HomeMy WebLinkAboutProject Information® Project Summary Job: Jun 03, 2019 +� wrightsoft Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM Project Information For. TESTA RESIDENCE FORT PIERCE, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 33147 Btuh Ducts 8870 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 42017 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ft2) 2625 2625 Volume (ft3) 29286 29286 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 156 78 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating Input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 11.8 kW 40312 Btuh 4 0 1550 cfm 0.037 cfm/Btuh 1.00 in H2O Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 23468 Btuh Ducts 12315 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 33994 Btuh Latent Cooling Equipment Load Sizing Structure 3262 Btuh Ducts 3488 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 6750 Btuh Equipment Total Load (Sen+Lat) 40744 Btuh Req. total capacity at 0.70 SHR 4.0 ton Cooling Equipment Summary Make Carrier Trade 16 SEER AC Cond CA16NA04800GOA0 Coil FX4DNF061L AH R I ref 9200322 Efficiency 13.0 EER, 16 SEER Sensible cooling 32550 Btuh Latent cooling 13950 Btuh Total cooling 46500 Btuh Actual air flow 1550 cfm Air flow factor 0.043 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.84 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -� wrightsoft® 2019-Jun-03 14:32:27 Right -Suite® Universal 2018 18.0.31 RSU08101 Page 1 �` E:\Documnets\wrightsoft HVAC\TESTARESIDENCE.rup Calc = MJ8 Front Door faces: E +�- wrightsoft Right-J® Worksheet Job: Entire House Date: Jun 03, 2019 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Eposed wall Room height Room dimensions Room area Entire House 256.0 ft 11.2 ft 2625.0 ft' M BATH 43.0 ft 10.0 ft heaticool 1.0 x 234.0 ft 234.0 ft2 Ty Construction number U-value (Btuh/ft' °F) Or HTM (Btuh/ft2) Area (ftj or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A 7:5fcs ' `, 2 glazing, clr low-e 2glazing, clrlbw-e 2 glazing; clr'low-e• 2 glazing, clr low-e 2 glazing, clr low-e 2,glazing,.cir_lawae_ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 11DO 13A-7.5fcs 2 glazing, olr low-e 2 glazing, clr low-e 2 glazing, clr low-e. ,' 2 glazing,. clr low-e ° ' 11D0 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 plazina, dr low a 16A-30md� _� __ _22A-tPh 0:083 0.650 0.650 0.650 0:650 0.650 0.650 0.083 0.650 0.650 0.390 0.083 0.650 0.650 0.656 0.650 0.$90 0.083 0.650 0.650 0.650 0_650 0.032 1;358 ' ' n n n'' n n n- _ n_ a a a e s s s s s„ -a- w w w w w - _ _ 18.20 118.20 18.20 48.20 18.20 . 18.20, 2.32 18.20 18.20 y 10.992 m 2.32- 18.20 18.20 18.20 18.20 - 1Q92 2.32 18.20 18.20 18.20 18.20 _LL 0.90. 38 02 - 1.10 14.99 14.99 14.99 14`.99 13.26 -'-' 10.68 1.10 14.91 14.66 10.34 1.10 . `' 14.99 " 13.26 '10.68 ' %68 10._3.4 1.10 32.65 10.68 10.68 14 66 _ - -2 24 ,_,_,._ 0 Qo 830 . 6 16 : 45 72 - .. 48 __12 598 36 36 24 862 ` ' . 48 96 12 ' 54 24 631 0 0 0 0 0 _____0 502 32 22 24 828 48 96 12 54 _1466 109 291 Big, 1310 874 218 1167 655 655 262 1459 874 1747 218, 983 'T'_ 697 90 240 675 ' 1079 636 ___128 128 554 537 528 _ 248 693 720 1273 128 577 248 140 6 0 0 01 0 __12 ---TO O 0 0 0 0 0 __0 _.,_ _0 . 284 109 0 0 0 0 "_218. 0 0 0 0 158 0 0 218 0 y y 135 90' 0 0 0 0 -- 128. 0 0 0 0 75 0 0 128 0 . W 0 0 0 �_ 0 80 0 0 12 0 0 0 0 0 68 0 0 12 0 0. _ _ _ W 510 36 20 15 36 2625 _ � _2625 __24 403 2 20 15 22 . v,-2625 , 256 __..._.._252 937 655 364 273 _ 655 '.~___ 2352 _,_9734 445 1175 214 160 _ 528 ______5880 �' _.0 210 0 20 15 0 175 0 20 15 -_0 407 0 364 273 0 ,_._:_v_w0 193 0 214 160 0 _ C ` F . - 234 �0 � .,v.