HomeMy WebLinkAboutBuilding Plan ReviewST. LUCIE COUNTY -FT PIERCE FIRE DISTRICT
BUILDING PLAN REVIEW
P. O. BOX 3030
Telephone: 407-462.2312
Ft. Pierce, FL 34948-3030
FAX: 407-462-2326
JURISDICTION:
St Lucie County
FPB. #:
6533
PROJECT NAME:
Edwards Road Bldg #6_
BLDG DEPT #:
96-010149
CONTRACTOR:
Drawdy Brothers
PHONE #:
407-464-8160
ARCHITECT:
Slocum & Platts
PHONE #:
407-465-3019
BUILDING OWNER:
Phillip Drawdy
REVIEW DATE:
1-17-96
BUILDING LOCATION:
937 Edwards Rd
# OF STORIES:
1
OCCUPANCY TYPE:
Storage
AUTO SPKLS:
Yes No X
GROSS SQ FOOTAGE:
500 sq ft
NET SQ FT:
OCCUPANT LOAD:
BASED ON:
sq ft per person
CONSTRUCTION TYPE:
NFPA 4220 _V
SBCCI _VI_ (un)
NEW CONSTRUCTION _X_TENANT
IMPROV RENOVATION ADDITION
_X_ SHELL ONLY
The Fire Marshal requires 24 hour notice on all inspections.
;. MEZZANINE ADDITION
4-1. Mezzanine Requirements. SBCCI Chapter 1005.6.3(1)
A mezzanine is permitted if the space below the mezzanine is totally open and
unencumbered by partitioned rooms or spaces.
Exception: The space beneath the mezzanine may be enclosed provided the enclosed
space is protected throughout with a smoke detection system in accordance
with NFPA #72 which sounds an alarm in the mezzanine.
A smoke detector must be installed in each office below the mezzanine and an indicating
device installed on the mezzanine level. ADA requires a visual signal also if a hearing
impaired person occupies the mezzanine level.
2. 34" handrails required on each side on the mezzanine stairs.. 42" guard at top landing.
3. The maximum travel distance to an exterior side hinged bolt cannot exceed 75'.
4. A separate permit is required from the Fire Marshal's Office for the installation of the
smoke detection system.
i
5. Provide a 2A-10BC rated fire extinguisher for the mezzanine level.
REVIEWED BN
DATE:.] — 4:7 - �
Sheet ___L of.
EDWARDS ROAD INDUSTRIAL BUILDING #6
+ 6. The Building Code requires a one (1) hour separation between the office area and the
remainder of the building. The mezzanine requires a door at the top of the stair landing
to be one (1) hour rated .with closing device.
7. The window in the office shall be 1/4" wire glass in a steel frame.
REVIEWED B
DATE: / - / -7 9
SHEET,_ OF ?—