HomeMy WebLinkAboutEnergy CalcsProject Name: Owner: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY COLE CONSTRUCTION SERVICES, LLC.PRESTRIDGE RESIDENCE Street: City, State, Zip: FORT PIERCE , FL , 505 N GRAVES ROAD Permit Number: Design Location: FL, Fort Pierce CHECKAIR BARRIER CRITERIA A continuous air barrier shall be installed in the building envelope. The exterior thermal envelope contains a continuous air barrier. Breaks or joints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. The junction of the foundation and sill plate shall be sealed. The junction of the top plate and the top of exterior walls shall be sealed. Knee walls shall be sealed. The space between window/door jambs and framing, and skylights and framing shall be sealed. Rim joists shall include the air barrier. The air barrier shall be installed at any exposed edge of insulation. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Narrow cavities Shafts, penetrations Crawl space walls Floors (including above-garage and cantilevered floors) Rim joists Windows, skylights Walls Ceiling/attic General COMPONENT Garage separation Recessed lighting Plumbing and wiring S h o w e r / t u b HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. The air barrier shall be installed behind electrical or communication boxes or air-sealed boxes shall be installed. The air barrier installed at exterior walls adjacent to showers and tubs shall separate them from the showers and tubs. Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Recessed light fixtures installed in the building thermal envelope shall be sealed to the drywall. Air sealing shall be provided between the garage and conditioned spaces. When required to be sealed, concealed fire sprinklers shall only be sealed in a manner that is recommended by the manuf acturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceilings. C o n c e a l e d Electrical/phone box on exterior walls Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA INSULATION INSTALLATION CRITERIA EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software9/8/2020 12:39 PM Page 1 of 1 Air-permeable insulation shall not be used as a sealing material. The insulation in any dropped ceiling/soffit shall be aligned with the air barrier. Cavities within corners and headers of frame walls shall be insulated by completely filling the cavity with a material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Rim joists shall be insulated. Floor framing cavity insulation shall be installed to maintain permanent contact with the underside of subfloor decking, or floor framing cavity insulation shall be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. and doors on exterior wall requirements Recessed light fixtures installed in the building thermal envelope shall be air tight and IC rated. sprinklers Where provided instead of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exterior walls adjacent to showers and tubs shall be insulated. 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� ����������������������������������������������������� EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 79/8/2020 12:38 PM Project Name: Owner: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY COLE CONSTRUCTION SERVICES, LLC.PRESTRIDGE RESIDENCE Street: City, State, Zip: FORT PIERCE , FL , 505 N GRAVES ROAD Permit Number: Design Location: FL, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area above grade (ft²) New (From Plans) Single-family 1 No 2251 7. Windows a. U-Factor: S H G C : b. U-Factor: S H G C : c. U-Factor: S H G C : d. U-Factor: S H G C : Sgl, U=0.32 322.28 ft² SHGC=0.22 Sgl, U=0.29 24.33 ft² SHGC=0.23 Sgl, U=0.33 24.00 ft² SHGC=0.21 N/A f t ² 8. Floor Types a. Slab-On-Grade Edge Insulation b. N/A c. N/A R=0.0 2251.00 ft² R=f t ² R=f t ² 9. Wall Types a. Concrete Block - Polystyrene Bead AggreR=0.0 2200.00 ft² b. Frame - Wood, Adjacent R=13.0 700.00 ft² c. N/A R=f t ² 10. Ceiling Types a. Roof Deck (Unvented)R=20.0 2251.00 ft² 128.00 ft² R=20.0b. Knee Wall (Unvented) c. N/A R = f t ² 11. Ducts a. Sup: Attic, Ret: Attic, AH: Garage 12. Cooling systems 13. Heating systems 14. Hot water systems