�23g ._ _,_210, _ r'_ .524 6 c) AED excursion 678 510 Envelope loss/gain 28341 1813013876 2157 12 a) Infiltration b) Room ventilation 4806 0 1287 0 738 0 198 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 4050 0 0 0 Subtotal (lines 6 to 13) 33147 23468 4614 2355 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 52% 0 0 0 33147 8870 0 0 0 23468 12315 27% 40% 0 0 0 4614 1235 0 0 0 2355 942 Total room load Air required (cfm) 42017 1550 35783 1550 5849 216 3297 143 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. +�f- war➢gFvtscwt- 2019-Jun-0314:32:27 �A ""'�" Right -Suite® Universal 2018 18.0.31 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\TESTARESIDENGE.rup Calc = MJ8 Front Doorfaces: E +�- wrightsoft° Right-JO Worksheet Job: Entire House Date: Jun 03, 2019 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@40L.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area M TOILET 3.0 ft 10.0 ft heat/cool 3.0 x 9.0 ft 27.0 ft2 BATH 2 5.0 ft 10.0 ft heat/cool 5.0 x 9.0 ft 45.0 ft2 Ty Construction number U-value (Btuh/ft' °F) Or HTM (Btuh/ft� Area (ft5 or perimeter (ft) Load (Btuh) Area (ft5 or perimeter (ft) Load (Btuh) Heat I Cool N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A-7.5fcs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 2.glazing,-clr-loWze_ 13A 7.5fcs 2 glazing, clr low-e 2 glazing, cir low-e 11D0 _ _ 13A-7.5fcs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 11D0 13A-7.5fcs 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e 2 glazinq, clr low-e 16A,3.0md __._ .22A-toh 0.083 0.650 0.650 0.650 0.650 0.650 --_0.650 0.083 0.650 0.650 _ 0.390 0.083 0.650 0.650 0.650 0.650 0.3.90 0.083 0.650 0.650 0.650 0.650 _�0.032 - - 1,358 _n n n n n n -n_ a a a -e _ s s s s s _ s w w w w _w , �, --_... - 2.32 18.20 18.20 18.20 18.20 18.20 -_:18,2Q 2.32 18.20 18.20 10,92 2.32 18.20 18.20 18.20 18.20 _ 10.92 2.32 18.20 18.20 18.20 _-,18.20 - __0.90. _38,02 1.10-- 14.99 14.99 '14.99 14.99 93:26 , 10;68 1.10 14.91 14.66 w_10,34 1.10 '14.99 13.26 10.68 .10.68 10.34 [Gros. 30 0 8 0 0 0 -______0 0 0 0 __ 0 - -0 0 0 0 0 0 -- 22 0 0 0 0 0 ____0 0 0 0 _ 0 _ 0 0 0 0 0 0 -- -- 51 0 146 0 0 0 .-_ _._..,. 0 0 0 0 0 - �' 0 0 0 0 0 ___--0 0 0 0 0 0 _ _ ,24 ___114 R -- 24 0 120 0 0 0 _- 0 0 0 0 0 -- 50 0 8 0 0 0 -_-._-0 0 0 0 0 - ---42 0 0 0 - 0- 0 ___,-_-__,0 0 0 0 m0 �~ 0 0 0 0 0 0 - --- 98 0 146 0 0 0 _ _.____0 0 0 0 -_ - 0 0 0 0 0 0 _ f--_Q 0 0 0 0 - _-0 - 40. -- - 46 0 120 0 0 0 „__--0 0 0 0 _ _ 0 0 0 0 0 0 0 0 0 0 0 . _ 101 -- - 0 -- - WI - i _ - 0 0 0 0 0 0 0 0 0 0 _ 0 �60 _ 0 _ - 0 0 0 0 0 0 0 0 0 0 _ -0 45 W 1.10 32.65 10.68 10.68 14.66 �2.24 _ 0.00 0 0 0 0 0 7 -T __27 _-_ 0 0 0 0 �0 ___ 27 3 _ 0 0 0 0 _ - 0 45 _ -F__ 45 5 190 6 c) AED a)cursion -6 -8 Envelope loss/gain 335 199 474 259 12 a) Infiltration b) Room ventilation 51 0 14 0 86 0 23 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 3M 212 559 282 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 0 386 103 0 0 0 212 114 27% 54% 0 0 0 559 150 0 0 0 282 152 Total room load Air required (cfm) 490 18 327 14 709 26 434 19 Calculations approved byACCA to meet all requirements of Manual J 8th Ed A&- wr1gtZtsoft- Right-Suite® Universal 2018 18.0.31 RSU08101 2019-Jun-03 1 Page 2 E:\Documnets\Wrightsoft HVAC\TESTA RES] DENC E.rup Calc = MJ8 Front Door faces: E +�- wrightsoft° Right-M Worksheet Job: Entire House Date: Jun 03, 2019 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BEDROOM 2 22.0 ft 10.0 ft heat/cool 1.0 x 220.0 ft 220.0 ftz M WIC 0 ft 10.0 ft heat/cool 1.0 x 128.0 ft 128.0 ft2 Ty Construction number U-value (Btuh!W °F) Or HTM (Btuh/ft� Area (ft� or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 - 13A-7.Sfcs . - 2 glazing,. clrlow-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2,glazing,_Gr low-e_-_ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e -11_DO - _ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 11 D0 _ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e _2 S1lazino, clr low-e 16A 30md_ r_ 22A_tph_` _ - 0.083 0.650 0.650 0.850 0.650 0.650 .__0.650 0.083 0.650 0.650 _ 0.390 - 0.083 0.650 0.650 0.650 0.650 .------ 0 390 n - n n n n n -,_.n_ a a a a s s s s s s __ 2.32 18.20 18.20 18.20 18.20 18.20 18.20, 2.32 18.20 18.20 1.0.92 2.32' 18.20 18.20 18.20 18.20 _ 10.92 2.32 18.20 18.20 18.20 18.20 __0.90- _ 38.02 -' 1.10 14.99 14.99 '14.99 14.99 13.26 - 10.68 1.10 14.91 14.66 10.34 1.10 ' 14.99 13.26 10.68 •10.68 10.34 1.16 32.65 10.68 10.68 - 14.66 _-.2.24 _ 0.00 140 0 0 45 0 0 --_--0 50 0 0 �_� �._0 _0 0 0 0 0. _____0 30 0 0 0 _ 0 220 _.._220 __._ 85 0 0 0 0 0 ----0 50 0 0 ---_-- 0 0 0 0 0 0 . -._ _._0 30 0 0 0 -.