HomeMy WebLinkAboutInspection ReportDecember 23, 2008
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-M2
U. GERLEY A QSSOCUQTES
STRUCTURAL ENGONEEGB
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.01
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION: 10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR: Daniello Construction, Inc., CGC #020612
AREA INSPECTED: Repairs #1 (B&C), 2, 3, 4, 5, 6, 7, 8, 9, 10, & 14B (per Project Drawing S1)
• Excavation of unsound concrete limits ven/ied
• Exposed reinforcing verified sandblasted to bright metal
Exposed reinforcing verified coated with anti-cor►osiorYbonding agent
INSPECTION DATE: December 15t', 2008
FINDINGS: Activities are satisfactory (see photographs, page 2)
COMMENTS: 1) Additional damage uncovered at #1, upper & lower column, noted as 'IT & 'C' (see
photos)
2) Additional damage uncovered at Stucco Repair #47, noted as "14B° (see photos)
3) All repairs this Inspection Report utilized Sika Armatec 110 Epocem anti-
corrosion/bonding agent and BASF LA40 Repair Mortar
Sincerely,
V.J.GERLEY
D ASSOCIATES
�"La-ter r�^r-�•-`
Certified: Victor J.G dey, PE I Field Coordination: Scott A. Lorraine, PE
Florida Spec.lnsp. #11, 9, Prof.Engr. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen. Mgr., Turtle Reef Club (via email)
Victor J. Gedey, PE V.J.Geriey & Assoc. (Project file; via email)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Note - ...:..os are for representative purposes only as noted h., i ions
I }rd "7
Additional upper repair "W at Col. D1
(initial cut-out to bonded reinforcing)
Repair#1 as designated Additional lower repair'1C"atCol. D1
(final cut-out, cleaned & coated) (initial cut-out to bonded reinforcing)
Non -Structural Stucco Repair #47 upgraded to Structural Column Repairs #8 & #9 with Beam Repair #1 D
Repair #"14B" (final cut-out cleaned & coated) (all to final cut-out, cleaned & coated, with #8 being fom►ed)
N
i
December 23, 2008
Pemnit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
U. GERLEY'A ASSOCIATES
3190 N.E. MAPLE AVE
JENSEN BEACH,FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.02
PROJECT:
Turtle Reef Club Condominium 11
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs #23, 31(B), 348, 37(B), 39 & 44B (per Project Drawings S1& S2)
• Excavation of unsound concrete limits verified
• Exposed ninforcing verified sandblasted to bright metal
• Exposed n inibming verified coated with anti-corrosion/bonding agent
INSPECTION DATE:
December 180', 2008
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at retaining wall (see photos, page 2):
• Unit 110 — Repair #31 B
• Unit 109 — Repair #34B
• Unit 108 — Repair #37B
• Unit 105 — Repair#44B
3) All repairs this Inspection Report utilized BASF Emaco P24 anti-
corrosion/bonding agent and BASF LA40 or HBA Repair Mortar
Sincerely,
V.J.GERL Y A D ASSOCIATES
Gd-t-1
Certified: Victor J. edey, PE I Field Coordination: Scott A. Lorraine, PE
Florida Spec.lnsp. 9, Prof.Engr. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen. Mgr., Turtle Reef Club (via email)
Victor J. Gedey, PE V.J.Gedey & Assoc. (Project file; via email)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Note tos are for representative purposes only as noted ii `ions
ems`-�'`
.-
��
•;' � `� a � I•-b ... x �` a fey.
Additional damage (#31B) at Unit #110 retaining wall
adjacent to repair#31 per Project Drawing S2
Additional damage (#37B) at Unit #108 retaining wall
adjacent to repair #37 per Project Drawing S2
Additional damage (#34B) at Unit #109 retaining wall
adjacent to repair #34 (wing wall) per Project Drawing S2
#37B eont d (note new #4 horiz bar) columnK41fetaining wall
adjacent to repair #37 per Project Drawing S2
Additional damage (#44B) at Unit #105 retaining wall adjacent to repair #44 (wing walq per Project Drawing S2 (column at right is
E4). Cut-out is through laundry room at garage level.
