HomeMy WebLinkAboutDaugherty Arcade Heat LoadDaugherty Arcade HVAC Load Analysis for Daugherty Arcade 7175 S US Hwy 1 Port St. Lucie, Florida Prepared By: Eric J. Svoboda, PE Fort Pierce Engineering, Inc. 315 South 7th Street Fort Pierce, FL 34950 772-672-4636 Thursday, August 20, 2020 Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 2 General Project Data Input General Project Information Project file name:Daugherty Arcade Heat Load.CH8 Project title:Daugherty Arcade Designed by:Eric J. Svoboda, PE Project date:Monday, July 07, 2008 Weather reference city:FORT PIERCE, FLORIDA, USA Client name:Daugherty Arcade Client address:7175 S US Hwy 1 Client city:Port St. Lucie, Florida Company name:Fort Pierce Engineering, Inc. Company representative:Eric J. Svoboda, PE Company address:315 South 7th Street Company city:Fort Pierce, FL 34950 Company phone:772-672-4636 Company fax:772-672-4637 Barometric pressure:29.894 in.Hg. Altitude:25 feet Latitude:27 Degrees Mean daily temperature range:15 Degrees Starting & ending time for HVAC load calculations:7am - 10pm Number of unique rooms in this project:6 Building Default Values Calculations performed:Both heating and cooling loads Lighting requirements:2.00 Watts per square foot Equipment requirements:1.00 Watts per square foot People sensible load multiplier:245 Btuh per person People latent load multiplier:155 Btuh per person Room sensible safety factor:0 % Room latent safety factor:0 % Room heating safety factor:0 % People diversity factor:100 % Lighting profile number:0 Equipment profile number:0 People profile number:0 Building default ceiling height:12.00 feet Building default wall height:14.00 feet Internal Operating Load Profiles (C = 100) hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 C C C C C C C C C C C C C C C C C C C C C C C C 2 C C C C C C C C C C C C C C C C C C C C C C C C 3 C C C C C C C C C C C C C C C C C C C C C C C C 4 C C C C C C C C C C C C C C C C C C C C C C C C 5 C C C C C C C C C C C C C C C C C C C C C C C C 6 C C C C C C C C C C C C C C C C C C C C C C C C 7 C C C C C C C C C C C C C C C C C C C C C C C C 8 C C C C C C C C C C C C C C C C C C C C C C C C 9 C C C C C C C C C C C C C C C C C C C C C C C C 10 C C C C C C C C C C C C C C C C C C C C C C C C Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 3 General Project Data Input (cont'd) Building-Level Design Conditions Design Month Outdoor Dry Bulb Outdoor Wet Bulb Indoor Rel.Hum Indoor Dry Bulb Grains Diff In/Outdoor Correction August 90 78 50%75 61.09 1 Winter 42 75 Master Roofs Roof No. ASHRAE Roof# Roof U-Fac Dark Color Susp. Ceil 1 1 0.050 No No Roof #1 Description: Metal Roof, R-20 Master Walls Wall No. ASHRAE Group Wall U-Fac Wall Color 1 C 0.095 D Wall #1 Description: Block wall, 8" sand & gravel, hollow core, siding exterior, interior finish, 1" extruded poly, R-5.0 Master Glass Glass No. Summer U-Factor Winter U-Factor Glass Shd.Coef. Interior Shading Interior Shd.Coef 1 0.810 0.830 1.000 1 0.550 Glass #1 Description: Default Glass Master Shading Devices Shade No. Dist Horiz Overh Projects Dist Beyond Right W.Edge Dist Beyond Left W.Edge Dist Overh Above Wind Dist Right Fin Proj Dist R-Fin Beyond W.Edge Ht Of Right Fin Dist Left Fin Proj Dist L-Fin Beyond W.Edge Ht Of Left Fin 1 10.00 50.00 50.