-� 0 -.�__220 _-,-_-22 -_ 221. 0' 0 819 0 0 -__ - 0 116 0 0 0 105 0 0 675 0 0 ­_0 0 0 0 0 0 ------0 0 0 0 .---_ M� 0 0 0 0 0 - _-_O 0 0 0 0 0 _____ O D 0 0 0 0, -----0 0 0 0 -�r- 0 0 0 0 0 .-'-.---0 0 0 0 0 0 _O 0 0 0 .0 0 --- �. 0 0 0 _0 0 0 0 0 -_ _ ._- -A,-- 0 0 0 0 _ _ 0 �' 1.15 - --0 0 0 0 0 0 -------0 0 0 0 _ --0 0 0 0 0 .__-._Q 0 0 0 0 y_ __287 - - ---0. _ . W I--G --0 55 0 0 0 -- _ D, W _ _C'_ F --- 0 0 0 0 0 ______0 70 0 0 0 - 0 _ 997. 837 0 0 0 0 0 ----0 33 0 0 0 0 0.083 0.650 0.650 0.650 0.650 0.032 ._ 1.35_8 w w w w _ _w- _-- �._ _ 493 0 _ _ _, _ 128 128 ___ _____-_ 128 0 6 c) AED excursion -48 -8 Envelope loss/gain 2259 13121 115 279 12 a) Infiltration b) Room ventilation 378 0 101 0 0 0 0 0 13 Intemal gains: Occupants @ 230 Appliances/other 0 0 250 0 0 0 Subtotal (lines 6 to 13) 2637 1663 115 279 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 14 2651 709 0 0 35 1698 915 27% 54% 0 0 8 123 33 0 0 20 299 161 Total room load Air required (cfm) 3361 124 2613 113 156 6 460 20 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - A- wright .Cwt- C 2019-Jun-03 14:32:27 .CA Right -Suite® Universal 2018 18.0.31 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\TESTA RES[ DENCE.rup Calc = MJ8 Front Door faces: E +Id- wrightsoft° Right-JO Worksheet Job: Entire House Date: Jun 03, 2019 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@�40L.COM 1 2 3 4 5 Room name E)q=ed wall Room height Room dimensions Room area MASTER BEDROOM 39.0 ft 10.0 ft heat/cool 21.0 x 18.0 ft 378.0 ft' HALLWAY 0 ft 10.0 ft heat/cool 15.0 x 4.0 ft 60.0 ftz Ty Construction number U-value (Btuh/ft;°F) Or HTM (Btuh/ft� Area (ft� or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 T '13A-7.5fcs - 2 glazing, dr low-e 2glazing, clriow-e 2 glazing, clr low-e 2,glazing, clrlow-e 2glazing, cirlow-e 2.glazing,-cir lcw:e_- 13A 7.5fcs glazing, cir low-e 2 glazing, cir low-e -11 DO� ^-_ 13A-7.5fos 2 glazing, clr l w-e 2glazing, dr,low-e 2 glazing, dr low-e 2 glazing, clr low-e 11DOv 13A-7.5fcs 2 glazing, cir low-e 2 glazing, clr law-e 2 glazing, clr low-e 2 giazinq, cir low_-e _16A130md' L 22A-tPh- 0. 883 0.650 0.650 0.650 0.650 0.650 -0.650 0.083 0.650 0.650 _- 0.390 0.083 0.650 0:650 0.650 0.650 ___ 0.390 0.083 0.650 0.650 0.650 0;650 _ 0.082 _ 1.358 n n n n n n .-n- a a a e s s s s s s- w w w w w =_ 18.20 18.20 18.20 18.20 18.20 18.2Q 2.32 18.20 18.20 _. _ 10_92 2.32 18.20 18.20 18.20 18.20 ..__ 10.92 2.32 18.20 18.20 18.20 _ 18.20 _0.90 38.02 '' 14.99 14.99 14.99 14.99 13:26 _._. 10.68 1.10 14.91 14.66 10.34 ^ 1.10 14.99 13.26 10.68 10.68 _ 10.34 1.10 32.65 10.68 10.68 14._66 w224 , 0.00 0 0 0 0 0 0 0 0 0 0 210 48 0 0- 0 --- -0 180 36 0 0 _ 0 - 378 ___-378 0 0 0 0 0 -__.___.0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 , 0 0 0 0 0 0 0 0 0 0 _ _ -_0 0 0 0 0 0 0 6 0 0 _ _0 0 0 0 0 0 0_ 0 0 _-__a 0 0 0 --- 0 0 0 0 0 0 -- --0. 0 0 0 0 0 54. 0 0 0 0 0 0 0 0 0 --- - - 0- 0 0 0 0 0 ------- ___0 0 0 0 0 __- 0 --___ 134 __ ___ 0 . W _-_-___0 0 0 0 0 _La2 - 162 48 0 0 0 0 144 2 0 0 0 __378 . ,39 - - 376 874 0 0 0 _w_--0 335 655 0 0 - _ 0 -__ 339 1483 --- 179 720 01 0 0 ____0 159 1175 0 0 0 0 0 0 0 0 0 0 0 0 0 0 - ---0 0 0 0 0 0 ___0 0 0 0 0 0 _ W C_- F __- _____-847 0 --__60 60 ` 80 0 6 c) AED exursion 309 4 Envelope loss/gain 4062 3388 54 131 12 a) Infiltration b) Room ventilation 669 0 179 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliancestother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 4731 3567 54 131 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 13 4744 1269 0 0 32 3599 1939 27% 54% 0 0 -54 0 0 0 0 -131 0 0 Total room load Air required (cfm) 6014 2221 5538 240 0 0 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed +�- wrigF%tsoft- �P. Right -Suite® Universal 2018 18.0.31 