HomeMy WebLinkAboutBuilding Plan ReviewST. LUCIE COUNTY -FT PIERCE FIRE DISTRICT
BUILDING PLAN REVIEW
P. O. BOX 3030
Ft. Pierce, FL 34948-3030 Telephone: 407.462-2312
FAX: 407-462-2325
JURISDICTION: St Lucie County_____ FPB #:
6558
PROJECT NAME: Donnick Storage_ BLDG DEPT #:
CONTRACTOR:
96050347
Paul Jacquin PHONE #:
ARCHITECT: Kendall Starrat
561-465-2475
_ PHONE #:
BUILDING OWNER: Tom Donnick REVIEW DATE:
561-464-1691
5-29-96
BUILDING LOCATION: 3504 Industrial 27th # OF STORIES:
1
OCCUPANCY TYPE: Storage AUTO SPKLS:
GROSS SO FOOTAGE: 4000 sq ft
Yes No X
—
NET SO FT:
OCCUPANT LOAD:
BASED ON:
CONSTRUCTION TYPE: NFPA #220 (000) SBCCI
sq ft per person
_II _ ,
_IV(un)
NEW CONSTRUCTION X_TENANT IMPROV
NOVREATION ******* *********************** *** ************* *******NOV*************ADD*_**ON*******SHELL
ALL REVISIONS LISTED MUST BE IN COMPLIANCE BEFORE
NL **x*******
THE FINAL
The Fire Marshal requires 24 hour
INSPECTION.
notice on all inspections.
The Building Department schedules all final inspections.
I. Provide a minimum of two remote exterior exits.
2. Provide an illuminated exit sign above each exterior exit.
3. Because emergency lighting is required, the required exit signs shall be provided with a
90 minute battery back up.
4. Provide a 3A-40BC rated fire extinguisher for each 75' of travel.
REVIEWED BY: '
DATE:
Sheet — of