HomeMy WebLinkAboutIsland Dunes II Unit 1006 Heat Load
Island Dunes II Unit 1006
HVAC Load Calculations
for
Island Dunes II Unit 1006
8800 S Ocean Drive
Jensen Beach, Florida 34957
Prepared By:
Eric J. Svoboda, PE
Fort Pierce Engineering, Inc.
315 South 7th Street
Fort Pierce, FL
772-672-4636
Monday, September 14, 2020
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Island Dunes II Unit 1006
Fort Pierce, FL 34950 Page 2
Project Report
General Project Information
Project Title:Island Dunes II Unit 1006
Designed By:Eric J. Svoboda, PE
Project Date:Wednesday, February 18, 2009
Client Name:Island Dunes II Unit 1006
Client Address:8800 S Ocean Drive
Client City:Jensen Beach, Florida 34957
Company Name:Fort Pierce Engineering, Inc.
Company Representative:Eric J. Svoboda, PE
Company Address:315 South 7th Street
Company City:Fort Pierce, FL
Company Phone:772-672-4636
Design Data
Reference City:Fort Pierce, Florida
Building Orientation:Front door faces North
Daily Temperature Range:Medium
Latitude:27 Degrees
Elevation:25 ft.
Altitude Factor:0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter:42 39.4 n/a n/a 72 n/a
Summer:95 80 53%50%75 66
Check Figures
Total Building Supply CFM:1,275 CFM Per Square ft.:0.867
Square ft. of Room Area:1,470 Square ft. Per Ton:468
Volume (ft³) of Cond. Space:13,230
Building Loads
Total Heating Required Including Ventilation Air:20,909 Btuh 20.909 MBH
Total Sensible Gain:28,021 Btuh 74 %
Total Latent Gain:9,685 Btuh 26 %
Total Cooling Required Including Ventilation Air:37,706 Btuh 3.14 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
Z:\ ...\Island Dunes II Unit 1006 Heat Load.rh9 Monday, September 14, 2020, 5:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Island Dunes II Unit 1006
Fort Pierce, FL 34950 Page 3
Load Preview Report
Scope
Net
Ton
ft.²
/Ton Area
Sen
Gain
Lat
Gain
Net
Gain
Sen
Loss
Sys
Htg
CFM
Sys
Clg
CFM
Sys
Act
CFM
Duct
Size
Building 3.14 468 1,470 28,021 9,685 37,706 20,909 266 1,275 1,275
System 1 3.14 468 1,470 28,021 9,685 37,706 20,909 266 1,275 1,275 12x18
Supply Duct Latent 228 228
Return Duct -2 1,870 1,868 483
Zone 1 1,470 28,023 7,586 35,609 20,426 266 1,275 1,275 12x18
1-Kitchen 110 2,331 1,000 3,331 0 0 106 106 1--6
2-Foyer 90 298 126 424 493 6 14 14 1--4
3-Living / Dining 440 9,530 2,331 11,861 6,963 91 434 434 4--6
4-Master Bedroom 260 8,804 1,094 9,898 6,610 86 401 401 4--6
5-Master Closet 50 0 0 0 0 0 0 0 0--0
6-Master Bath 70 237 700 937 0 0 11 11 1--4
7-Bath 40 237 700 937 0 0 11 11 1--4
8-Hall 50 0 0 0 0 0 0 0 0--0
9-Bedroom 190 3,840 779 4,619 4,014 52 175 175 2--5
10-Den 170 2,746 856 3,602 2,346 30 125 125 2--5
Z:\ ...\Island Dunes II Unit 1006 Heat Load.rh9 Monday, September 14, 2020, 5:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Island Dunes II Unit 1006
Fort Pierce, FL 34950 Page 4
System 1 AHU-1 Summary Loads
Component
Description
Area
Quan
Sen
Loss
Lat
Gain
Sen
Gain
Total
Gain
1A-hb-o: Glazing-Single pane, operable window, heat-
absorbing, metal frame with break, u-value 1.08,
SHGC 0.52
318 10,303 0 16,789 16,789
1A-cm-o: Glazing-Single pane, operable window, clear,
metal frame no break, u-value 1.27, SHGC 0.75
72 2,743 0 2,988 2,988
11P: Door-Metal - Polyurethane Core 21 183 0 189 189
13A-5ocs: Wall-Block, board insulation only, R-5 board
insulation, open core, siding finish
241 904 0 612 612
Subtotals for structure:14,133 0 20,578 20,578
People:16 3,200 3,680 6,880
Equipment:2,100 1,800 3,900
Lighting:0 0 0
Ductwork:3,505 2,099 847 2,946
Infiltration: Winter CFM: 99, Summer CFM: 51 3,271 2,286 1,116 3,402
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
System 1 AHU-1 Load Totals:20,909 9,685 28,021 37,706
Check Figures
Supply CFM:1,275 CFM Per Square ft.:0.867
Square ft. of Room Area:1,470 Square ft. Per Ton:468
Volume (ft³) of Cond. Space:13,230
System Loads
Total Heating Required Including Ventilation Air:20,909 Btuh 20.909 MBH
Total Sensible Gain:28,021 Btuh 74 %
Total Latent Gain:9,685 Btuh 26 %
Total Cooling Required Including Ventilation Air:37,706 Btuh 3.14 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
Z:\ ...\Island Dunes II Unit 1006 Heat Load.rh9 Monday, September 14, 2020, 5:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Island Dunes II Unit 1006
Fort Pierce, FL 34950 Page 5
System 1 Room Load Summary
No
Room
Name
Area
SF
Htg
Sens
Btuh
Min
Htg
CFM
Run
Duct
Size
Run
Duct
Vel
Clg
Sens
Btuh
Clg
Lat
Btuh
Min
Clg
CFM
Act
Sys
CFM
---Zone 1---
1 Kitchen 110 0 0 1-6 540 2,331 1,000 106 106
2 Foyer 90 493 6 1-4 155 298 126 14 14
3 Living / Dining 440 6,963 91 4-6 552 9,530 2,331 434 434
4 Master Bedroom 260 6,610 86 4-6 510 8,804 1,094 401 401
5 Master Closet 50 0 0 0-0 0 0 0 0 0
6 Master Bath 70 0 0 1-4 124 237 700 11 11
7 Bath 40 0 0 1-4 124 237 700 11 11
8 Hall 50 0 0 0-0 0 0 0 0 0
9 Bedroom 190 4,014 52 2-5 641 3,840 779 175 175
10 Den 170 2,346 30 2-5 458 2,746 856 125 125
Duct Latent 228
Return Duct 483 -2 1,870
System 1 total 1,470 20,909 266 28,021 9,685 1,275 1,275
System 1 Main Trunk Size:12x18 in.
Velocity:850 ft./min
Loss per 100 ft.:0.101 in.wg
Cooling System Summary
Cooling
Tons
Sensible/Latent
Split
Sensible
Btuh
Latent
Btuh
Total
Btuh
Net Required:3.14 74% / 26%28,021 9,685 37,706
Actual:3.50 70% / 30%29,400 12,600 42,000
Equipment Data
Heating System Cooling System
Type:Direct Exchange Heat Pump Direct Exchange Heat Pump
Model:50PCV042
Indoor Model:50PCV042
Brand:Carrier Carrier
Efficiency:4.3 COP 13.2 EER
Sound:0 0
Capacity:42,000 Btuh 42,000 Btuh
Sensible Capacity:n/a 29,400 Btuh
Latent Capacity:n/a 12,600 Btuh
Z:\ ...\Island Dunes II Unit 1006 Heat Load.rh9 Monday, September 14, 2020, 5:11 PM