RSU08101 2019-Jun-03 14:Page 4 ge 4 E:\Documnets\Wrightsoft HVACITESTA RESIDENCE.rup Calc = MJS Front Dcor faces: E +� wrightsoft° Right-M Worksheet Job: Entire House Date: Jun 03, 2019 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 2 3 4 5 Room name FVosed wall Room height Room dimensions Room area CLST 2 O ft 10.0 ft heaticool 2.0 x 6.0 ft 12.0 ft' HALF BATH O ft 10.0 ft heat/cool 6.0 x 6.0 ft 36.0 ft' Ty Construction number U-value (Btuh/f? °F) Or HTM (Btuh/ft� Area (ft� or perimeter (ft) Load (Btuh) Area (ftj or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat I Cool 6 11 __. 13A 7.Sfcs ` 2 glazing, dr low-e 2 glazing, clrlaw-e 2 glazing, clr low-e 2 glazing, dr low-e 2 glazing, clr low-e 2.glazing, clr low-e__ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 11DO -13A-7.5fcs 2 glazing, clr low-e 2 glazing, clrlow-e 2 glazing, Grlow-e 2 glazing, cir low=e 11D0.._.__.-. 0083 0.650 0.650 0.650 0.650 0;650 0.650 0.083 0.650 0.650 0..-390 -n n n n n n -.._n_ a a a -e s s: s s s _ 2:32 18.20 18.20 18.20; 18.20 18.20, 18.20 2.32 18.20 18.20 10_92 2.32 18.20 18.2-0 18.20 18.20 10:92 2.32 18.20 18.20 18.20 _^18.20 -0,90 38.02 1.10 14.99' `. 14.99 %99 %99 13.26 .v_ 10.68 1.10 14.91 14.66 _ 10.34 1'.10 14.99 13.26 10.68 10.68 __.10..34 1.10 32.65 10.68 10.68 14.60 u2.24 0.00 " 0 0 0 0 0 0 ----_-0 _.M : 0 0 0 0 0 0 ----._0 0 0 0 0 _�- 0 0 0 0 0 --_----0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -_---0 0 0 0 0-- 0_._.-._.;0 0 0 0 0 0 ----0 0 0 0 0--.--- 0 0 0 0 0 _____0 0 0 0 0 0 0 0 0 0 .--i.._0 0 0 0 0 0 0 0 0 0 D __-------0 0 0 0 ____0 0 0 0 0 0 _ Q. 0 0 0 0 0 W 0 0 0 0 - 0 0 0 0.083 0:650 0.650 0.650 0.650 0 390. _,_ 0 . 0 0 0 0 0 0 0 0 0 0 ___ ' 0 0 0 0 0 ___--0 0 0 0 0 0 T 0 0 0 0 0 ____-____0 0 0 0 0 0 __ �0 0 0 0 0 0 _0 0 0 0 0 0 _ 0 0 0 0 0 0 0 - 0 0 0 0 ._._..__0 0 0 0 0 ._ W _ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, dr low-e 2 glazing, clr low-e _2_glazinp, dr (Mw _ a16A 30md��.� 22A_tph _ _ 0.083 0.650 0.650 0.650 _ 0 650 0,032 1.358 ,ems_ w w w w w _ - . 0 0 0 0 0 C� _ F �. 12 _____., 12 _ 12 0 -_-.. 11: 0 -T 27 0 _ _ ��36 36 _0 36 0 _� ---. �_-32 0 - -- 81, -__ _ 0 _ 6 c) AED excursion -1 -2 Envelope loss/gain 11 26 32 78 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliancestother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 11 26 32 78 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 50. 0 0 -11 0 0 0 0 -26 0 0 27% 54% 0 0 17 49 13 0 0 41 120 64 Total room load Air required (cfm) 0 0 0 0 62 2 184 8 Calculations approved byACCA to meet all requirements of Manual J 8th Ed 2019-Jun-03 14:32:27 Right -Suite® Universal 2018 18.0.31 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\TESTA RES]DENCE.rup Calc = MJ8 Front Door faces: E +Id- wrightsoft° Right-JO Worksheet Job: Entire House Date: Jun 03, 2019 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@}\OL.COM 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area OFFICE 23.0 ft 10.0 ft heat/cool 17.0 x 15.0 ft 255.0 ft' FOYER 18.0 ft 10.0 ft heat/cool 9.0 x 9.0 ft 81.0 W Ty Construction number U-value (BtuWftk*F) Or HTM (Btuh/ft� Area (ft� or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat cool 6 11 -- --- U. M 0.650 0.650 0.650 0.650 0:650 -_--__0.650.-n._. 0.083 0.650 0.650 . -.0.390' 0.083 0.650 0.650 0.650 0.650 _ 0.390 0.083 0.650 0.650 0.650 __--- 0.650 0.032 ___ ._358 _ r n n n n n a a a e._ s s s s s - s- w w w w w_ -� _ T - ' 2.32 18.20 18.20 18.20 18.20 18.20 - 16.20 2.32 18.20 18.20 0.92 __.1. 2.32 18.20 18.20 18.20 18.20 ---10.-92 2.32 18.20 18.20 18.20 18.20 �._0.90 _A_ 38.02 1.10 14.99 14.99 14.99 14.99 13.26 10.68 1.10 14.91 14.66 V- 10.34 1:10 14.99 13.26 10.68 10.68' -_ 10.34 1.10 32.65 10.68 10.68 - 14.66 _ _ 224 __--0_00 - - 170 0 0 0 36 0 J__-_0.__. 60 0 0 __ _ 0 _ 0 0 0 0 0 ----_-0 0 0 0 0 -.0 , 255 - - �134 0 0 0 0 0 ---0 60 0 0 ...___ _�0 0 0 0 0 0 0 0 0 0 0 .