8-5 10-6-4 17-0-0 20-4-8 26-4-0 34-0-0 5-0-
0-0 7-8-5 2-9-15 1 6 5-12 3-4-8 5-11-8 7-8-0 1-0-0
aI1
6
5x8 MT18HS 11
4.00 12
Scale=1:59.8
13 12
3x12 2.00 12
5x12 = 2x3 II 3x6 =
=
10.64 20-4-8 26.4.0 34-0-0
10-6-4 9-10-4 5+11-8 7-8-0
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) I/deft Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.85
Vert(LL) 0.76
14 >539 360
MT20
244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.90
Vert(CT) -1.18
13-14 >344 240
MT18HS
244/190
BCLL 0.0
Rep Stress Incr
YES
WB 0.60
Horz(CT) 0.36
10 n/a n/a
BCDL 10.0
Code FBC20171TPI2014
Matrix -MS
Weight: 155 lb
FT = 0%
LUMBER-
BRACING-
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 1-7-8 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 3-9-12 oc bracing.
WEBS 2x4 SP No.3
*Except*
WEBS
1 Row at midpt 6-14
6-14: 2x4 SP
M 30
OTHERS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Horz 2=-179(LC 8)
Max Uplift 2=-803(LC 10), 10=-803(LC 10)
Max Grav 2=1312(LC 1), 10=1312(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-5529/3776, 3-5=-5164/3538, 5-6=-5209/3667, 6-7=-2424/1902, 7-9=-2462/1813,
9-1 0=-3195/221 0
BOT CHORD'2-14=-3466/5266,13-14=-1305/2115,12-13=-1948/2995,10-12=-1948/2995
WEBS 3-14=-355/314, 5-14=-293/354,6-14=-2175/3326,6-13=-279/534, 7-13=-237/277,
9-13=786/560,9-12=0/269
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 13-7-3, Extedor(2) 13-7-3
to 20-6-4, Interior(1) 20-64 to 31-7-3, Exterior(2) 31-7-3 to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown;
Lumber DOL=1.60 plate grip DOL=1.60
3) All plates are MT20 plates unless otherwise indicated.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Bearing at joint(s) 2 considers parallel to grain value using ANSI/rP1 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
2=803, 10=803.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 11111.7473 rev. f010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design into the overall r
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing M iTek-
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
city
Ply
M11323
'
T19884598
M11323
A6
SPECIAL
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8,240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:29 2020 Page 1
I D:2GIScwwyY5hnG hXVARzUkuyuFU M-YYr6a4B_WeYX90cbw00HJlx7i IyPMm6DxBgy00zU Uju
1-0-0 8-11-11 16-0-0 18-0-0 20-4 8 25-11-15 34-0-0 5 0
100 8-11-11 7-0-5 2-M 2-4-8 5.7-7 8-0-1 0-0
4.00 12
T
6
3x12 = 2.00 12
LOADING (psf)
SPACING-
2-0-0
TCLL
20.0
Plate Grip DOL
1.25
TCDL
7.0
Lumber DOL
1.25
BCLL
0.0
Rep Stress Incr
YES
BCDL
10.0
Code FBC20171TPI2014
LUMBER-
' TOP CHORD 2x4 SP M 30 'Except'
3-5,6-7: 2x4 SP M 31
BOT CHORD 2x4 SP M 30
WEBS
2x4 SP No.3 *Except*
5-14: 2x4 SP M 30
OTHERS
2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0
Max Horz 2=-169(LC 8)
Max Uplift 2=-803(LC 10), 9=-803(LC 10)
Max Grav 2=1312(LC 1), 9=1312(LC 1)
6x10 MT18HS =
5x6 =
5x6 =
25.11-15
3x6 =
Scale = 1:61.9
CSI.
DEFL. in (loc) I/deft Ud
PLATES GRIP
TC 0.81
Vert(LL) 0.69 14 >590 360
MT20 244/190
BC 0.93
Vert(CT) -0.9214-17 >443 240
MT18HS 244/190
WB 0.88
Horz(CT) 0.34 9 n/a n/a
Matrix -MS
Weight: 157 lb FT = 0%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 2-2-0 oc pudins.
BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-4=-5491/3336, 4-5=-5095/3071, 5-6=-2314/1551, 6-8=2398/1533, 8-9=-3199/1981
BOT CHORD 2-14=-3040/5224,13-14=-1195/2361,12-13=-1123/2199,11-12=-1731/3001,
9-11=-1731/3001
WEBS 4-14=-492/513, 5-14=1707/2959, 5-13=-405/196, 6-13=-179/522, 8-12=-893/660,
8-11=0/303
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 31-7-3, Exterior(2) 31-7-3
to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
2=803, 9=803.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 11,1II.7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall Mel(
building design. Bracing indicated is to prevent buckling of individual truss web andfor chord members only. Additional temporary and permanent bracing 1 V IiTel(
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke Fast Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
T19884599
M11323
A7
SPECIAL
1
1
Job Reference (optional)
Cnambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:30 2020 Page 1
I D: W SJgpGwal Ppeur6hk9UIG5yuFU L-01 PUnQCcHygOmYBnUkX W ryTl Fi 145CtN9gaVwrzUUjt
�1-0-0 8-10-10 14-0-0 20-0-0 2511-15 34-0-0 15-01
-0-0 8-10-10 5-1-6 6-0-0 5-11-15 8-0-1 -0-0
�1
6
5x8 = 5x6 =
Ann
5x12 = 2x3 I 3x6 =
3x12 = 2.00 12
LOADING (psf)
SPACING- 2-0-0
CSI.
TCLL 20.0
Plate Grip DOL 1.25
TC 0.83
TCDL 7.0
Lumber DOL 1.25
BC 0.90
^ BCLL 0.0
Rep Stress Incr YES
WB 0.95
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
LUMBER-
. TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 *Except*
4-11: 2x4 SP M 30
REACTIONS. (size) 2=0-8-0, 7=0-8-0
Max Horz 2=-149(LC 8)
Max Uplift 2=-803(LC 10), 7=-803(LC 10)
Max Grav 2=1312(LC 1), 7=1312(LC 1)
DEFL. in (]cc) I/deft L/d
Vert(LL) 0.66 11 >616 360
Vert(CT) -1.10 10-11 >369 240
Horz(CT) 0.34 7 n/a n/a
Scale=1:60.8
PLATES
GRIP
MT20
244/190
MT18HS
244/190
Weight: 147 lb
FT = 0%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 2-2-0 cc purlins.
BOT CHORD Rigid ceiling directly applied or 4-0-2 cc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-5484/3370, 34=-5116/3126, 4-5=-2229/1544, 5-6=-2448/1599, 6-7=-3169/1993
BOT CHORD 2-11=3071/5219, 10-11 =-I 590/2874, 9-1 0=-1 738/2968, 7-9=-1738/2968
WEBS 3-11=4191443,4-11=1466/2647,4-10=-812/448,5-10=-205/487,6-10=-785/575,
6-9=0/272
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 31-7-3, Exterior(2) 31-7-3
to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise Indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift atjoint(s) except Qt=lb)
2=803, 7=803.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING - Verify destgn parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE M11-7473 rev. 10/03/2015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall p �a
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP/1 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
M11323
•
T19884600
M11323
AS
SPECIAL
�Qty
1
1
Job Reference (optional)
CRambers Truss, Inc., Fort Pierce, FL
3x12
8-8.4
4.00 12
2.00 12
8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:31 2020
3-3-12 3-8.4 4-8-4 ' 1-7-8 ' 2-8-12
5x6 =
3x4 =
4 21 5
2x3 11 5x8 =
6 22 7 0v_1 /
12 11
5x12 = 3x4 =
4x5 =
Scale = 1:60.6
10.6-4 20.4-8
22-0-0 34-0-0
10-6-4 9-10-4
1-7-8 12-M
Plate Offsets (X,Y)—
[2:0-1-15,Edge), [7:0-5-8,0-2-81
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc) I/dell Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.78
Vert(LL)
0.65 12-13 >624 360
MT20
244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.90
Vert(CT)
-1.08 12-13 >379 240
MT18HS
244/190
BCLL 0.0
Rep Stress Incr YES
WB 0.69
Horz(CT)
0.33 9 n/a n/a '
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 154 lb
FT = 0%
LUMBER-
BRACING-
. TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly applied or 2-2-0 cc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD Rigid ceiling directly applied or 3-11-11 cc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0
Max Horz 2=-129(LC 8)
Max Uplift 2=-803(LC 10), 9=-803(LC 10)
Max Grav 2=1312(LC 1). 9=1312(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=5488/3444, 3-4=5117/3183, 4-5=-3911/2497, 5-6=-2576/1770, 6-7=-2586/1779,
7-8=-2663/1762,8-9=-3021/1971
BOT CHORD 2-13=-3143/5224, 12-13=-1956/3292, 11-12=-136912481, 9-11 =-1 70512827
WEBS 3-13=396/420, 4-13=-1028/1721, 5-13=-300/797, 5-12=-894/601, 6-12=-265/263,
7-12=294/391, 7-11=374/691, 8-11=-535/502
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 24-13 to 31-7-3, Extedor(2) 31-7-3
to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
'
This item has been
6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
electronically Signed and
7) Bearing atjoint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
sealed by Velez, Joaquin, PE
capacity of bearing surface.
