DATE TESTED:KSM JOB # :204448-1pd/CF/jo
CONTRACTOR:JM Custom Pools PERMIT #:2006-0895
JOB LOCATION:3411 S. Indian River Drive NUC #234
Fort Pierce, Florida Nuc Model:MC-DR
P.O. # : Nuc Serial #:MD60308234
ITEM TESTED :Pool Backfill Compaction
TEST LOCATION
OF SAMPLE DEPTH PEN
READ
DRY
DENSITY
MAX. DRY
PROCTOR VALUE
PERCENT
COMPACTION
1 South 0'-1'45 103.1 106.0 97.3%
2 1'-2'50+-"95.0% +
3 2'-3'50+-"95.0% +
4 3'-4'50+-"95.0% +
5 Northwest 0'-1'45 102.4 106.0 96.6%
6 1'-2'50+."95.0% +
7 2'-3'50+-"95.0% +
8 3'-4'50+-"95.0% +
9 Northeast 0'-1'45 104.1 106.0 98.2%
10 1'-2'50+-"95.0% +
11 2'-3'50+-"95.0% +
12 3'-4'50+-"95.0% +
Soil Description:
Light Brown Sand
In Place Moisture:
6.1%
Proctor Optimum Moisture:
12.0%
Proctor Max. Dry Density: P.C.F.
106.0
@ Test Locations the Density &
Penetrometer reading indicate the
Degree of Compaction Meets
Minimum Requirement
for Plumbed Backfill
Respectfully Submitted:
Bryan E. Dahlke, P.E.
V.P. of Engineering
PE # 81439 9/14/2020
Email to: St Lucie Building Department; jmcustompoolsinc@gmail.com
SOIL COMPACTION REPORT
ASTM D 1557 and ASTM D 6938
September 11, 2020
Disclaimer:Contractor is responsible to maintain
the pool backfill in the condition that KSM
completed the indicated passed compaction test.
KSM is not responsible if the poolbackfill has been
altered from the approved inspected condition.
Proudly Serving Florida since 1990