a. Electric Cap: 50 gallons b. Conservation features None d. N/A R=f t ² Area Weighted Average Overhang Depth:8.939 ft. Area Weighted Average SHGC:0.220 Description Area Insulation Area Insulation Area Insulation Area 15. Credits None 3 (370.6 sqft.) (2900.0 sqft.) (2379.0 sqft.) (2251.0 sqft.) Conditioned floor area below grade (ft²) 0 a. Central Unit a. Electric Strip Heat k B t u / h r 40.0 SEER:16.00 Efficiency k B t u / h r Efficiency 27.0 COP:1.00 f t ² R 6 175 EF: 0.980 Glass/Floor Area: 0.165 Total Proposed Modified Loads: Total Baseline Loads: 81.18 81.95 PASS I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code. PREPARED BY: DATE: I hereby certify that this building, as designed, is in compliance with the Florida Energy Code. OWNER/AGENT: DATE: BUILDING OFFICIAL: DATE: Review of the plans and specifications covered by this calculation indicates compliance with the Florida Energy Code. Before construction is completed this building will be inspected for compliance with Section 553.908 Florida Statutes. - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2). FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method FORM R405-2017 9-9-2020 PROJECT Title: Owner Name: # of Units: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY COLE CONSTRUCTION SER 1 PRESTRIDGE RESIDENCE Family Type: New/Existing: Bedrooms: Conditioned Area: Total Stories: Worst Case: Rotate Angle:0 No 1 2251 3 New (From Plans) Single-family Address Type: Lot # Block/Subdivision: PlatBook: Street: County: City, State, Zip: FL , FORT PIERCE , St. Lucie 505 N GRAVES ROAD Street Address Comment: Building Type: User Cross Ventilation:No Whole House Fan:No TMY Site Design Temp Int Design Temp Heating Design Daily Temp Design Location 2.5 %97.5 %Degree Days Moisture RangeWinter Summer CLIMATE 90 70 75 299 62 Low39FL_VERO_BEACH_MUNIFL, Fort Pierce______ Number Name Area Volume BLOCKS 1 Entire House 2251 23200.7 Number Name Area Volume SPACES Kitchen Occupants Bedrooms Cooled HeatedInfil ID Finished 1 M WIC 70 700 No 0 Yes Yes1 Yes 2 M BATH 106 1060 No 0 Yes Yes1 Yes 3 M TOILET 24 240 No 0 Yes Yes1 Yes 4 UTILITY RM 190 1900 No 0 Yes Yes1 Yes 5 MASTER BEDROO 278 2780 No 0 1 Yes Yes1 Yes 6 M HALL 32 320 No 0 Yes Yes1 Yes 7 KITCHEN 240 2400 Yes 0 Yes Yes1 Yes 8 SHOP 156 1560 No 0 Yes Yes1 Yes 9 LIVING/DINING 620 6890.7 No 0 Yes Yes1 Yes 10 WIC 3 32 320 No 0 Yes Yes1 Yes 11 BEDROOM 3 144 1440 No 0 1 Yes Yes1 Yes 12 BATH 2 72 720 No 0 Yes Yes1 Yes 13 BEDROOM 2 141 1410 No 0 1 Yes Yes1 Yes 14 WIC 2 36 360 No 0 Yes Yes1 Yes 15 HALL 56 560 No 0 Yes Yes1 No 16 SHOP BATH 54 540 No 0 Yes Yes1 No # Floor Type Area Tile Wood Carpet FLOORS Perimeter R-Value Joist R-ValueSpace Perimeter 1 70 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -017 ft M WIC 2 106 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -07 ft M BATH 9/8/2020 12:38 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 7 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT # Floor Type Area Tile Wood Carpet FLOORS Perimeter R-Value Joist R-ValueSpace Perimeter 3 24 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -06 ft M TOILET 4 190 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -08 ft UTILITY RM 5 278 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -035 ft MASTER BEDRO 6 32 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -02 ft M HALL 7 240 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -014 ft KITCHEN 8 156 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -012 ft SHOP 9 620 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -040 ft LIVING/DINING 10 32 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -04 ft WIC 3 11 144 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -024 ft BEDROOM 3 12 72 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -06 ft BATH 2 13 141 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -025 ft BEDROOM 2 14 36 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -04 ft WIC 2 15 56 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -01 ft HALL 16 54 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -01 ft SHOP BATH # Type Materials Color Absor. Roof Solar Deck Insul. Pitch ROOF Tested Roof