N
December 23, 2008
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
W.J. GERLE 11 0 WSSOCHW II ES
STRUCTURAL ENGIMEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.03
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION: 10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR: Daniello Construction, Inc., CGC #020612
AREA INSPECTED: Repair; #1(1B), 2(2B), 3, 4(4B), 5, 6, 7, 8, 9, 10(10B), & 14B (per Project Drawing S1)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patchinglp/acement after form removal verified
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE: December 1e, 2008
FINDINGS: Activities are satisfactory
COMMENTS: [See photos]
1) Additional repair at #1 (IR#1), upper & lower column, noted as "B" & "C"
2) Additional repair at #2, opposite beam face, noted as "26"
3) Additional repair at #4, mid column / opposite face, noted as W"
4) Additional repair at #10, beam spall continuation at column, noted as "I OW
5) Additional repair at stucco #47, lower column A, noted as "146"
6) All repairs this Inspection Report utilized BASF Emaco P24 anti-
corrosion/bonding agent and BASF LA40 Repair Mortar
Sincerely,
V.J.GERL14\Y AND ASSOCIATES
Certified: VctJ.Gefley, PE
Florida Spec.l Sp. #89, Prof.Engr. #21422
'CI•
( e"-�
J ��
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen. Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Ge►tey & Assoc. (Project file; via email)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Note .:tos are for representative purposes only as noted 'i : —;pions
Repair#1, #1B, & #iC
Repair #10B
Repair #4B
Repair #2B (small spall to be repaired by cleaning & patching with BASF HBA)
Repair #14B
.2
r-= A
Y.J. GERL Y o ASSOCIATES
STRUCTURAL EMONEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
January 16, 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
INSPECTION REPORT NO.04
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs #313, 11(B), 12, 14, 16, 17, 18, 21C, 21D, 27, 28, 29, 29B, 34C, 35, 36, 38, 39,
40, 41, 41 B, 42, 43, & 44 (per Project Drawings S1& S2 - Supplemental Repairs
denoted w/ suffix'B', 'C', etc.)
• Excavation of unsound concrete limits verified
• Exposed reinforcing verified sandblasted to bright metal
• Exposed reinforcing verified coated with anti-cofrosionlbonding agent
INSPECTION DATE:
January e, 2008
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beam, BJor retaining wall (see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent and
BASF LA40 or HBA Repair Mortar
3) Project drawings will be revised at Projects end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GEMEY AND ASSOCIATES
V�
Certified:
Florida Sm
J.Gedey, IPE
;p. #89, P of.Engr. #21422
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file; via email)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
—^F
Inspection Report #4 — Photos are for representative purposes only as noted in captions
Supplemental Repair #38 — beam
at Col.Une 'D'
Supplemental Repair #118 — Col H2
Supplemental Repair #298 — Unit 110
I
STRUCTURAL EYVGINEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
January 16, 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
INSPECTION REPORT NO.05
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
• Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs #1C, 313, 11(B),12,14, 16, 17, 18, 21C, 21D, 23, 27, 28, 30, 31(B), 32, 33,
34(B&C), 35, 36, 37(B), 38, 39, 40, 41(B), 42, 43, & 44B
(per Project Drawings S1& S2 - Supplemental Repairs denoted w/ sutiix'B', 'C', etc.)