using a Digital Signature.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
Printed copies of this
p
2=803, 9=803.
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE M11.7473 rev, 1010312015 BEFORE USE.
Design valid for use only with MTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
•
T19884601
M11323
A9
HIP
�Qty
1
1
�M`11323
Job Reference (optional)
l.narrDers i russ, inc., ron vierce, rL mz4U s mar a zuzu MI i eK inoU5IDes, inc. rn Apr 3 ui:o4:Jz zuzu rage i
ID:_etcl cxC3ixW7huls7ypJyuFUK-y7XEC6DspZw6OsKAc9Z_xNZ18W4CZ7Mfd83c?izUUjr
1-0-0 fi-7-15 10: 0 15-2-14 204-0 24-0-0 27-4-1 34-0.0 5-0-
-0-0 6-7-15 3-0-1 5-2-14 5-1-2 3-8-0 3�-1 6-7-15 -N
4.00 12
4x4 = 3x4 = 20 II 4x8 =
4 24 525 26 6 27 7
Scale=1:58.6
15 14 13 12 11
3x5 = 3x8 = 3x6 = 6x8 = 3x6 = 3x4 = 3x5
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in (loc) I/deb L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.35
Vert(LL) -0.18 11-21 >917 360
MT20 244/190
TCOL 7.0
Lumber DOL
1.25
BC 0.54
Vert(CT) -0.38 11-21 >432 240
BCLL 0.0
Rep Stress Incr
YES
WB 0.89
Horz(CT) 0.02 13 n/a n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 156 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly applied or 5-11-9 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0, 13=0-8-0
Max Horz 2=109(LC 9)
Max Uplift 2=-430(LC 10), 9=-249(LC 10), 13=-928(LC 10)
Max Grav 2=685(LC 19), 9=386(LC 20), 13=1616(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1275/1025, 3-4=913/708, 4-5=-829r105, 5-6=-565/807, 6-7=-565/807,
7-8=-104/278, 8-9=-341/235
BOT CHORD 2-15=-836/1187, 13-15=-34/309, 11-13=256/348, 9-11=-124/304
WEBS 3-15=-425/501,5-15=-444/665,5-13=-121511079,6-13=-264/300, 7-11=-255/396,
8-11=-461/521,7-13=-837/703
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) -1-0-0 to 2-4-13, Interior(1) 24-13 to 5-2-5, Exterior(2) 5-2-5 to
14-9-11, Interior(l) 14-9-11 to 19-2-5, Exterior(2) 19-2-5 to 28-9-11, Interior(1) 28-9-11 to 31-7-3, Exterior(2) 31-7-3 to 35-0-0
zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
This item has been
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
electronically Signed and
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
sealed by Velez, Joaquin, PE
2=430, 9=249,13=928.
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.74T3 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery• erection and bracing of trusses and truss systems, see ANS11TPN Quality Criteria, DSB-99 and BCSI Building Component 6904 Parke East Blvd.
Safety information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
11323T1M11323
GRA
HIP
�Qty
1J
Mob
Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:33 2020
ID:_etC1 cxC3ixVV?huts?ypJyuFUK-OK4cPSEUat2zdOvM9s4DTb5n5vPvlY6proo9X
1-0-0 8-0-0 11-1-1 17-M 18-6-0 22-2-2 26-0-0 34-0-0
0-0 8-0-0 3-1-1 5 10-15 1-6-0 3 8-2 3-9-14 8-0-0
THIS TRUSS IS NOT SYMMETRIC.