Area Gable Area Emitt Tested EmittSA (deg) Rad Barr 1 Hip Metal 2517 ft² Light 0.2 20 26.6______No0 ft² 0.9 NoN ATTIC # Type Ventilation Area RBS IRCCVent Ratio (1 in) ______ 1 Full attic Unvented 2251 ft² N N0 9/8/2020 12:38 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 7 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT # Ceiling Type R-Value Area Framing Frac Truss Type CEILING Space Ins Type 1 Under Attic (Unvented)0 70 ft² 0.1 Wood______M WIC Blown 2 Under Attic (Unvented)0 106 ft² 0.1 Wood______M BATH Blown 3 Under Attic (Unvented)0 24 ft² 0.1 Wood______M TOILET Blown 4 Under Attic (Unvented)0 190 ft² 0.1 Wood______UTILITY RM Blown 5 Under Attic (Unvented)0 278 ft² 0.1 Wood______MASTER BEDRO Blown 6 Under Attic (Unvented)0 32 ft² 0.1 Wood______M HALL Blown 7 Under Attic (Unvented)0 240 ft² 0.1 Wood______KITCHEN Blown 8 Under Attic (Unvented)0 156 ft² 0.1 Wood______SHOP Blown 9 Under Attic (Unvented)0 620 ft² 0.1 Wood______LIVING/DINING Blown 10 Under Attic (Unvented)0 32 ft² 0.1 Wood______WIC 3 Blown 11 Under Attic (Unvented)0 144 ft² 0.1 Wood______BEDROOM 3 Blown 12 Under Attic (Unvented)0 72 ft² 0.1 Wood______BATH 2 Blown 13 Under Attic (Unvented)0 141 ft² 0.1 Wood______BEDROOM 2 Blown 14 Under Attic (Unvented)0 36 ft² 0.1 Wood______WIC 2 Blown 15 Under Attic (Unvented)0 56 ft² 0.1 Wood______HALL Blown 16 Under Attic (Unvented)0 54 ft² 0.1 Wood______SHOP BATH Blown 17 Knee Wall (Unvented)20 15 ft² 0.1 Wood______MASTER BEDRO Blown 18 Knee Wall (Unvented)20 3 ft² 0.1 Wood______M HALL Blown 19 Knee Wall (Unvented)20 18 ft² 0.1 Wood______KITCHEN Blown 20 Knee Wall (Unvented)20 60 ft² 0.1 Wood______LIVING/DINING Blown 21 Knee Wall (Unvented)20 6 ft² 0.1 Wood______WIC 3 Blown 22 Knee Wall (Unvented)20 8 ft² 0.1 Wood______BEDROOM 3 Blown 23 Knee Wall (Unvented)20 18 ft² 0.1 Wood______SHOP Blown WALLS #Wall Type R-Value Area Adjacent Framing Solar Ornt Fraction Absor. HeightWidth Ft In Ft InTo Cavity Sheathing R-ValueSpace Grade% Below 1 0 0M WIC 0007 10S Concrete Block - Polystyrene 0.20Exterior70.0 ft² ____ 2 0 0M WIC 00010 10W Concrete Block - Polystyrene 0.20Exterior100.0 ft² ____ 3 0 0M BATH 0007 10S Concrete Block - Polystyrene 0.20Exterior70.0 ft² ____ 4 0 0M TOILET 0006 10S Concrete Block - Polystyrene 0.20Exterior60.0 ft² ____ 5 0 0UTILITY RM 0008 10S Concrete Block - Polystyrene 0.20Exterior80.0 ft² ____ 6 13 0UTILITY RM 00021 10E Frame - Wood 0.20.1Garage210.0 ft² ____ 7 0 0MASTER BE 00020 10N Concrete Block - Polystyrene 0.20Exterior200.0 ft² ____ 8 0 0MASTER BE 00015 10W Concrete Block - Polystyrene 0.20Exterior150.0 ft² ____ 9 0 0M HALL 0002 10N Concrete Block - Polystyrene 0.20Exterior20.0 ft² ____ 10 13 0M HALL 0004 10E Frame - Wood 0.20.1Garage40.0 ft² ____ 11 0 0KITCHEN0002 10N Concrete Block - Polystyrene 0.20Exterior20.0 ft² ____ 12 0 0KITCHEN00012 10W Concrete Block - Polystyrene 0.20Exterior120.0 ft² ____ 13 13 0KITCHEN00014 10S Frame - Wood 0.20.1Garage140.0 ft² ____ 14 0 0SHOP00012 10E Concrete Block - Polystyrene 0.20Exterior120.0 ft² ____ 15 13 0SHOP0007 10S Frame - Wood 0.20.1Garage70.0 ft² ____ 16 0 0LIVING/DININ 00020 14E Concrete Block - Polystyrene 0.20Exterior280.0 ft² ____ 17 0 0LIVING/DININ 00020 14W Concrete Block - Polystyrene 0.20Exterior280.0 ft² ____ 9/8/2020 12:38 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 7 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT WALLS #Wall Type R-Value Area Adjacent Framing Solar Ornt Fraction Absor. HeightWidth Ft In Ft InTo Cavity Sheathing R-ValueSpace Grade% Below 18 0 0WIC 3 0004 10W Concrete Block - Polystyrene 0.20Exterior40.0 ft² ____ 19 0 0BEDROOM 3 00012 10N Concrete Block - Polystyrene 0.20Exterior120.0 ft² ____ 20 0 0BEDROOM 3 00012 10W Concrete Block - Polystyrene 0.20Exterior120.0 ft² ____ 21 0 0BATH 2 0006 10N Concrete Block - Polystyrene 0.20Exterior60.0 ft² ____ 22 0 0BEDROOM 2 00013 10N Concrete Block - Polystyrene 0.20Exterior130.0 ft² ____ 23 0 0BEDROOM 2 00012 10E Concrete Block - Polystyrene 0.20Exterior120.0 ft² ____ 24 0 0WIC 2 0004 10E Concrete Block - Polystyrene 0.20Exterior40.0 ft² ____ 25 13 0SHOP BATH 0009 10E Frame - Wood 0.20.1Garage90.0 ft² ____ 26 13 0SHOP BATH 0009 10W Frame - Wood 0.20.1Garage90.0 ft² ____ 27 13 0SHOP BATH 0006 10S Frame - Wood 0.20.1Garage60.0 ft² ____ # Ornt Panes NFRC U-Factor SHGC Area Depth Separation Int ShadeFrame Screening WINDOWS Overhang Orientation shown is the entered, Proposed orientation. Wall ID Imp 1 S Low-E Single 0.29 0.23 8.0 ft² 1 ft 0 in 1 ft 4 in NoneVinyl None______Yes3 Y 2 S Low-E Single 0.29 0.23 10.3 ft² 1 ft 0 in 1 ft 4 in NoneVinyl None______Yes4 Y 3 N Low-E Single 0.32 0.22 24.0 ft² 1 ft 0 in 1 ft 4 in NoneVinyl None______Yes7 Y 4 W Low-E Single 0.32 0.22 24.1 ft² 1 ft 0 in 1 ft 4 in NoneVinyl None______Yes8 Y 5 W Low-E Single 0.33 0.21 24.0 ft² 15 ft 0 in 1 ft 4 in NoneVinyl None______Yes12 Y 6 E Low-E Single 0.32 0.22 42.7 ft² 8 ft 0 in 1 ft 4 in NoneVinyl None______Yes14 Y 7 E Low-E Single 0.32 0.22 42.7 ft² 8 ft 0 in 1 ft 4 in NoneVinyl None______Yes16 Y 8 E Low-E Single 0.32 0.22 48.0 ft² 8 ft 0 in 1 ft 4 in NoneVinyl None______Yes16 Y 9 W Low-E Single 0.32 0.22 56.0 ft² 15 ft 0 in 1 ft 4 in NoneVinyl None______Yes17 Y 10 W Low-E Single 0.32 0.22 48.0 ft² 15 ft 0 in 1 f t 4 in NoneVinyl None______Yes17 Y 11 N Low-E Single 0.32 0.22 15.5 ft² 15 ft 0 in 1 f t 4 in NoneVinyl None______Yes19 Y 12 N Low-E Single 0.29 0.23 6.0 ft² 1 ft 0 in 1 ft 4 in NoneVinyl None______Yes21 Y 13 E Low-E Single 0.32 0.22 21.3 ft² 1 ft 0 in 1 ft 4 in NoneVinyl None______Yes23 Y # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation GARAGE 1 800 ft² 800 ft² 70 ft 10 ft 13______ Method CFM 50 ACH 50ELASLAScope INFILTRATION ACHEqLA# 2706.7 7148.6.000458Wholehouse .1758279.46Proposed ACH(50)1 9/8/2020 12:38 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 7 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT HEATING SYSTEM # System Type Efficiency Capacity DuctsSubtypeBlockSpeed 1 Electric Strip Heat/COP:1 27 kBtu/hr ______sys#1None1 # System Type Efficiency Capacity Air Flow SHR COOLING SYSTEM DuctsSubtypeBlockSubtype 1 Central Unit/SEER: 16 40 kBtu/hr 1200 cfm 0.8______sys#1Split1 Single # System Type EF Cap Use SetPnt Conservation HOT WATER SYSTEM SubType Location 1 Electric 0.98 50 gal 62.3 gal 120 deg None______None Garage FSEC Company Name System Model #Collector Model # Collector SOLAR HOT WATER SYSTEM Storage FEFCert #Area Volume None None f t ² ______ # Location R-Value Area Location Area ---- Supply -------- Return ---- Leakage Type Handler CFM 25Air QN RLF DUCTS Heat Cool HVAC # TOT OUT CFM25 1 Attic 6 175 ft² Attic 18 ft² Default Leakage Garage (Default) c______1 1 (Default) c TEMPERATURES Programable Thermostat: N Ceiling Fans: Cooling [ ] Jan [ ] Feb [ ] Mar [ ] Apr [ ] May [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec [ ] Dec [X] Dec[X] Nov [X] Nov [ ] Oct [X] Oct [ ] Sep [ ] Sep [ ] Aug [ ] Aug [ ] Jul [ ] Jul[ ] Jun [ ] Jun [X] Jun [ ] May [ ] May [ ] Apr [X] Apr [X] Mar [X] Mar [X] Feb [ ] Feb [X] Jan [ ] Jan Heating Venting Thermostat Schedule:HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD)AM PM 78 80 78 80 78 80 78 80 78 78 78 78 78 78 78 78 80 78 80 78 80 78 80 78 Cooling (WEH)AM PM 78 80 78 80 78 80 78 80 78 78 78 78 78 78 78 78 80 78 80 78 80 78 80 78 Heating (WD)AM PM 65 68 65 68 65 68 65 68 65 68 65 68 65 68 68 68 68 68 68 68 68 68 68 68 Heating (WEH)AM PM 65 68 65 68 65 68 65 68 65 68 65 68 65 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft.0 ft² 0 ft 0.3 M WIC Default(8 lbs/sq.ft.f t ² f t 0.3 M BATH Default(8 lbs/sq.ft.f t ² f t 0.3 M TOILET Default(8 lbs/sq.ft.f t ² f t 0.3 UTILITY RM Default(8 lbs/sq.ft.f t ² f t 0.3 MASTER BEDROO Default(8 lbs/sq.ft.f t ² f t 0.3 M HALL Default(8 lbs/sq.ft.f t ² f t 0.3 KITCHEN Default(8 lbs/sq.ft.f t ² f t 0.3 SHOP 9/8/2020 12:38 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 6 of 7 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft.f t ² f t 0.3 LIVING/DINING Default(8 lbs/sq.ft.f t ² f t 0.3 WIC 3 Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 3 Default(8 lbs/sq.ft.f t ² f t 0.3 BATH 2 Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 2 Default(8 lbs/sq.ft.f t ² f t 0.3 WIC 2 Default(8 lbs/sq.ft.f t ² f t 0.3 HALL Default(8 lbs/sq.ft.f t ² f t 0.3 SHOP BATH 9/8/2020 12:38 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 