- 0 _-255 __- ___23 - 311 0 0 0 655 0 --_--_0 139 0 0 _._ 0 0 0 0 0 0 0 0 0 0 0 ._._ ___ 0 _-__228 __ 875 - -- 125 0 0 0 _ 655 0 153 0 0 -- -262 0 0 0 0 -------•0 0 0 0 0 0. - -- 60 0 0 0 540 D 73 0 0 v----248 0 0 0 0 0 ---- -0 0 0 0 0 . _- 0 _ _ ----- 0 13A-7. Sfcs - -- 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2.glazing,_Gr-low--e_ 13A 7.5fcs 2 glazing, clr low-e 2 glazing, cir low-e 11D0-----__-__� 13A7.5fos 2 glazing, Gt low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 11D0------_ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr lower_ 16Q-36md _ 226toh - -_ i 148 0 0 0 540 0 --_-0 66 0 0 ___ 0 0 0 0 0 0 0 - - 90 0 0 0 36 0 90 0 0 ---- - 24 0 0 0 0 , _ _0 0 0 0 0 ._--- 0 81 - -"- 64 0 0 0 0 0 66 0 0 ___-_24 0 0 0 0 _-._._-0 0 0 0 0 _0 _ _81 _- --- 18 - W W - W _ 0 0 0 0 ._ _.--_ 0 57.1 _____0 ___ - C __ F 684 --r_ 255 -- 81 6 c) AED excursion -63 -33 Envelope loss/gain 2209 1262 1953 1068 12 a) Infiltration b) Room ventilation 395 0 106 01 309 0 83 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 800 0 0 0 Subtotal (lines 6 to 13) 2604 2168 2262 1151 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 6 2610 698 0 0 15 2183 1176 279/. 540/. 0 0 0 2262 605 0 0 0 1151 620 Total room load Air required (cfm) 3309 122 3359 145 2867 106 1771 77 Calculations approved WACCA to meet all requirements of Manual J 8th Ed. -� wrigF2tsoft- A . Page 6 Right -Suite@ Universal 2018 18.0.31 RSU08101 2019-Jun-03 14:ge 6 E:\Documnets\WriVAC ghtsoft H\TESTA RESIDENCE.rup Calc = MJS Front Door faces: E +� wrightsoft° Right-J® Worksheet Job: Entire House Date: Jun 03, 2019 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name E)qosed wall Room height Room dimensions Room area LINEN CLST O ft 10.0 ft heat/cool 6.0 x 2.0 ft 12.0 ftz AHU CLST O ft 10.0 ft heat/cool 4.0 x 2.0 ft 8.0 ft' Ty Construction number U-value (Btuh/ft' °F) Or HTM (Btuh/ft2) Area (ft� or perimeter (ft) Load (Btuh) Area (ftj or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A 7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2glazing, clr low-e 2 glazing, Gr low-e 2 glazing, cir low-e 2.glazing, clr_low--e-_ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, dr low-e 11D0--- 13A-7.5fcs - 2glazing, clr low-e 2glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 13A 7.5fcs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 2_plazinq. clr low-e 226_tph 0:083 0.650 0.650 0.650 0.650 0.650 _-_-- 0;650 0.083 0.650 0.650 �0_390 0.083 0.650 0.650 0.650 0.650 0.083 0.650 0.650 0.650 ----_ 0.650 8. , ri.- n n n n n --n_ a a a e_ s s s s s w w w w -w_ _ 2.32 18.20 18.20 18.20 r 18.20 18.20 18.20, 2.32 18.20 18.20 _- 10_92 2.32 18.20 18.20 18.20 18.20 2.32 18.20 18.20 18.20 ,,-0.9Q _38.02. - 1.10 14.99 14.99 14.99 14.99 13.26 ___10.68 1.10 14.91 14.66 --1Q34 111.10 14.99 ' 13.26 10.68 10.68 1.10 3265 10.68 10.68 _ _2.24 0:00 0._._0 0 0 0 0 0 -__�-_0 0 0 0 _.____0 0 0 0 0 0 0 0 0 0 _-_-_ 12 12 0 0 0 0 '0 _ -_0 0 0 0 ----0 -0 0 0 0 0 __.._....._ 0 0 0 0 0 0 __-_-_0 0 0 0 - o 0 0 0 0 0 _ W 0 0 0 0 0 0 __-__0 0 0 0 - -0 0 0 0 0 0 O 0 0 0 0 0 __^0 0 0 0 --. - 0 .0 0 0 0 0 0 0 0 0 -- _0 _ .-_8 8 O 0 0 0 0 0 _-_0..-__-0. 0 0 0 -- - 0 -6, 0 0 0 0 .�---_- 0 0 0 0 0 0 0 0 0 - -0 - 0 0 0 0 0 0 0 0 0 __ _-- 0. _ - 7 0. 0 0 0 0 0 0 0 0 -- --6 0 0 0 0 0 0 0 0 0 ___ 0. ____18 _ 0 -L--G W �-G - - W 0 0 0 0 -- -0 ___ 12 0 0 0 0 0 -- 0 ___ 11 0 0 0 0 0 _- _ 0 -____27 0 0 0 0 0 - _ 0 _8 F __, 0 - ! _ _ -__- 6 c) AED excursion -1 -1 Envelope loss/gain 11 26 7 17 12 a) Infiltration b) Room ventilation 0 00 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 11 26 7 17 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 -11 0 0 0 0 -25 0 0 27% 54% 0 0 -7 0 0 0 0 -17 0 0 Total room load Air required (cfm) 0 0 0 0 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrfightsoft� Right-Suite® Universal 2018 18.0.31 RSU08101 2019-Jun-03 14:32:27 Page 7 E:1DocumnetslWrightsoft HVAC\TESTARESIDENCE.rup Calc = MJS Front Door faces: E +� wrightsoft° Right-JO Worksheet Job. Entire House Date: Jun 03, 2019 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area LAUNDRY O ft 10.o ft heat/cool 1.0 x 