HomeMy WebLinkAboutEngineering ENGINEERING =- EXPPESS° I , Order(Ref)#: (44073-6596875000) Project Details: HAFT CONDO DOOR REPLACEMENT i Contractor: J&G CARPENTRY, INC. 9490 S. OCEAN DRIVE, UNIT 716A 7030iS.W. 16TH COURT PEMBROKE JENSEN BEACH, FL PINES, FL Subject: Wind Load Design Pressure Calculations (Components &Cladding) Site Information General Calculation Building Classification: enclosed Directionality Factor(Kd): 0.85 Wind Speed (V„lt): 170 mph Gust-Effect Factor(G): 0.85 Exposure Category: d Internal Pressure Roof Type: monoslope Coefficient(GCP;): ±0.18 Roof Slope (0): 1.2 deg Topographical Factor(Kzt): 1.0 Mean Roof Height (h): 88.0 ft Velocity Pressure Exposure K Min. Building Dimension (L): 53.0 ft Coefficient( n): 1.40 Parapet>_3 feet? No Velocity Pressure (qh): 88.13 psf End Zone (a): 5.3 ft ASD Method: P=0.6w Mark Qty Elev(ft) Size:W x H (in) Zone Shutter. Area (ft) Kz(Kh) q z(q h) GCP+ GCP_ Pressures (psf) 1 (1) 58.0 36.0 x 80.0 4 No 20.0 1.30 81.97 0.90 -0.90 +53.8/—57.1 IIII \\ WRD NOTES:Design is in accordance with ASCE 7-10(ASD method)and the Florida Building Code Sixth Edition(2017).ReQ 6488 are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering Express: Valid Only VrY�' h Raised/Sf Wei Results are based on contractor-supplied data and shall be field verified by others prior to use.Selection&installatia¢p? Engineer Seal products shall be approved using these dimensions and pressures as verified by others. `0 S o > C1F P, \� Note:For openings to be properly rated in Zone 4,no part of the opening shall be within 5.3 feet of any building corner. 1\'P\020 This engineer has not field visited this location and if this cannot be clearly identified by others,the opening shall be re- 1 evaluated prior to installation of any fenestration. All other information provided above including mean roof height, tl eet, P.E. building minimum dimensions,opening sizes,&other supporting data was provided by others. For definitions of the E86488 above terms,visit EngineeringExpress.com/Wiki" #9885 64791(44029-4604745370) PHONE:(954)354-0660—FAX:(954)354-0443 AutoPrint ENGINEERINGEXPRESS.COM PAGE 1 OF 1 I I