PROPER ORIENTATION IS ESSENTIAL.
4x4 =
14
Scale=1:60.6
3x5 = 3x6 II 3x6 = 6x8 = 3x6 = 6x8 = 4x4 =
6x8 =
TRUSS DESIGNED FOR WIND LOADS IN THE PLANE
OF THE TRUSS ONLY. FOR STUDS EXPOSED TO WIND
(NORMAL TO THE FACE), SEE STANDARD INDUSTRY
GABLE END DETAILS AS APPLICABLE, OR CONSULT
QUALIFIED BUILDING DESIGNER AS PER ANSIITPI 1.
8-0-0 11-1-1 18-&0 26-0-0 34-0.0
8-0-0 3-1-1 7-4-15 7-6-0 8-0-0
Plate Offsets (X,Y)— [2:0-2-2,Edge], [3:0-3-8,Edge], [21:0-3-8,Edge], [24:0-3-8,0-3-0], [27:0-3-8,0-3-0]
LOADING (psf)
SPACING-
2-0-0
CSI.
TCLL
20.0
Plate Grip DOL
1.25
TC 0.91
TCDL
7.0
Lumber DOL
1.25
BC 0.57
` BCLL
0.0
Rep Stress Incr
NO
WB 0.98
BCDL
10.0
Code FBC2017/TPI2014
Matrix -MS
DEFL,
in (loc)
Ildefl
Ud
PLATES GRIP
Vert(LL)
0.20 24-35
>914
360
MT20 244/190
Vert(CT)
-0.24 29-32
>552
240
Horz(CT)
0.02 22
n/a
n/a
Weight: 194 lb FT = 0%
LUMBER- BRACING-
. TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 4-2-5 oc purlins.
BOT CHORD 2x4 SP M 30 Except:
WEBS 2x4 SP No.3 1 Row at midpt' 8-21
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
JOINTS 1 Brace at Jt(s): 7, 8, 19, 17, 14
REACTIONS. All bearings 0-8-0.
(lb) - Max Horz 2=-179(LC 6)
Max Uplift All uplift 100 lb or less at joint(s) except 2=-351(LC 8), 27=1168(1_C 8), 26=-1495(LC 8),
22=-625(LC 8)
Max Grav All reactions 250 lb or less at joint(s) except 2=487(LC 17), 27=2232(LC 13), 26=2929(LC 14).
22=984(LC 14)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-621/387, 3-5=-304/838, 5-7=-588/1209, 7-8=-588/1209, 8-12=-588/1209,
12-13=-588/1209, 13-15=-588/1209, 15-16=-588/1209, 16-18=-588/1209,
18-20=-2230/1280, 20-21=-2230/1280, 21-22=-2271/1263, 6-9=-126/305, 9-11 =-1 06/363,
11-14=-193/412, 14-17=-94/271, 19-21=-143/272
BOT CHORD 2-29=-247/677, 27-29=189/540, 26-27=-779/446, 24-26=411/653, 22-24=-1083/2108
WEBS 3-29=-500/1176, 3-27=-1766/911, 5-27:;-748/622, 5-26=-546/351, 13-26=-946/617,
18-26=-2412/1474, 18-24=-846/1780,21-24=-35/351,4-5=608/514, 19-20=-335/305,
14-15=-556/407, 11-12=-254/54
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
This item has been
It: Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
electronically signed and
3) Provide adequate drainage to prevent water ponding.
Sealed by Velez, Joaquin, PE
4) All plates are 2x3 MT20 unless otherwise indicated.
using a �191ta1 Signature.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
'
Printed copies of this
6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
document are not Considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 351 lb uplift at joint 2, 1168 lb uplift at
signed and sealed and the
joint 27, 1495 lb uplift at joint 26 and 625 lb uplift at joint 22.
Signature must be verified
8) Girder carries hip end with 8-0-0 end setback.
On any electronic copies.
9) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord.
Joaquin Velez PE No.68182
10) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 967 lb down and 461 lb up at
MiTek USA, Inc. FL Cart 6634
26-0-0, and 967 Ib down and 461 lb up at 8-0-0 on bottom chord. The design/selection of such connection device(s) is the
6904 Parke East Blvd. Tampa FL 33610
responsibility of others.