90.0 ft 90.0 ftz PANTRY O ft 10.0 ft heat/cool 4.0 x 5.0 ft 20.0 ftz Ty Construction number U-value (Btuh/ft;°F) Or HTM (Btuh/ft� Area (ftz or perimeter (ft) Load (Btuh) Area (ftz or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 19A-7.3fcs 2 glazing; clr low-e 2 glazing,, cirlow-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e .2.gla7ing, clr low-e__-_- 13A-7.5fcs glazing, clr low-e 2 glazing, clr low-e __ _ _ 13A 7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 1100 0.083 0.650 0.650 0.650 0.650 0.650 --_0650 0.083 0.650 0.650 __ 0.390 0.083T 0.650 0.650 0.650 0.650 0 390 0.083 0.650 0.650 0.650 ,__ 0.650 ,-0,032 1-. 358 -ri n n n n n _--ri_ a a a a s ,-s w w w w _w ` 2.32 18.20 18.20 18.20 18.20 18.20 -_18.20 2.32 18.20 18.20 __-.10.92_ 2.32 18.20 18.20 18.20 18.20 _ 10:92 2.32 18.20 18.20 18.20 .__ 18M.. _`0,90- 38.02 1 1-0 14.99 14.99 - 14.99 14.99 : 13,26 ._._._10.68 1.10 14.91 14.66 10.34, 1.10 14.99 13.26 . 10:68 10.68 10 34 1.10 32.65 10.68 10.68 14.66 - 2.24 -0.00 -' -- p 0 0 0 0 0 -- --_0 0 0 0 , 0 0 0 0 0 0 m0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 ____0 0 0 0 0 0 ------ 0 0 0 0 --� 0 0 ____0 _.- O 0 0 0 0 0 ---___,0 0 0 0 _ 0 0 0 0 0 0 0 6 0 0 0 0 0 -____--._0 0 0 0 - r_0 0 0 0 0 ' 0 0 ___0 0 0 0 0 0 _ _0 0 0 0 0 0 0 0 0 0 ______0 0 0 0 0 --_ _-_0 ,_20 0 0 0 0 0 - 0 0 0 0 --- 0 0 0 0 0 0 ..... ._ 0 0 0 0 0 ----- 0 _.._._..___20 0 0 0 0 0 __-.-_-o. 0 0 0 _- -_ 0. 0 0 0 0' 0 ____0 0 0 0 0 --- --_-0- 18' 0 0 0 0 0 __._-- .0 0 0 0 _._ 0 - 0 0 -0 0, 0 0 0 0 0 - -- - __0_ _. _45- -_--__0 _ W [�2 D11DO W _ _ _C_ _ F __-_,-_ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e _2.Alazinp, cl_r low-e _169.30md - M 226_tph,_ - 0 0 0 0 - 0 0 0 0 0 0 0 0 ____-_ 9020 90 - 0 0 6 c) AED excursion -20 -1 Envelope loss/gain 81 182 18 44 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 500 0 0 0 Subtotal (lines 6 to 13) 81 682 18 44 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 277 357 96 0 0 171 852 459 27% 54% 0 0 0 18 5 0 0 0 44 23 Total room load Air required (cfm) 453 17 1312 57 1 23 1 67 3 Calculations approved byACCA to meet all requirements of Manual J 8th Ed A-wr➢ghtsoft� AA Right -Suite® Universal 2018 18.0.31 RSU08101 2019-Jun-03 1 Pag9e 8 E:\Documnets\Wrightsoft HVAC\TESTARESIDENCE.rup Calc = MJ8 Front Door faces: E +� wrightsoft° Right-M Worksheet Job: Entire House Date: Jun 03, 2019 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Bq)osed wall Room height Room dimensions Room area WINE RM 4.0 ft 10.0 ft heat/cool 4.0 x 5.0 ft 20.0 ft2 HALL 6.0 ft 10.0 ft heat/cool 6.0 x 5.0 ft 30.0 ft2 Ty Construction number U-value (Btuh/ft'-°F) Or HTM (Btuh/ft� Area or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6_ 11 ' 13A-7.5fcs 2 glazing, rdr low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, drlow-e 2 glazing, dr low-e .2.glazing, clr.low_e.__. 13A-7.5fcs 2 glazing, cir low-e 2 glazing, clr low-e 0.083 0.650 0.650 0.650 0.650 0.650 -.-.0.650 0.083 0.650 0.650 -n n n n n n _-n_.._ a a a 2.32 18.20 18.20 18.20 18.20 18.20 18.20: 2.32 18.20 18.20 1.10 '14.99 14.99 : 14.99 14.99 13.26 --_ 10.68 1.10 14.91 14.66 1.10-40 14.99 13.26 10.68 10:68 1034 1.10 32.65 10.68 10.68 __ 14_66 e�224 0 0 0 0 0 0 __--_ ---0 0 0 0 0 - 0 0 0 0 0 _ -_- 0 0 0 0 40 0 0 0 0 ^---____;0 0 0 0 0 _ 0 ��_._ 20 ___ _ 4 f -0 0 0 0 0 0 _----A 0 0 0 93 - 0 0 0 0 ___`0 0 0 0 0 __ _ 0 _ _ 18 152 --'---0 0 0 0 0 0 -_ �0 0 0 0 44 0 0 0 0 0 0 0 0 0 0 0 _._ _-0 0 0 0 60 0 0 0 0 •__-24 0 0 0 0 _____ `0 __ _ _,�30 30 u T 0 0 0 0 0 0 0 0 0 0 - 36 0 0 0 0 _-_24 0 0 0 0 _ ____ . , 30 0 0 0 0 0 0 -0. 0 0 0 ~ 84 0 0 0 0 -__.-262 0 0 0 0 0 0 0 0 0 0 ---._ ---0 0 0 0 40 0 0 0 0 -__248- 0 0 0 0 0 _____ _-0 _ _ , W 13A 7.5fcs , " - 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 11D0_ 13A-7.5fcs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazinq, clr low a -„ 16A-30md- 22A-tph-_.p_ 0.083 0.650 0.650 0.650 0.650 0_.390 0.083 0.650 0.650 0.650 --.-,-0.650 ___ _0.032 1.358 s s s s s _s w w w w _ w ,_ - 2.32 18.20 18.20-. 