• Satisfactory formwork to repair limits vertfled
• Satisfactory repair mortar patching/placement after form removal verified
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE:
January e, 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beam, BJor retaining wall (see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent and
BASF LA40 or HBA Repair Mortar as applicable
3) Project drawings will be revised at Projects end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
VA.GERLEMAND ASSOCIATES
Certified: Victor
Florida Spec.ln:
Geriey, PE I
. #89, Prof. ngr. #21422
L�•t f I7'�"��`
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file; via email)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #5 — Photos are for representative purposes only as noted in captions
Col. D1
Col. 03
Supplemental Repair #3B
Beam at Col line V
Supplemental Repair #31 B
retaining wall at Unit 110
Col. H2
retaining wall at Unit 109
Col. 03
Col M4, Unit 109
retaining wall at Unit 108 retaining wall at Unit 106 retaining wall at Unit 105
January 16, 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
87RUCIIl1UlAL LSIIVOIfUEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.06
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION: 10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR: Daniello Construction, Inc., CGC #020612
AREA INSPECTED: Repairs # 12B, 14C, 15,16B, 20, 21(B&E), 22, 24, 25, 26,
29C, 44C-G, 53, & 54
(per Project Drawings S1& S2 - Supplemental Repairs denoted w/ suffoc'B', 'C', etc.)
Excavation of unsound concrete limits verified
Exposed reinforcing verified sandblasted to bright metal
Exposed reinforcing verified coated with anti-corrosion/bonding agent
INSPECTION DATE: January le, 2009
FINDINGS: Activities are satisfactory
COMMENTS: 1) Additional damage uncovered at columns, beam, &/or retaining wall (see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent and
BASF LA40 or HBA Repair Mortar as applicable
3) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GERLEM AND ASSOCIATES
Certified: Victor k4lFlorida Spec.lnsngr. #21422
distrib: Charlie And ws Gen.Mgr., Turtle Reef Club
Victor J. Gerley, PE V.J. Gerfey & Assoc.
Scott A. Lorraine, PE Scoff A. Lorraine, PE, LLC
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
(via email)
(Project file; via email)
(Project file)
1
Inspection Report #6 — Photos are for representative purposes only as noted in captions
Supplemental repairs #44C, 44D, 44E, 44F, & 44G (left to right), retaining wall Unit 105
February 11t', 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
Y.J. IYJSEE�yll��pUL �O�r���A 22WMM(SSMO22��WT'EV
SIMUCO URALS 6N WHEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.07
pec��oe�
FEB 2 3 2009 D
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION: 10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR: Daniello Construction, Inc., CGC #020612
AREA INSPECTED: Repairs # 12B, 14C, 15, 16B, 20, 21(B&E), 22, 24, 25, 26, 29(B&C), 44C-G,
(per Project Drawings S1 & S2 - Supplemental Repairs denoted w/ suffix 'B', 'C', etc.)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patching(placement after form removal verified
• Repair area deemed acceptable for stun o repair (shoring removed)
INSPECTION DATE: January 20t', 2009
FINDINGS: Activities are satisfactory
COMMENTS: 1) Additional damage uncovered at columns, beam, retaining wall, Wor walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF LA40, HBA Repair Mortar, or 3500psi ready -mix
as applicable
3) Project drawings will be revised at Projects end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GERLINLAND ASSOCIATES
Certified: Victor J. erley, PE
Florida SDec.InSp #89. Prof.Enar #21422
distrib: Charlie Andrews Gen. Mgr., Turtle Reef Club
Victor J. Gerley, PE V.J.Gerley & Assoc.
Scott A. Lorraine, PE Scoff A. Lorraine, PE, LLC
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
(via email)
(Project file; via email)
(Project file)
1
Inspection Report #7 — Photos are for representative purposes only as noted in captions
Supplemental Repair#14C (Col 12)
Supplemental Repair #218 (slab at Col 01)
Supplemental Repair #29C (Col P4)
Supplemental Repairs #44C-G (Unit 105 Ret Wall)
February 11d', 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
l . (`cW�S�Effo��Il��pLL(�L�rSE��ppO�fo� �Ap �f{ASSOrr���ffoo���ATES �
37RUCTUU1AL, EINGIII�IEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.08
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 1D, 3C&D, 12C, 20B, 29D, 46, 47, 48, 52(B), 78, 79,102
(per Project Drawings S1& S2 - Supplemental Repairs denoted w/ suf ix'B', 'C', etc.)