Date:
11) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
April 3,2020
andard
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE M11.7473 rev. f010312015 BEFORE USE,
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component. not
a buss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall rt /�
building design. Bracing indicated is to prevent buckling of Individual truss web andlor chord members only. Additional temporary and permanent bracing MiTek*
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI1TPI1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
T19884602
M11323
GRA
HIP
1
1
Job Reference a tional
Chambers Truss, Inc., Fort Pierce, FL ts.z4u s mar B zuzu mi iex mousmes, inc. rn Apr a Uf:o4:33 LULU rage z
ID:_etC1 cxC3ixW?huls?ypJyuFUK-QK4cPSEUat2zdOvM9s4DTb5n5vPvlY6proo9XAzUUjq
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=-54, 21-23=54, 29-30=-20, 24-29=-47(F=-27), 24-33=-20, 3-11=-126(F=-72), 11-21 =-1 26(F=-72)
Concentrated Loads (lb)
Vert: 29=-641 (F) 24=-641(F)
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MI1.7473 rev. 10/03/2015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSYTP/f quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
.
T19884603
M11323
GRB
HIP
�Qty
1
1
�M11323
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:34 2020 Page 1
ID:SrRaEyyrgO4M78G4raWBLWyuFUJ-uWe7doF7LAApF9UZjacSOoe_iJjPt Oby4SYi3czUUjp
1-0 0 8-M 13-8-0 17-0 0 20-0-0 26-0-0 34-0-0 5-0-
0-0 8-0-0 5-8-0 3-4-0 3-4 5-8-0 8-0-0 -0-0
4.00 12
46 =
5x12 MT18HS =
4x10 =
2x3 11 4x6 =
23 4 5 6
2x3 11
7 24
5x12 MT18HS =
Scale = 1:58.6
(V
3I�
3x6 II 5x6 = 6x12 = 6x12 = 5x6 — 3x6 II 4x6 —
13-8-0 20-4-0 26-0-0 34-0-0
16 15 14 13 12 11
LOADING (psf)
SPACING-
2-0-0
TCLL 20.0
Plate Grip DOL
1.25
TCDL 7.0
Lumber DOL
1.25
• BCLL 0.0
Rep Stress Incr
NO
BCDL 10.0
Code FBC2017lrP12014
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 *Except*
4-14,7-13: 2x6 SP N0.2
CSI.
DEFL.
in (loc) I/deft Ud
PLATES
GRIP
TC 0.80
Vert(LL)
0.2216-19 >999 360
MT20
244/190
BC 0.68
Vert(CT)-0.3016-19 >820 240
MT18HS
244/190
WB 0.90
Horz(CT)
0.06 9 Na n1a
Matrix -MS
Weight: 153 lb
FT = 0%
BRACING -
TOP CHORD
Structural wood sheathing directly applied or 3-1-14 oc puriins.
BOT CHORD
Rigid ceiling directly applied or 5-3-14 oc bracing.
WEBS
1 Row at midpt 3-14, 8-13, 6-13
REACTIONS. (size) 2=0-8-0, 13=0-8-0, 9=0-8-0
Max Horz 2=90(LC 7)
Max Uplift 2=-853(LC 8), 13=-2590(LC 8), 9=-345(LC 8)
Max Grav 2=1451(LC 13), 13=4743(LC 15), 9=528(LC 14)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3625/1950, 34=-2080/1236, 4-6=-2080/1236, 6-7=-1296/2589, 7-8=-1296/2589,
8-9=751 /370
BOT CHORD 2-16=-1729/3460, 14-16=-1753/3525, 11-13=-262/733, 9-11=-241/668
WEBS 3-16=435/1209, 3-14=-1552/774, 4-14=-837/691, 7-13=-878/713, 8-13=-3635/1919,
8-11=432/1204,6-14=-1453/2814,6-13=-3198/1807
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 853 lb uplift at joint 2, 2590 lb uplift at
joint 13 and 345 lb uplift at joint 9.
8) Girder carries hip end with 8-0-0 end setback.
9) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 967 lb down and 461 lb up at
26-0-0, and 967 lb down and 461 lb up at 8-0-0 on bottom chord. The design/selection of such connection device(s) is the
responsibility of others.
10) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=-54, 3-8=-131(F=-77), 8-10=-54, 16-17=-20, 11-16=49(F=29), 11-20=-20
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING -Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MIf-7473 rev. f0/0312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not �®
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall�-
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
•
T79884603
M11323
GRB
HIP
1
1
�M11323
Job Reference (optional)
13hambers Truss, Inc., Fort Pierce, FL
LOAD CASE(S) Standard
Concentrated Loads (Ib)
Vert: 16=-641(F) 11=-641(F)
8.240 S Mar 9 ZUZU MITBK Industnes, Inc. Fri Apr 3 Ul:b4:3b ZUZU Page Z
ID:SrRaEyyrg04M78G4raW BLWyuFUJ-MiCNg7Gl6UIgtJ31HH7hYCB9Sj3emSr6J6HGb22UUjo
®WARNING- Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE M11-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall �
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS1iTPN Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Informafron available from Truss Plate Institute, 218 N. Lee Street, Suite 312. Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
`
T19884604
M11323
J2
MONO TRUSS
�Qty
8
1
�M`11323
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:35 2020 Page 1
ID:xl?zSlzTbJCDIIrGPHI QukyuFUI-MiCNg7G16UIgtJ3IHH7hYOBJ7jCDmgz6J6HGb2zUUjo
1-0-0 2-M
Scale = 1:7.8
3x4 =
2-0-0
2-0-0
LOADING (psf)
SPACING- 2-0-0
cSl.
DEFL. in
(loc) I/deb L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.18
Vert(LL) -0.00
7 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.07
Vert(CT) -0.00
7 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00
3 n/a n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MP
Weight: 8 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 2-0-0 oc pudins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=67(LC 10)
Max Uplift 3=-28(LC 10), 2=-136(LC 10), 4=-3(LC 7)
Max Grav 3=39(LC 15), 2=141(LC 1), 4=31(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) • This truss has been designed for a live load of 20.Opsf on the bottom chord In all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 28 lb uplift at joint 3, 136 lb uplift at joint
2 and 3 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE M11.7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall p ��
building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing IV ale
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312. Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
M11323
•
T19884605
M11323
J4
MONO TRUSS
8
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:36 2020 Page 1
ID:PDYLfd_5MdK4MSQTz?ZfRxyuFUH-gvml2TGNtoQXUTexftew5DjQW7UmV7DFYm1 p8UzUUjn
-1-0-0 4-0-0
1-0-0 4-0-0
3x4 =
LOADING (psf)
SPACING-
2-0-0
TCLL
20.0
Plate Grip DOL
1.25
TCDL
7.0
Lumber DOL
1.25
BCLL
0.0 '
Rep Stress Incr
YES
BCDL
10.0
Code FBC2017/TP12014
LUMBER -
TOP CHORD
2x4 SP No.3
BOT CHORD
•
2x4 SP No.3
REACTIONS.
(size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=104(LC 10)
Max Uplift 3=-80(LC 10), 2=-161(LC 10), 4=7(LC 10)
Max Grav 3=90(LC 1), 2=207(LC 1), 4=69(LC 3)
Scale = 1:11.1
CSI.
DEFL. in
(loc) I/deft Ud
PLATES GRIP
TC 0.39
Vert(LL) 0.02
4-7 >999 360
MT20 244/190
BC 0.37
Vert(CT) ' -0.02
4-7 >999 240
WB• 0.00
Horz(CT) -0.00
3 n/a n/a
Matrix -MP
Weight: 14 lb FT = 0%
BRACING -
TOP CHORD
Structural wood sheathing directly applied or 4-0-0 oc pudins.