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 4 Building Summary Loads Building peaks in August at 3pm. Bldg Load Descriptions Area Quan Sen Loss %Tot Loss Lat Gain Sen Gain Net Gain %Net Gain Roof 6,260 10,329 10.77 0 12,148 12,148 4.79 Wall 1,898 5,950 6.21 0 2,555 2,555 1.01 Glass 370 10,134 10.57 0 10,687 10,687 4.21 Floor Slab 171 3,499 3.65 0 0 0 0.00 Skin Loads 29,912 31.19 0 25,390 25,390 10.01 Lighting 12,520 0 0.00 0 42,720 42,720 16.84 Equipment 6,260 0 0.00 0 21,360 21,360 8.42 Pool Latent 0 0 0.00 0 0 0 0.00 People 105 0 0.00 16,275 25,725 42,000 16.55 Partition 0 0 0.00 0 0 0 0.00 Cool. Pret.1,853 0 0.00 32,442 21,495 53,938 21.26 Heat. Pret.1,853 36,211 37.76 0 0 0 0.00 Cool. Vent.1,853 0 0.00 44,478 9,051 53,529 21.10 Heat. Vent.1,853 29,770 31.05 0 0 0 0.00 Cool. Infil.0 0 0.00 0 0 0 0.00 Heat. Infil.0 0 0.00 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 1,323 1,323 0.52 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap.0 0 0.00 0 13,478 13,478 5.31 Reheat Cap.0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 95,893 100.00 93,195 160,544 253,739 100.00 Building Summary Sen Loss %Tot Loss Lat Gain Sen Gain Net Gain %Net Gain Ventilation 29,770 31.05 44,478 9,051 53,529 21.10 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 36,211 37.76 32,442 21,495 53,938 21.26 Room Loads 29,912 31.19 16,275 128,673 144,948 57.13 Plenum Loads 0 0.00 0 0 0 0.00 Fan/Duct/Misc Loads 0 0.00 0 1,323 1,323 0.52 Building Totals 95,893 100.00 93,195 160,544 253,739 100.00 Check Figures Total Building Supply Air (based on a 21° TD):5,529 CFM Total Building Vent. Air (33.52% of Supply):1,853 CFM Total Conditioned Air Space:6,260 Sq.ft Supply Air Per Unit Area:0.8832 CFM/Sq.ft Area Per Cooling Capacity:296.1 Sq.ft/Ton Cooling Capacity Per Area:0.0034 Tons/Sq.ft Heating Capacity Per Area:15.32 Btuh/Sq.ft Total Heating Required With Outside Air:95,893 Btuh Total Cooling Required With Outside Air:21.14 Tons Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 5 Air Handler #1 - RTU 1 - Summary Loads Rm No Description Room Peak Time Area People Volume Htg.Loss Htg.CFM CFM/Sqft Sen.Gain Clg.CFM CFM/Sqft Lat.Gain S.Exh W.Exh Htg.O.A. Req.CFM Act.CFM Clg.O.A. Req.CFM Act.CFM 1 Front Arcade 2pm August 2,890 50 34,680 16,069 884 0.31 57,158 2,988 1.03 7,750 0 0 Direct 950 884 Direct 950 946 2 Office 3pm August 240 2 2,880 2,638 145 0.60 4,997 261 1.09 310 0 0 Direct 79 145 Direct 79 83 Room Peak Totals: Total Rooms: 2 Unique Rooms: 2 3,130 52 37,560 18,708 1,029 0.33 62,155 3,249 1.04 8,060 0 0 1,029 1,029 1,029 1,029 Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 6 Air Handler #1 - RTU 1 - Total Load Summary Air Handler Description:RTU 1 Constant Volume - Proportion Supply Air Fan:Draw-Thru with program estimated horsepower of 0.31 HP Fan Input:0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio:0.90 --- This system occurs 1 time(s) in the building. --- Air System Peak Time:2pm in August. Outdoor Conditions:Clg: 90° DB, 78° WB, 126.54 grains, Htg: 42° DB Indoor Conditions:Clg: 75° DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss:18,708 Btuh Infiltration sensible loss:0 Btuh 0 CFM Outside Air sensible loss: 15,544 Btuh 1,029 CFM Supply Duct sensible loss:0 Btuh Return Duct sensible loss:0 Btuh Return Plenum sensible loss:0 Btuh Total System sensible loss:34,252 Btuh Heating Supply Air: 18,708 / (.999 X 1.08 X 17) =1,029 CFM Winter Vent Outside Air (100.0% of supply) =1,029 CFM Room space sensible gain:62,152 Btuh Infiltration sensible gain:0 Btuh Draw-thru fan sensible gain:778 Btuh Supply duct sensible gain:0 Btuh Reserve sensible gain:12,063 Btuh Total sensible gain on supply side of coil:74,993 Btuh Cooling Supply Air: 74,993 / (.999 X 1.1 X 21) =3,249 CFM Summer Vent Outside Air (31.7% of supply) =1,029 CFM Return duct sensible gain:0 Btuh Return plenum sensible gain:0 Btuh Outside air sensible gain:4,524 Btuh 1,029 CFM Blow-thru fan sensible gain:0 Btuh Total sensible gain on return side of coil:4,524 Btuh Total sensible gain on air handling system:79,516 Btuh Room space latent gain:8,060 Btuh Infiltration latent gain:0 Btuh Outside air latent gain:21,726 Btuh Total latent gain on air handling system:29,786 Btuh Total