• Excavation of unsound concrete limits verified
• Exposed reinforcing verified sandblasted to bright metal
• Exposed reinforcing venfred coated with anti-corrosionlbonding agent
INSPECTION DATE:
January 23`d, 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beams, retaining wall Wor walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent
3) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GEgLEY AND ASSOCIATES
Certified: Victor. .Gerley, PE
Florida Spec.lns . #89, Prof.En r. #21422
distrib: Charlie Andrews Gen Mgr, Turtle Reef Club
Victor J. Gerley, PE V.J. Gerfey & Assoc.
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC
rim
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
(via email)
(Project file; via email)
(Project file)
1
Inspection Re , , M — Photos are for representative purposes only a- _. -�d in captions
•r-Ur
1 ���.1
Supplemental repair #3C (slab/beam at
Supplemental repair #1
Line D)
-. I
(underside, left & upper surface, right)
Supplemental repair#208 (stairwell column)
Supplemental repair #528
(stairwell column, 14 floor)
February 11 d', 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
W.J. GERLEY o ASSOCHAT S
STRUCTURAL ENNN ERE
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.09
CE 0
FEB 2 3 2009
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 3C&D,12C, 20B, 29D, 46, 47, 48, 52, 52B, 78, 79, & 102
(per Project Drawings S1 & S2 - Supplemental Repairs denoted w/ suffix '13% 'C', etc.)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patching/placement after form removal verified
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE:
February 2"d, 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beam, retaining wall, &/or walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF LA40, HBA Repair Mortar, or 3500psi ready -mix
as applicable
3) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GERL A ASSOCIATES
Certified: Victor-J.Ge iey, PE Field Coordination: Scott A. Lorraine, PE
Florida Spec.lnsp. 9, Prof.Eng #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen Mgr, Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file; via email)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #9 — Photos are for representative purposes only as noted in captions
Supplemental repairs
at grade)
Supplemental repair # 29D (overhead -Unit 110 balcony underside)
r�
April 2e, 2009
Permit # 0810-0190 `
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
W.J. lElLSlA WSSOCOATES
U7WUCg1RAti ENGINEERS 3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
0810 - G 6q-D
INSPECTION REPORT NO.10
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION: 10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR: Daniello Construction, Inc., CGC #020612
AREXINSPECTED: Repairs # 1D&E, 13,15,19, 20C, 27B, 281113, 51B, 54, 55, 57, 58, 6013, 60C, 78B,
78D, 84, 85, 90, & 91
(per Project Drawings S1& S2 - Supplemental Repairs denoted w/ suffx'B', 'C', etc.)
• Excavation of unsound concrete limits verified
• Exposed reinforcing verified sandblasted to bright metal
• Exposed reinforcing verified coated with anti-corrosioMbonding agent
INSPECTION DATE: February 25t', 2009
FINDINGS: Activities are satisfactory
COMMENTS: 1) Additional damage uncovered at columns, beams, retaining wall Wor walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
-Sincerely,
V.J.GERLE' AND ASSOCIATES
Id.,
Certified: Victor 4Gerley, PE Field Coordination: Scott A. Lorraine, PE
Florida Spec.lns #89, Prof.Engr. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gedey & Assoc. (Project filel)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #10 — Photos are for representative purposes only as noted in captions
Suppl. repair #20C (Beam at Ocean
Suppl. repair# 1E (Column at Garage entrance)
(Col. at Ocean Stairs)
#78B
2
s) Suppl. Rep. #60C (1 Flr Ocean Stairs)
April 28", 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
37RUC4MRAd EaMMC ERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.11
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION: 10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR: Daniello Construction, Inc., CGC #020612
AREA INSPECTED: Repairs # 1 DBE, 13,15,19, 20C, 271B, 28B, 51 B, 54, 55, 57, 58, 60B, 60C, 78B,
78D, 84, 85, 90, & 91
(per Project Drawings S1 & S2 - Supplemental Repairs denoted w/ suffix 'B', 'C', etc.)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patching/placement after form removal verified
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE: March 6, 2009
FINDINGS: Activities are satisfactory
COMMENTS: 1) Additional damage uncovered at columns, beam, retaining wall, Wor walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF LA40, HBA Repair Mortar, or 3500psi ready -mix
as applicable
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GER E ND ASSOCIATES
'`/•
Certified: Victor .Gerley, PE Field Coordination: Scott A. Lorraine, PE
Florida Spec.lns . #89, Prof.Engr. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J. Gerley & Assoc. (Project filel)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #11 — Photos are for representative purposes only as noted in captions
SuppL repair #518
Y.J.