7 of 7 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� ����������������������������������������������������� 2017 EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 99 The lower the Energy Performance Index, the more efficient the home. 1. New home or, addition 1. __________ New (From Plans) 2. Single-family or multiple-family 2. __________ Single-family 3. No. of units (if multiple-family)3. __________ 1 4. Number of bedrooms 4. __________ 3 5. Is this a worst case? (yes/no)5. __________No 6. Conditioned floor area (sq. ft.)6. __________2251 7. Windows, type and area a) U-factor:(weighted average) 7a._________0.319 b) Solar Heat Gain Coefficient (SHGC) 7b._________0.220 c) Area 7c._________370.6 8. Skylights a) U-factor:(weighted average) 8a._________NA b) Solar Heat Gain Coefficient (SHGC) 8b._________NA 9. Floor type, insulation level: a) Slab-on-grade (R-value) 9a._________0.0 b) Wood, raised (R-value) 9b._________ c) Concrete, raised (R-value) 9c._________ 10. Wall type and insulation: A. Exterior: 1. Wood frame (Insulation R-value) 10A1.________ 2. Masonry (Insulation R-value) 10A2.________0.0 B. Adjacent: 1. Wood frame (Insulation R-value) 10B1.________13.0 2. Masonry (Insulation R-value) 10B2.________ 11. Ceiling type and insulation level a) Under attic 11a.________0.0 b) Single assembly 11b.________ c) Knee walls/skylight walls 11c.________20.0 d) Radiant barrier installed 11d.________No 12. Ducts, location & insulation level a) Supply ducts R_______6.0 b) Return ducts R_______6.0 c) AHU location Garage 13. Cooling system: Capacity_______40.0 a) Split system SEER_______16.0 b) Single package SEER_______ c) Ground/water source SEER/COP_______ d) Room unit/PTAC EER_______ e) Other __________ 14. Heating system:Capacity_______27.0 a) Split system heat pump HSPF_______ b) Single package heat pump HSPF_______ c) Electric resistance COP_______1.0 d) Gas furnace, natural gas AFUE_______ e) Gas furnace, LPG AFUE_______ f) Other 15. Water heating system a) Electric resistance EF_______0.98 b) Gas fired, natural gas EF_______ c) Gas fired, LPG EF_______ d) Solar system with tank EF_______ e) Dedicated heat pump with tank EF_____ f) Heat recovery unit HeatRec%_______ g) Other 16. HVAC credits claimed (Performance Method) a) Ceiling fans _________ b) Cross ventilation _________No c) Whole house fan _________No d) Multizone cooling credit _________ e) Multizone heating credit _________ f) Programmable thermostat _________No *Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be completed based on installed code compliant features. Builder Signature:_________________________________________Date:____________________________________ Address of New Home: ____________________________________City/FL Zip: ________________________________505 N GRAVES ROAD FORT PIERCE, FL 9/8/2020 12:40:54 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� ����������������������������������������������������� Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Project Summary Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information PRESTRIDGE RESIDENCE, COLE CONSTRUCTION SERVICES, LLC.For: 505 N GRAVES ROAD, FORT PIERCE, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh28123 Struc ture Btuh22917 Ducts Btuh6749 Ducts Btuh8021 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh34872 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh29391 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3584 Ducts Btuh2614 Central vent (0 cfm)Btuh0 CoolingHeating (none) 22512251Area (ft²)Equipment latent load Btuh6198 2499024990Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh35588 Equiv. AVF (cfm)67133 Req. total capacity at 0.70 SHR ton3.5 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR6042J1 AHRI ref Coil TEM6A0C42H41++TDR AHRI ref 8628154 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW9.6 Sensible cooling Btuh28000 Heating output Btuh32679 Latent cooling Btuh12000 Temperature rise °F22 Total cooling Btuh40000 Actual air flow cfm1333 Actual air flow cfm1333 Air flow factor cfm/Btuh0.038 Air flow factor cfm/Btuh0.043 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House M WIC 2 Exposed wall 204.0 ft 17.0 ft 3 Room height 11.1 ft 10.0 heat/coolft 4 Room dimensions ft7.0x10.0 5 Room area 2251.0 ft²70.