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 80 lb uplift at joint 3, 161 lb uplift at joint
2 and 7 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall MiTek*
iTe k•
building design. Bracing Indicated is to prevent budding of individual truss web and/or chord members only. Additional temporary and permanent bracing
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the iVl
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP/1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Ply
'
T19884606
M11323
J6
MONO TRUSS
�Qty
8
1
�M11323
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:36 2020 Page 1
ID:tP6jtzJ7xSx_c_fXi4uz9yuFUG-gvml2TGNtoQXUTexr?ew5DjR?7MUV7DFYml p8UzUUjn
-1-0-0 6-0-0
1-0-0 6-0-0
Scale = 1:14.6
3x4 =
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) Vdefl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.36
Vert(LL) 0.11
4-7 >629 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.83
Vert(CT) -0.12
4-7 >617 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00
3 n/a n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MP
Weight: 20 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc puffins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=142(LC 10)
Max Uplift 3=-131(LC 10), 2=-194(LC 10), 4=8(LC 10)
Max Grav 3=145(LC 1). 2=279(LC 1), 4=102(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 131 lb uplift at joint 3, 194 lb uplift at
joint 2 and 8 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 111II-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek*
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI TP/1 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
T19884607
M11323
JB
MONO TRUSS
20
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:37 2020 Page 1
I D:tP6jtzj7xSx_c_fXi4uz9yuFUG-J5K7FpH7d5YO6dD8Oi99eRGYgXquEaTPmOmNgxzUUj m
1-0-0 8-0-0
1-0-0 8-0-0
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 31
3x5 =
8-0-0
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
I/deft
Ud
Plate Grip DOL
1.25
TC 0.62
Vert(LL)
0.26
4-7
>367
360
Lumber DOL
1.25
BC 0.38
Vert(CT)
-0.30
4-7
>319
240
Rep Stress Incr
YES
WB 0.00
Horz(CT)
-0.00
3
n/a
n/a
Code FBC2017/TPI2014
Matrix -MP
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=180(LC 10)
Max Uplift 3=-175(LC 10), 2=-228(LC 10), 4=-15(LC 10)
Max Grav 3=188(LC 1), 2=352(LC 1), 4=145(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
Scale=1:17.4
PLATES GRIP
MT20 244/190
Weight: 26 lb Fr = 0%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc puffins.
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf,, h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 3-1-13, Exterior(2) 3-1-13
to 7-11-8 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 175 lb uplift at joint 3, 228 lb uplift at
joint 2 and 15 lb uplift atjoint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 11111.7473 rev. f010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP/1 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke Fast Blvd.
Safety Information avallable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandda, VA 22314. Tampa, FL 36610
Job
Truss
Truss Type
city,
Ply
M11323
T19884608
M11323
KJ8
MONO TRUSS
4
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
1-5-0 7-3-4
8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:64:38 2020 Page 1
I D: Lcg54J? Lu EancmZr4Qb7 W MyuFU F-nHuVT91dOPgFknoKyPgOAeo oawBGzwZY?4WwCNzUUjI
Scale = 1:20.3
3x4 = „ 5
3x4 =
LOADING (psf)
SPACING- 2-0-0
CS1.
TCLL 20.0
Plate Grip DOL 1.25
TC 0.29
TCDL 7.0
Lumber DOL 1.25
BC 0.30
BCLL 0.0 '
Rep Stress, Incr NO
WB 0.46
BCDL 10.0
Code FBC2017fTP12014
Matrix -MS
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3
REACTIONS. (size) 4=Mechanical, 2=0-11-5, 6=Mechanical
Max Horz 2=244(LC 8)
Max Uplift 4=-205(LC 8), 2=305(LC 8), 6=-286(LC 8)
Max Grav 4=245(LC 13). 2=466(LC 1), 6=590(LC 13)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=1151/523
BOT CHORD 2-7=687/1126, 6-7=-687/1126
WEBS 3-7=0/330, 3-6=-1236/755
DEFL. in (loc) I/deft L/d
Vert(LL) 0.07 7-10 >999 360
Vert(CT) -0.12 7-10 >999 240
Horz(CT) 0.02 6 n/a n/a
PLATES GRIP
MT20 244/190
Weight: 44 lb FT = 0%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pur ins.
BOT CHORD Rigid ceiling directly applied or 8-9-6 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 205 lb uplift at joint 4, 305 lb uplift at
joint 2 and 286 lb uplift at joint 6.
6) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-2=-54
Trapezoidal Loads (plf)
Vert: 2=0(F=27, B=27)-to-4=-152(F=-49, B=-49), 8=0(F=10, B=10)-to-5=-56(F=-18, B=-18)
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 10/03/2015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verily the applicability of design parameters and property Incorporate this design Into the overall
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek*
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TPII Quality Criteria, DSB-89 and BCSI Building Component Blvd.
e East
Safety Information available from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, 6904 Parke
East
Symbols
PLATE LOCATION AND ORIENTATION
Center plate on joint unless x, y
offsets are indicated.