(GLSnpRp(L5Epp11��pA 2W�I�/S�SM2O��(�ATES
STRUCTURAL UUl7AL LSOVl91EIfVEERS
3190 N.E. MAPLE AVE m
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
D
April 28 ,Zoos
MAY — 5 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
INSPECTION REPORT NO.12
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
f
LOCATION:
10800 South Ocean Drive
Jensen Beach,;Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 58B, 60D, 83, 86, 92, 104, 105, 106
(per Project Drawings S2 & S3 - Supplemental Repairs denoted w/ suffix'B', 'C', etc.)
• Excavation of unsound concrete limits verified
• Exposed reinforcing verified sandblasted to bright metal
• Exposed reinforcing verified coated with anti-corrosion/bonding agent
INSPECTION DATE:
March 18u', 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beams, retaining wall &/or walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Projects end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.G R Y AND ASSOCIATES
N
CerRed: Vcto J.Gerley,
Florida Spec.l sp. #89, PiTEngr. #21422
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Ld-t�
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
April 28, 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
W.J. WCRdEASSOCIATESSTRUC5RAL ENGOVEERS 3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.13
DI�
MAY - 5 2009
08-6 -at 9z)
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 58B, 60D, 83, 86, 92, 104,105, 106
(per Project Drawings S1& S2 - Supplemental Repairs denoted w/ suffix'B', 'C', etc.)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patching/placement after form removal verified
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE:
April le, 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beam, retaining wall, &/or walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF LA40, HBA Repair Mortar, or 3500psi ready -mix
as.applicable
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Projects end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GE Y AND ASSOCIATES
Certified: Vict r J.Gerley, PE Field Coordination: Scott A. Lorraine, PE
Florida Spec.l sp. #89,
Prof. ngr. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #13 — Photos are for representative purposes only as noted in captions
June le, 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
STRUCTURAL EHROa[ ERE
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT.NO.14
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 32B, 58C, 106(B&C)i 107C
(per Project Drawings S3, S4, & S5 - Supplemental Repairs denoted w/ suffix 'B', 'C', etc.)
• Excavation of unsound concrete limits verified
• Exposed reinforcing verified sandblasted to bright metal,
• Exposed reinforcing verified coated with anti-corrosion/bonding agent
INSPECTION DATE:
May 5t', 2009
FINDINGS:
Activities are satisfactory
COMMENTS: 1) Additional damage uncovered at columns, beams, retaining wall &/or walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GERLEY AND ASSOCIATES
Certified: Victor 4.Gerley, PE
Florida Spec.lns . #89, Prof.Engr. #21422
distrib: Charlie Andrews Gen. Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file)
SaottA. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
/ Latl
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
lip* ►
Inspection Report #14 — Photos are for representative purposes only as noted in captions
Supp. repair #106C (5" level column P1)
Suppleme
2
Supp. repair #107C (roof & stairwell column 9110))
imn P4)
W.J.