18.20 18.20 - 10:92 2.32 18.20 18.20 18.20 18.20 -0:90. 38 02 0 0 0 0 .-__ W _0 0 0 0 0 - _ 0 20 20 _' 0 0 0 0 _ __0 -v 45 T__0 _ . C.� F -___. ____-_,27 228 0 00 _ 6 _ 6 c)AED excursion -3 -11 Envelope loss/gain 263 86 601 344 12 a) Infiltration b) Room ventilation 69 0 18 0 103 0 28 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 332 104 704 372 14 15 Less e)demal load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 220 552 148 0 0 116 220 119 27% 540/6 0 0 -704 0 0 0 0 -372 0 0 Total room load Air required (cfm) 699 26 339 15 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed +w wrightsoft� A Right-SuiteUniversal 2018 18.0.31 RSU08101 2019-Jun-03 1 Paglome 9 E:\Documnets\WdghtsoftHVAC\TESTARESIDENCE.rup Calc = MJ8 Front Door faces: E +� wrightsoft Right-J® Worksheet Job: Entire House Date: Jun 03, 2019 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area DINING ROOM 33.0 ft 10.0 ft heat/cool 15.0 x 14.0 ft 210.0 ft' KITCHEN 0 ft 14.0 ft heat/cool 16.0 x 17.0 ft 272.0 ftz Ty Construction number U-value (Btuh/ft1 °F) Or HTM (Btuwft� Area (ft� or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 - W W -_ _ Cr_.- F _ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clydow-e 2 glazing, cir low-e 2 glazing, clr low-e _2.glazing, clr_low=e___ 13A-7.5fcs 2 glazing, clr low-e 2 glazing, dr low-e 11D0� 13A-7.5fcs �- 2 glazing, •dr low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 13A 7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low_e_- 16A-30md_ 22A-tph -_ A.083 0.650 0.650 0.650 0.650 0.650 .___-0.650 0.083 0.650 0.650 _.0.390 0.083 0.650 0.650 0.650 0.650 - 0.390 0.083 0.650 0.650 0.650 -0.650 __._0.032 - 1.358 n n n n n n _-n- a a a _e -s' s s s s _ s-' w w w w _w . 2:32 18.20 18.20 18.20 18.20 18.20 --18.2Q 2.32 18.20 18.20 10.9210.34 - 2.32 18.20 18:20 18.20 18.20 -- 10.92 2.32 18.20 18.20 18.20 18.20 6:90 38.02 1.10 14.99 14.99 14.99 14.99 13.26 - 10.68 1.10 14.91 14.66 1.10 14.99 13.26 10.68 10.68 _T 1034 1.10 32.65 10.68 10.68 _14.66 =2:29 0.00 0 0 0 0 0 0 _.._._---_0 90 0 36 - 0 - 150 0 ' 0 0 54 ___0 90 0 0 0 _ 36 �__,_ 210 --210 0 0- 0 0 0 0 0 54 0 22 0 ^ - 96 0 0 0 54 -- 0 54 0 0 0 22 ®210 33 0 0 0 0 0 0 ---__ 0 125 0 655 0 ---223 0 0 0 983 - - -0 125 0 0 0 __- 655 _ _ 188 1255 0 0 0 0 0 0 ___0 60 0 528 0 0 0 0 0 0 0 -------0 0 0 0 0 0 0 0 0 0' ---_._-.._0 0 0 0 0 0 0 0 0 0 -----__ -A 0 0 0 0 0 0 0 0 _-- - 0 0 0 0 0 -,__ 0 __244. 0 0 0 0 0 0 0 -_- -- 0 0 0 0 _ 0 0 0 0 0 0 -- - --0 0 0 0 0 0 60a 0 106 0 0 0 577 - -.0 60 0 0 0 -- _528 -_.-_ 470 0 _----0 0 0 0 0 0 --_-0---_----0 0 0 0 .0 0 Q ----0 0 0 0 0 `_; 0 _� _,,,272 272 0 0 0 0 -_-_ 0 _,_`._272 0 6 c) AED excursion 288 -88 Envelope loss/gain 4210 2616 244 522 12 a) Infiltration b) Room ventilation 566 0 152 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 2500 Subtotal (lines 6 to 13) 4777 2768 244 3022 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 220 492970 1337 0 0 116 2884 1554 27% 54% 0 0 11 254 68 0 0 26 3047 1642 Total room load Air required (cfm) 6334 234 4438 192 1 1 322 12 4689 203 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �A Right -Suite® Universal 2018 18.0.31 RSU08101 2019-Jun-03 Pag9e 10 E:\Documnets\WrightsoftHVAC\TESTARESIDENCE.rup Calc = MJ8 Front Door faces: E +�- wrightsoft° Right-JO Worksheet Job: Entire House Date: Jun 03, 2019 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area GREAT ROOM 60.0 ft 14.0 ft heat/cool 1.0 x 487.0 ft 487.0 ft' Ty Construction number U-value (Btuh/ft2 °F) Or HTM (Btuh/ft5 Area (ft5 or perimeter (ft) Load (Btuh) Area or perimeter Load Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W 13A-7.5fcs 2glazing, clrlow-e 2 glazing, clr'low-e 2 glazing, clr low-e 2 glazing, clr'low-e 2 glazing, clr low-e .2 glazing, clr-low e_ - 13A 7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 11D0- ---- - -- 13A 7.5fcs 2glazing, cir'low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir low-e 11 D.0 _-- 13A 7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 olazinq,_clr low-e 16A 30md- 0.083 0.650 0.650 0.650 0.650 0.650 0.650 0.083 0.650 0.650 - - 0.390 0.083 0.650 0.650 0.650 0.650 --_0,390 0.083 0.650 0.650 0.650 . ---0.650 -- 0;032 n n n n n n _.n_ a a a e s s s s s s w w w w -w-. - _- 2.32 18.20 18.20 18.20 18.20 18.20 __18.20, 2.32 18.20 18.20 - 10.92 2.92 118.20' 18.20 18.20 18.20 10.92 2.32 18.20 18.20 18.20 18.20 . 