Dimensions are in ft-in-sixteenths.
Apply plates to both sides of truss
and fully embed teeth.
Ole
For 4 x 2 orientation, locate
plates 0- 'lid' from outside
edge of truss.
This symbol indicates the
required direction of slots in
connector plates.
* Plate location details available in MiTek 20120
software or upon request.
PLATE SIZE
The first dimension is the plate
4 x 4 width measured perpendicular
to slots. Second dimension is
the length parallel to slots.
LATERAL BRACING LOCATION
Indicated by symbol shown and/or
by text in the bracing section of the
output. Use T or I bracing
if indicated.
BEARING
Indicates location where bearings
(supports) occur. Icons vary but
reaction section indicates joint
number where bearings occur.
Min size shown is for crushing only.
Industry Standards:
ANSI/TPI1: National Design Specification for Metal
Plate Connected Wood Truss Construction.
DSB-89: Design Standard for Bracing.
BCSI: Building Component Safety Information,
Guide to Good Practice for Handling,
1 Installing & Bracing of Metal Plate
Connected Wood Trusses.
Numbering System
6-4-8 dimensions shown in ft-in-sixteenths
(Drawings not to scale)
1 2 3
TOP CHORDS
C1-2 C2.3
WEBS 4
O= O
U �''� S U
d
d
O c7-e c6a cs s
BOTTOM CHORDS
8 7 6 5
JOINTS ARE GENERALLY NUMBERED/LETTERED CLOCKWISE
AROUND THE TRUSS STARTING AT THE JOINT FARTHEST TO
THE LEFT.
CHORDS AND WEBS ARE IDENTIFIED BY END JOINT
NUMBERS/LETTERS.
PRODUCT CODE APPROVALS
ICC-ES Reports:
ESR-1311, ESR-1352, ESR1988
ER-3907, ESR-2362, ESR-1397, ESR-3282
Trusses are designed for wind loads in the plane of the
truss unless otherwise shown.
Lumber design values are in accordance with ANSI/TPI 1
section 6.3 These truss designs rely on lumber values
established by others.
© 2012 MiTek® All Rights Reserved
MiTek
MiTek Engineering Reference Sheet: MII-7473 rev. 10/03/2015
® General Safety Notes
Failure to Follow Could Cause Property
Damage or Personal Injury
1. Additional stability bracing for truss system, e.g.
diagonal or X-bracing, is always required. See BCSI.
2. Truss bracing must be designed by an engineer. For
wide truss spacing, individual lateral braces themselves
may require bracing, or alternative Tor I
bracing should be considered.
3. Never exceed the design loading shown and never
stack materials on inadequately braced trusses.
4. Provide copies of this truss design to the building
designer, erection supervisor, property owner and
all other interested parties.
5. Cut members to bear tightly against each other.
6. Place plates on each face of truss at each
joint and embed fully. Knots and wane at joint
locations are regulated by ANSI/TPI 1.
7. Design assumes trusses will be suitably protected from
the environment in accord with ANSIITPI 1.
8. Unless otherwise noted, moisture content of lumber
shall not exceed 19% at time of fabrication.
9. Unless expressly noted, this design is not applicable for
use with fire retardant, preservative treated, or green lumber.
10. Camber is a non-structural consideration and is the
responsibility of truss fabricator. General practice is to
camber for dead load deflection.
11. Plate type, size, orientation and location dimensions
indicated are minimum plating requirements.
12. Lumber used shall be of the species and size, and
in all respects, equal to or better than that
specified.
13. Top chords must be sheathed or purlins provided at
spacing indicated on design.
14. Bottom chords require lateral bracing at 10 ft. spacing,
or less, if no ceiling is installed, unless otherwise noted.
15. Connections not shown are the responsibility of others.
16. Do not cut or alter truss member or plate without prior
approval of an engineer.
17. Install and load vertically unless indicated otherwise.
18. Use of green or treated lumber may pose unacceptable
environmental, health or performance risks. Consult with
project engineer before use.
19. Review all portions of this design (front, back, words
and pictures) before use. Reviewing pictures alone
is not sufficient.
20. Design assumes manufacture in accordance with
ANSIfrPI 1 Quality Criteria.