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 550 504 2585 1606 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 6 0 54 56 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 16 0 140 147 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 24 0 215 226 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 560 405 2077 1291 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 107 0 956 2767 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 48 0 430 1245 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 280 262 1340 833 70 70 359 223 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 8 8 72 75 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 10 10 93 98 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 810 658 3370 2094 100 100 512 318 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 24 0 215 623 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 24 0 217 629 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 56 0 502 1453 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 48 0 430 1245 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2251 2251 3569 3080 70 70 111 96 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2251 204 7757 0 70 17 646 0 6 c) AED excursion 0 -25 Envelope loss/gain 24022 17468 1628 612 12 a) Infiltration 4101 1099 317 85 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 4350 0 Subtotal (lines 6 to 13)28123 22917 1945 697 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 28123 22917 1945 697 15 Duct loads 24%35%6749 8021 24%35%467 244 Total room load 34872 30938 2412 941 Air required (cfm)Air required (cfm)1333 1333 92 41 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH M TOILET 2 Exposed wall 7.0 ft 6.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft106.0x1.0 ft6.0x4.0 5 Room area 106.0 ft²24.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 70 62 318 197 60 50 254 158 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 8 8 72 75 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 10 10 93 98 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 106 106 168 145 24 24 38 33 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 106 7 266 0 24 6 228 0 6 c) AED excursion -26 -2 Envelope loss/gain 824 392 614 287 12 a) Infiltration 130 35 112 30 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 0 Subtotal (lines 6 to 13)954 727 725 317 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 954 727 725 317 15 Duct loads 24%35%229 254 24%35%174 111 Total room load 1183 981 899 428 Air required (cfm)Air required (cfm)45 42 34 18 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 3 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name UTILITY RM MASTER BEDROOM 2 Exposed wall 8.0 ft 35.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft190.0x1.0 ft278.0x1.0 5 Room area 190.0 ft²278.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 200 176 902 560 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 24 0 215 226 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 80 80 410 255 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 150 126 644 400 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 24 0 217 629 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 190 190 301 260 278 278 441 380 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 190 8 304 0 278 35 1331 0 6 c) AED excursion -36 137 Envelope loss/gain 1015 478 3750 2334 12 a) Infiltration 149 40 652 175 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 500 1000 Subtotal (lines 6 to 13)1165 1018 4403 3508 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 118 50 59 25 14 Subtotal 1283 1069 4462 3534 15 Duct loads 24%35%308 374 24%35%1071 1237 Total room load 1591 1443 5533 4770 Air required (cfm)Air required (cfm)61 62 211 206 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 4 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M HALL KITCHEN 2 Exposed wall 2.0 ft 14.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft8.0x4.0 ft20.0x12.0 5 Room area 32.0 ft²240.