0.90, 38.02 1.10 14.99 14.99 14.99 14.99 13.26 -._ 10,68 1.10 14.91 14.66 -_10 34 .1.10 14.99'' 13.26 .10.68 10.68; --10.34 1.10 32.65 10.68 10.68 14.66 _ ,2.24 0,00 210 0 0 0 0 48 _ ,-- 0 368 36 0 .._-. --0 322 0 96 0 0 -_- -0 0 0 0 0 0 487 _ 487 162 0 0 0 0 0 _ ---- 0 272 32 0 - - - 0 226 0 96 0 0 ___-- -0 0 0 0 0 ti _ 0 - 487 ___-_60 376 0 0 0 0 874 - _ ----0 632 655 0 - - 0 525 0 1747 0 0 -- 0 0 0 0 0 _0 ___ 436 --2281 179 0 0 0 0 636 -- ----0 300 537 0 - ---0 249 0 1273 0 0 -.-- 0 0 0 0 0 _-_ 0 __ 1091 0 - - _:_ - -- - - _ _ _--- . ___- _.- • -�... ---- ___- -- ---_-- _----- - -- -- -- .- W -- - - ^-. - W - _ C -__. 6 c) AED excursion -131 Envelope loss/gain 7528 4134 12 a) Infiltration b) Room ventilation 1442 0 386 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 Subtotal (lines 6 to 13) 8970 4521 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 27% 54% 0 0 0 8970 2400 0 0 0 4521 2435 Total room load Air required (cfm) 11370 4191301 6956 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. -F•Fi- wrigF�tsoft� ^` Right -Suite® Universal 2018 18.0.31 RSU08101 Page 12019-Jun-03 14:32:2 .4CCP. 1 E:1Documnets\Wrightsoft HVAC\TESTARESIDENCE.rup Calc = MJ8 Front Door faces: E - - wrightsofto Duct System Summary Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799. Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM F-roject intormation For. TESTA RESIDENCE FORT PIERCE, FL Job: Date: Jun 03, 2019 By: Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply / return available pressure 0.500 / 0.500 in H2O 0.500 / 0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 1550 cfm 1550 cfm Total effective length (TEL) 173 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 709 26 19 1.000 5.0 Ox 0 VIFx 38.4 135.0 st5 BEDROOM 2 h 3361 124 113 1.000 7.0 Ox0 VIFx 20.7 115.0 st1 DINING ROOM h 6334 234 192 1.000 8.0 Ox0 VIFx 20.0 115.0 st3 FOYER h 2867 106 77 1.000 6.0 Ox 0 VIFx 22.8 115.0 st1 GREAT ROOM h 5685 210 151 1.000 8.0 Ox 0 VIFx 29.4 115.0 st2 GREAT ROOM -A h 5685 210 151 1.000 8.0 Ox 0 VIFx 28.4 115.0 st2 HALF BATH c 184 2 8 1.000 4.0 Ox 0 VIFx 18.4 115.0 st1 KITCHEN c 2345 6 102 1.000 7.0 Ox 0 VIFx 31.1 115.0 st2 KITCHEN -A c 2345 6 102 1.000 7.0 Ox0 VIFx 31.9 115.0 st2 LAUNDRY c 1312 17 57 1.000 6.0 Ox 0 VIFx 13.0 115.0 st3 M BATH h 2924 108 71 1.000 6.0 Ox 0 VIFx 38.0 135.0 st5 M BATH -A h 2924 108 71 1.000 6.0 Ox0 VIFx 27.8 115.0 st4 M TOILET h 490 18 14 1.000 4.0 Ox 0 VIFx 34.8 135.0 st5 M WIC c 460 6 20 1.000 5.0 Ox 0 VIFx 22.8 115.0 st4 MASTER BEDROOM c 2769 111 120 1.000 7.0 Ox 0 VIFx 25.0 115.0 st4 MASTER BEDROOM -A c 2769 111 120 1.000 7.0 Ox0 VIFx 27.6 115.0 st4 OFFICE c 3359 122 145 1.000 8.0 Ox 0 VIFx 15.8 115.0 st1 PANTRY c 67 1 3 1.000 4.0 Ox 0 VIFx 17.1 115.0 st3 WINE RM h 699 26 15 1.000 4.0 Ox 0 VIFx 18.1 115.0 st3 -+ wrightsoft, 2019-Jun-0314:32:29 �� <W �• a ti^� -.��wM Right -Suite® Universal 2018 18.0.31 RSU08101 Page 1 i4CC% EADocumnets\Wrightsoft HVAC\TESTARESIDENCE.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg CIg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st2 Peak AVF 431 504 1.000 764 11.0 0 x 0 VinlFlx st1 Peak AVF 354 343 1.000 649 10.0 0 x 0 VinlFlx st3 Peak AVF 277 267 1.000 627 9.0 0 x 0 VinlFlx st5 Peak AVF 152 104 1.000 436 8.0 0 x 0 VinlFlx st4 st4 Peak AVF 488 436 1.000 739 11.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) CIg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1550 1550 0 0 0 0 Ox 0 VIFx 1* w�rightsoft- .11M . � +��•*+�M—•���M Right -Suite® Universal 2018 18.0.31 RSU08101 E:\Documnets\Wrightsoft HVAC\TESTA RESIDENCE.rup Calc = MJ8 Front Door faces: E 2019-Jun-03 14:32:29 Page 2