'V/ 3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
June 15t', 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
INSPECTION REPORT NO.15
c��oer�
PROJECT:
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 32B, 58C,106(B&C),107C
(per Project Drawings S3, S4, & S5 - Supplemental Repairs denoted w/ suffix'B', 'C', etc.)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patching/placement after form removal venBed
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE:
May Ie, 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beam, retaining wall, &/orwalkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF LA40, HBA Repair Mortar, or 3500psi ready -mix
as applicable
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Projecrs end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GE L AND ASSOCIATES
/% err7—..''
r
Certified: Vict r J.Gerleyl PE Field Coordination: Scott A. Lorraine, PE
Florida Spec. nsp. #89,
Prof.Engr. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #15 — Photos are for representative purposes only as noted in captions
Su,
S
Al
Supp. repair #107C (underside stairwell roof & column 9110)
June 15t', 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
W.J. GERLE r A ASSOMATES CE G G D NI
STRUCTURAL EMONEERS p
JENSEN BEACH,FFLORIDAE34957 J U N 1 9 2009
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.16
PROJECT: Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 32C, 6013, 107B,108,108B
(per Project Drawings S4, S5, & S6 - Supplemental Repairs denoted w/ suftbc 'B', 'C', etc.)
• Excavation of unsound concrete limits verified
• Exposed reinforcing verified sandblasted to bright metal
• Exposed ►einfoirang vexed coated with anti-corrosion/bonding agent
INSPECTION DATE:
May 21s', 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beams, retaining wall Wor walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF Emaco P24 anti- corrosion/bonding agent
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GERUEVAND ASSOCIATES
Certified: Victor J Gerley, PE
Florida Spec.ins . #89, Prof.En r. #21422
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gedey & Assoc. (Project file)
Scott A. Lorraine, PE Scott A. Loraine, PE, LLC (Project file)
1
,,- /, �J • ,
Field Coordination: Scott A. Lorraine, PE
Florida Prof.Engr. #38714
F- jw -0
Inspection Report #16 — Photos are for representative purposes only as noted in captions
Supp. repair #1078 (roof edge Unit 509)
June 15U', 2009
Permit # 0810-0190
ST. LUCIE COUNTY
PUBLIC WORKS DEPARTMENT
CODE COMPLIANCE DIVISION
2300 Virginia Avenue
Fort Pierce, Florida 34982-5632
STRUCTURAL EMOMEERS
3190 N.E. MAPLE AVE
JENSEN BEACH, FLORIDA 34957
TEL 772 334-2600
FAX 772 334-2603
INSPECTION REPORT NO.17
PROJECT:'
Turtle Reef Club Condominium II
2008 Building "C" Concrete Repairs
LOCATION:
10800 South Ocean Drive
Jensen Beach, Florida 34957
CONTRACTOR:
Daniello Construction, Inc., CGC #020612
AREA INSPECTED:
Repairs # 32C, 60D, 107B, 108, 108B
(per Project Drawings S4, S5, & S6 - Supplemental Repairs denoted w/ suffix'13% 'C', etc.)
• Satisfactory formwork to repair limits verified
• Satisfactory repair mortar patching/placement after form removal verified
• Repair area deemed acceptable for stucco repair (shoring removed)
INSPECTION DATE:
June 3`d, 2009
FINDINGS:
Activities are satisfactory
COMMENTS:
1) Additional damage uncovered at columns, beam, retaining wall, Wor walkway slab
(see photos, page 2)
2) All repairs this Inspection Report utilized BASF LA40, HBA Repair Mortar, or 3500psi ready -mix
as applicable
3) Vector Galvashield XP+ sacrificial anodes installed (see Project drawings & specifications)
4) Project drawings will be revised at Project's end to reflect "as -repaired" conditions including
supplemental repairs as noted herein
Sincerely,
V.J.GERLE
D ASSOCIATES
Certified: Victor J.G dey, PE Field Coordination: Scott A. Lorraine, PE
Florida Spec.lnsp.
9, Prof.En r. #21422 Florida Prof.Engr. #38714
distrib: Charlie Andrews Gen.Mgr., Turtle Reef Club (via email)
Victor J. Gerley, PE V.J.Gerley & Assoc. (Project file)
Scott A. Lorraine, PE Scott A. Lorraine, PE, LLC (Project file)
1
Inspection Report #17 — Photos are for representative purposes only as noted in captions
Supp. repair #1088 (roof edge & partial overhead Unit 510)