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 20 20 102 64 20 20 102 64 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 120 96 492 306 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 24 0 215 623 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 32 32 51 44 240 240 381 328 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 32 2 76 0 240 14 532 0 6 c) AED excursion -4 190 Envelope loss/gain 229 103 1722 1511 12 a) Infiltration 37 10 261 70 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1600 Subtotal (lines 6 to 13)267 113 1983 3181 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -267 -113 89 38 14 Subtotal 0 0 2072 3218 15 Duct loads 24%35%0 0 24%35%497 1126 Total room load 0 0 2569 4345 Air required (cfm)Air required (cfm)0 0 98 187 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 5 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name SHOP LIVING/DINING 2 Exposed wall 12.0 ft 40.0 ft 3 Room height 10.0 heat/coolft 14.0 heat/coolft 4 Room dimensions ft13.0x12.0 ft31.0x20.0 5 Room area 156.0 ft²620.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 120 77 396 246 280 189 970 603 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 43 0 382 1107 43 0 382 1107 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 48 0 430 1245 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 280 176 902 560 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 56 0 502 1453 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 48 0 430 1245 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 620 620 983 848 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 12 456 0 620 40 1521 0 6 c) AED excursion 81 -231 Envelope loss/gain 1482 1647 6120 6830 12 a) Infiltration 224 60 1044 280 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 200 Subtotal (lines 6 to 13)1706 1707 7164 7310 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 35 29 14 Subtotal 1706 1707 7199 7339 15 Duct loads 24%35%409 598 24%35%1728 2569 Total room load 2115 2305 8926 9907 Air required (cfm)Air required (cfm)81 99 341 427 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 6 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC 3 BEDROOM 3 2 Exposed wall 4.0 ft 24.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft8.0x4.0 ft12.0x12.0 5 Room area 32.0 ft²144.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 120 104 535 332 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 16 0 140 147 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 40 40 205 127 120 120 615 382 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 32 32 51 44 144 144 228 197 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 32 4 152 0 144 24 913 0 6 c) AED excursion -7 -56 Envelope loss/gain 408 165 2430 1002 12 a) Infiltration 75 20 447 120 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 450 Subtotal (lines 6 to 13)482 185 2878 1572 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 8 10 8 14 Subtotal 492 193 2888 1580 15 Duct loads 24%35%118 67 24%35%693 553 Total room load 610 260 3581 2133 Air required (cfm)Air required (cfm)23 11 137 92 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 7 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 BEDROOM 2 2 Exposed wall 6.0 ft 25.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft6.0x12.0 ft141.0x1.0 5 Room area 72.0 ft²141.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 60 54 277 172 130 130 666 414 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 6 0 54 56 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 120 99 506 314 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 21 0 191 553 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 72 72 114 99 141 141 224 193 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 6 228 0 141 25 951 0 6 c) AED excursion -12 13 Envelope loss/gain 673 315 2537 1488 12 a) Infiltration 112 30 466 125 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)785 345 3003 1613 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 15 12 10 8 14 Subtotal 799 357 3013 1621 15 Duct loads 24%35%192 125 24%35%723 567 Total room load 991 482 3736 2188 Air required (cfm)Air required (cfm)38 21 143 94 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 8 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC 2 HALL 2 Exposed wall 4.0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft9.0x4.0 ft14.0x4.0 5 Room area 36.0 ft²56.