system sensible and latent gain:109,302 Btuh Pretreated air sensible loss:21,096 Btuh Pretreated air sensible gain:12,440 Btuh Pretreated air latent gain:20,989 Btuh Check Figures Total Air Handler Supply Air (based on a 21° TD):3,249 CFM Total Air Handler Vent. Air (31.67% of Supply):1,029 CFM Total Conditioned Air Space:3,130 Sq.ft Supply Air Per Unit Area:1.0381 CFM/Sq.ft Area Per Cooling Capacity:343.6 Sq.ft/Ton Cooling Capacity Per Area:0.0029 Tons/Sq.ft Heating Capacity Per Area:10.94 Btuh/Sq.ft Total Heating Required With Outside Air:34,252 Btuh Total Cooling Required With Outside Air:9.11 Tons Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 7 Air Handler #2 - RTU 2 - Summary Loads Rm No Description Room Peak Time Area People Volume Htg.Loss Htg.CFM CFM/Sqft Sen.Gain Clg.CFM CFM/Sqft Lat.Gain S.Exh W.Exh Htg.O.A. Req.CFM Act.CFM Clg.O.A. Req.CFM Act.CFM 3 Rear Arcade 2pm August 2,610 50 31,320 6,108 449 0.17 44,645 1,905 0.73 7,750 0 0 Direct 687 449 Direct 687 689 4 Storage 6pm August 320 1 3,840 3,231 238 0.74 5,182 221 0.69 155 0 0 Direct 84 238 Direct 84 80 5 Women 2pm August 100 1 1,200 413 30 0.30 1,485 63 0.63 155 0 0 Direct 26 30 Direct 26 23 6 Men 5pm August 100 1 1,200 1,452 107 1.07 2,094 89 0.89 155 0 0 Direct 26 107 Direct 26 32 Room Peak Totals: Total Rooms: 4 Unique Rooms: 4 3,130 53 37,560 11,204 824 0.26 53,406 2,279 0.73 8,215 0 0 824 824 824 824 Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Daugherty Arcade Fort Pierce, FL 34950 Page 8 Air Handler #2 - RTU 2 - Total Load Summary Air Handler Description:RTU 2 Constant Volume - Proportion Supply Air Fan:Draw-Thru with program estimated horsepower of 0.22 HP Fan Input:0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio:0.87 --- This system occurs 1 time(s) in the building. --- Air System Peak Time:3pm in August. Outdoor Conditions:Clg: 90° DB, 78° WB, 125.80 grains, Htg: 42° DB Indoor Conditions:Clg: 75° DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss:11,204 Btuh Infiltration sensible loss:0 Btuh 0 CFM Outside Air sensible loss: 14,226 Btuh 824 CFM Supply Duct sensible loss:0 Btuh Return Duct sensible loss:0 Btuh Return Plenum sensible loss:0 Btuh Total System sensible loss:25,430 Btuh Heating Supply Air: 11,204 / (.999 X 1.08 X 13) =824 CFM Winter Vent Outside Air (100.0% of supply) =824 CFM Room space sensible gain:53,150 Btuh Infiltration sensible gain:0 Btuh Draw-thru fan sensible gain:546 Btuh Supply duct sensible gain:0 Btuh Reserve sensible gain:1,415 Btuh Total sensible gain on supply side of coil:55,111 Btuh Cooling Supply Air: 55,111 / (.999 X 1.1 X 22) =2,279 CFM Summer Vent Outside Air (36.2% of supply) =824 CFM Return duct sensible gain:0 Btuh Return plenum sensible gain:0 Btuh Outside air sensible gain:4,528 Btuh 824 CFM Blow-thru fan sensible gain:0 Btuh Total sensible gain on return side of coil:4,528 Btuh Total sensible gain on air handling system:59,639 Btuh Room space latent gain:8,215 Btuh Infiltration latent gain:0 Btuh Outside air latent gain:22,752 Btuh Total latent gain on air handling system:30,967 Btuh Total system sensible and latent gain:90,606 Btuh Pretreated air sensible loss:15,115 Btuh Pretreated air sensible gain:9,056 Btuh Pretreated air latent gain:11,453 Btuh Check Figures Total Air Handler Supply Air (based on a 22° TD):2,279 CFM Total Air Handler Vent. Air (36.15% of Supply):824 CFM Total Conditioned Air Space:3,130 Sq.ft Supply Air Per Unit Area:0.7282 CFM/Sq.ft Area Per Cooling Capacity:414.5 Sq.ft/Ton Cooling Capacity Per Area:0.0024 Tons/Sq.ft Heating Capacity Per Area:8.12 Btuh/Sq.ft Total Heating Required With Outside Air:25,430 Btuh Total Cooling Required With Outside Air:7.55 Tons Z:\ ...\Daugherty Arcade Heat Load.CH8 Thursday, August 20, 2020, 01:53 PM