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 8.968.96 9.419.41 0 0 0 0 0 0 0 0 11 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 40 40 205 127 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 8.968.96 9.419.41 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 8.968.96 25.9425.94 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 36 36 57 49 56 56 89 77 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 36 4 152 0 56 0 0 0 6 c) AED excursion -7 -3 Envelope loss/gain 414 170 89 74 12 a) Infiltration 75 20 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)489 190 89 74 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 8 -89 -74 14 Subtotal 499 198 0 0 15 Duct loads 24%35%120 69 24%35%0 0 Total room load 618 267 0 0 Air required (cfm)Air required (cfm)24 12 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-08 12:00:31 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 9 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 08, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name SHOP BATH 2 Exposed wall 0 ft 3 Room height 10.0 heat/coolft 4 Room dimensions ft6.0x9.0 5 Room area 54.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 .G 2 glazing, clr low-e 0.320 n 8.96 9.41 0 0 0 0 .G 2 glazing, clr low-e 0.320 n 8.96 9.41 0 0 0 0 .G 2 glazing, clr low-e 0.320 n 8.96 9.41 0 0 0 0 11 W 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 G 2 glazing, clr low-e 0.320 e 8.96 25.94 0 0 0 0 G 2 glazing, clr low-e 0.320 e 8.96 25.94 0 0 0 0 W 13AB-0fcs 0.183 s 5.12 3.18 0 0 0 0 G 2 glazing, clr low-e 0.320 s 8.96 9.41 0 0 0 0 G 2 glazing, clr low-e 0.320 s 8.96 9.41 0 0 0 0 W 13AB-0fcs 0.183 w 5.12 3.18 0 0 0 0 G 2 glazing, clr low-e 0.320 w 8.96 25.94 0 0 0 0 G 2 glazing, clr low-e 0.320 w 8.96 25.94 0 0 0 0 G 2 glazing, clr low-e 0.320 w 8.96 25.94 0 0 0 0 G 2 glazing, clr low-e 0.320 w 8.96 25.94 0 0 0 0 C 16X19-0md 0.408 -1.59 1.37 54 54 86 74 F 22A-tph 1.358 -38.02 0.00 54 0 0 0 6 c) AED excursion -13 Envelope loss/gain 86 61 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 300 Subtotal (lines 6 to 13)86 361 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 86 361 15 Duct loads 24%35%21 126 Total room load 106 487 Air required (cfm)4 21 2020-Sep-08 12:00:37 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary Sep 08, 2020Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information PRESTRIDGE RESIDENCE, COLE CONSTRUCTION SERVICES, LLC.For: 505 N GRAVES ROAD, FORT PIERCE, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1333cfm1333 Total effective length (TEL)ft217 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st5155.055.8VlFx0x05.01.0002138991hBATH 2 st5155.062.5VlFx0x07.01.000941433736hBEDROOM 2 st5155.061.6VlFx0x07.01.000921373581hBEDROOM 3 st2115.029.7VlFx0x07.01.00094492172cKITCHEN st2115.023.1VlFx0x07.01.00094492172cKITCHEN-A st4135.040.3VlFx0x08.01.0001421143303cLIVING/DINING st4135.034.0VlFx0x08.01.0001421143302cLIVING/DINING-A st4135.041.3VlFx0x08.01.0001421143302cLIVING/DINING-B st1115.011.8VlFx0x06.01.00042451183hM BATH st1115.016.1VlFx0x04.01.0001834899hM TOILET st3135.026.0VlFx0x06.01.00041922412hM WIC st1115.014.8VlFx0x07.01.0001031062766hMASTER BEDROOM st3135.027.5VlFx0x07.01.0001031062766hMASTER BEDROOM-A st2115.024.8VlFx0x07.01.00099812305cSHOP st2115.025.0VlFx0x05.01.000214487cSHOP BATH st1115.012.2VlFx0x06.01.00062611443cUTILITY RM st5155.058.1VlFx0x04.01.0001224618hWIC 2 st5155.058.1VlFx0x04.01.0001123610hWIC 3 2020-Sep-08 12:00:37 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...umnets\Wrightsoft HVAC\PRESTRIDGE RESIDENCE.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 365 230 1.000 668 10.0 0x0 VinlFlx st4 st4 Peak AVF 706 657 1.000 899 12.0 0x0 VinlFlx st2 st2 Peak AVF 889 964 1.000 690 16.0 0x0 VinlFlx st3 Peak AVF 198 143 1.000 567 8.0 0x0 VinlFlx st1 st1 Peak AVF 444 369 1.000 814 10.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 13330 1333 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������